Essentials for Reliable Fiber Test Results
Table 2. Fiber Test Settings (cont.)
Setting Description
SETUP > Fiber >
Test Method >
Method A, B, C
Loss results include connections added after referencing. The reference and test connections determine
which connections are included in results. The Test Method refers to the number of end connections
included:
Method A: Loss results include one connection at one end of the link.
Method B: Loss results include connections at both ends of the link. The reference and test connections
shown in this manual produce Method B results, but are modified versions of connections shown in the
standards. The modified connections let you connect to links that do not use SC connectors, while
ensuring Method B results. For links with small form-factor (SFF) connectors or different connector types
at each end, use hybrid patch cords or alternate reference and test connections. See the Technical
Reference Handbook or visit the Fluke Networks Knowledge Base for suggestions.
Method C: Loss results exclude connections at the ends of the link. Only the fiber loss is measured.
Different standards have different names for the three test methods. See Appendix A for details. The
Technical Reference Handbook provides additional information on test methods.
This setting does not affect loss results. It is only saved with the results to record which method you used.
-continued-