Introduction 

The i3000s 24 Flex, i3000s 36 Flex, and i2000 Flex AC Current 
Probes (hereafter referred to as “the Probe”) are used with 
oscilloscopes, digital multimeters, recorders or data loggers. The 
i3000s probes can be used to measure AC current up to 3000 A. 
The i2000 can be used to measure AC current up to 2000 A. The 
flexible measuring head allows current measurements on 
conductors that are hard to reach or inaccessible using typical 
clamp-on current probes. 

The Probes provide a low-voltage (3 V AC for i3000s models, 
and 2 V AC for i2000) output that is proportional to the current 
being measured. The Probes provide full-scale direct readings for 
30 A, 300 A, and 3000 A when using the i3000s models, and 20 
A, 200 A, and 2000 A when using the i2000. 

Symbols 

The following table shows the symbols used on the product 
and/or in this manual. 

Symbol Description 

~

 

Do not dispose of this product as unsorted municipal 
waste. Contact Fluke or a qualified recycler for 
disposal. 

W

 

Important Information. Refer to the manual. 

T

 

Double/Reinforced insulation. 

-

 

Do not apply around or remove from the HAZARDOUS 
LIVE conductors. 

P

 

Complies with the relevant European standards. 

>

 

Conforms to Underwriters’ Laboratory, Inc. 

PN 2560447 
March 2006 

©2006 Fluke Corporation. All rights reserved.  

Содержание i2000 Flex

Страница 1: ...for i3000s models and 2 V AC for i2000 output that is proportional to the current being measured The Probes provide full scale direct readings for 30 A 300 A and 3000 A when using the i3000s models and 20 A 200 A and 2000 A when using the i2000 Symbols The following table shows the symbols used on the product and or in this manual Symbol Description Do not dispose of this product as unsorted munic...

Страница 2: ... protective clothing and gloves as required Do not install this product on live conductors Always de energize the circuit under test before installing the flexible measuring head Always inspect the electronics unit connecting cable and flexible measuring head for damage before using the Probe Do not use the Probe if damaged Always connect Probe to display device before installing the flexible meas...

Страница 3: ...racteristics Measuring ranges i3000s 24 and 36 Flex i2000 Flex 30 A 300 A 3000 A AC switch selectable 20 A 200 A 2000 A AC switch selectable Output sensitivity 100 mV 10 mV 1 mV per A AC coupled Accuracy at 25 ºC 1 of range 45 65 Hz Frequency range i3000s 24 and 36 Flex i2000 Flex 10 Hz to 50 kHz 3 dB 10 Hz to 20 kHz 1 dB Phase error 1 45 65 Hz 10 at 20 kHz Linearity 0 2 of reading from 10 100 of ...

Страница 4: ...kaline batteries all probes Or an optional Class II external power supply 3 V i3000 and i3000s Battery life i3000s 24 and 36 Flex i2000 Flex 400 hours typical 200 hours typical Low battery Indicated by a red LED General Characteristics Enclosure IP5X flame retardant UL94 VO rated Material Valox 357 Output con i3000s 24 and 36 Flex i2000 Flex Coaxial cable with a male safety BNC connector BNC to Ba...

Страница 5: ...e insulated Cable diameter 14 3 mm 0 562 in Bend radius 38 1 mm 1 5 in Output cable 2 m long 78 7 in Coupling diameter 22 2 mm 0 875 in Material TPE rubber Polypropylene UL94 VO rated Operating temperature 20 C to 90 C 4 F to 194 F Storage temperature 40 C to 105 C 40 F to 221 F Maximum relative humidity 85 Weight 0 18 kg 0 4 Ib Safety BS EN 61010 1 600 V CAT III Pol Deg 2 ...

Страница 6: ...perating Instructions Ieb0001 eps A Measuring head B Measuring head coupling C Head output cable D Enclosure E Power on Range selector F Battery low indicator G Power on indicator H Output cable I Safety BNC connector J External power supply input ...

Страница 7: ...at the output is disconnected from other equipment To install the battery 1 Use a coin or a similar tool to turn the battery lock turn until the dot aligns with the unlock symbol 2 Remove the battery cover 3 Install the batteries ensuring that correct polarity is observed 4 Replace the battery cover and turn the battery lock until the dot aligns with the lock symbol External Power Supply i3000s Mo...

Страница 8: ...nductors with a potential of over 600 V 2 Wrap the flexible measuring head around the conductor to be tested in a close coupling manner 3 Energize the circuit under test 4 For most accurate measurement centre the flexible head around the conductor 5 Locate coupling away from the nearby conductors WX Warning To avoid electric shock or injury Do not use the flexible current probe to measure bare con...

Страница 9: ...reases Momentary lighting of LED indicates batteries are good Continuous lighting of LED indicates low battery and requires replacement at the earliest No lighting of LED indicates batteries are dead and require replacement immediately Maintenance WX Warning To avoid electric shock or injury do not use Probe if damaged Always inspect the electronics unit connecting cable and flexible measuring hea...

Страница 10: ...est Fluke authorized service center to obtain return authorization information then send the product to that Service Center with a description of the problem THIS WARRANTY IS YOUR ONLY REMEDY NO OTHER WARRANTIES SUCH AS FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSED OR IMPLIED FLUKE IS NOT LIABLE FOR ANY SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES ARISING FROM ANY CAUSE OR THEOR...

Отзывы: