5  Fluke Corporation     Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

Product specifications

Model

Measurement range

Resolution

Accuracy

Volt

Vrms (ac+dc)

434-II

1 V to 1000 V phase to neutral

0.1 V

± 0.5 % of nominal voltage****

435-II and 437-II

1 V to 1000 V phase to neutral

0.01 V

± 0.1 % of nominal voltage****

Vpk

1 Vpk to 1400 Vpk

1 V

5 % of nominal voltage

Voltage Crest Factor (CF)

1.0 > 2.8

0.01

± 5 % 

Vrms½

434-II

1 V to 1000 V phase to neutral

0.1 V

± 1 % of nominal voltage

434-II  and 435-II

0.1 V

± 0.2 % of nominal voltage

Vfund

434-II

1 V to 1000 V phase to neutral

0.1 V

± 0.5 % of nominal voltage

435-II and 437-II

0.1 V

± 0.1 % of nominal voltage

Amps (accuracy excluding clamp accuracy)

Amps (ac +dc)

i430-Flex 1x

5 A to 6000 A

1 A

± 0.5 % ± 5 counts

i430-Flex 10x

0.5 A to 600 A

0.1 A

± 0.5 % ± 5 counts

1mV/A 1x

5 A to 2000 A

1A

± 0.5 % ± 5 counts

1mV/A 10x

0.5 A A to 200 A (ac only)

0.1 A

± 0.5 % ± 5 counts

Apk

i430-Flex

8400 Apk

1 Arms

± 5 % 

1mV/A

5500 Apk

1 Arms

± 5 % 

A Crest Factor (CF)

1 to 10

0.01

± 5 % 

Amps½

i430-Flex 1x

5 A to 6000 A

1 A

± 1 % ± 10 counts

i430-Flex 10x

0.5 A to 600 A

0.1 A

± 1 % ± 10 counts

1mV/A 1x

5 A to 2000 A

1A

± 1 % ± 10 counts

1mV/A 10x

0.5 A A to 200 A (ac only)

0.1 A

± 1 % ± 10 counts

Afund

i430-Flex 1x

5 A to 6000 A

1 A

± 0.5 % ± 5 counts

i430-Flex 10x

0.5 A to 600 A

0.1 A

± 0.5 % ± 5 counts

1mV/A 1x

5 A to 2000 A

1A

± 0.5 % ± 5 counts

1mV/A 10x

0.5 A A to 200 A (ac only)

0.1 A

± 0.5 % ± 5 counts

Hz
Hz

Fluke 434 @ 50 Hz nominal

42.50 Hz to 57.50 Hz

0.01 Hz

± 0.01 Hz

Fluke 434 @ 60 Hz nominal

51.00 Hz to 69.00 Hz

0.01 Hz

± 0.01 Hz

Fluke 435/7 @ 50 Hz nominal

42.500 Hz to 57.500 Hz

0.001 Hz

± 0.01 Hz

Fluke 435/7 @ 60 Hz nominal

51.000 Hz to 69.000 Hz

0.001 Hz

± 0.01 Hz

Fluke 437 @ 400 Hz nominal

340.0 Hz to 460.0 Hz

0.1 Hz

± 0.1 Hz

Power
Watts (VA, var)

i430-Flex

max 6000 MW

0.1 W to 1 MW

± 1 % ± 10 counts

1 mV/A 

max 2000 MW

0.1 W to 1 MW

± 1 % ± 10 counts

Power factor (Cos j/DPF)

0 to 1

0.001

± 0.1 % @ nominal load conditions

Energy
kWh (kVAh, kvarh)

i430-Flex 10x

Depends on clamp scaling and V nominal

± 1 % ± 10 counts

Energy loss

i430-Flex 10x

Depends on clamp scaling and  V nominal

± 1 % ± 10 counts 

Excluding line resistance accuracy

Harmonics
Harmonic order (n)

DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7

Inter-harmonic order (n)

OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7

Volts

%f

0.0 %  to  100 %

0.1 %

± 0.1 % ± n x 0.1 %

%r

0.0  % to 100 %

0.1 %

± 0.1 % ± n x 0.4 %

Absolute

0.0 to 1000 V

0.1 V

± 5 % * 

THD

0.0 %  to  100 %

0.1 %

± 2.5 %

Amps

%f

0.0 %  to  100 %

0.1 %

± 0.1 % ± n x 0.1 %

%r

0.0 %  to  100 %

0.1 %

± 0.1 % ± n x 0.4 %

Absolute

0.0 to 600 A

0.1 A

± 5 % ± 5 counts

THD

0.0 %  to  100 %

0.1 %

± 2.5 %

Watts

%f or %r

0.0 %  to  100 %

0.1 %

± n x 2 %

Absolute

Depends on clamp scaling and V nominal

± 5 % ± n x 2 % ± 10 counts

THD

0.0 %  to  100 %

0.1 %

± 5 %

Phase Angle

-360° to +0° 

± n x 1° 

Shop for Fluke products online at:

1.877.766.5412

www.

MyFlukeStore

.com

Содержание 435-II

Страница 1: ...models capture 100 120 cycles 50 60Hz of each event that is detected in all modes without set up Automatic Transient Mode 435 and 437 Series II analyzers capture 200 kHz waveform data on all phases s...

Страница 2: ...fect of unevenly loading each phase in three phase systems Unbalance can often be corrected by reconnect ing loads on different phases to ensure the current drawn on each phase is as equal as possible...

Страница 3: ...luded i430flex TF with sensitivity 10x 5 Arms to 6000 Arms with included i430flex TF with sensitivity 1x 0 1 mV A to 1 V A and custom for use with optional ac or dc clamps Input impedance 1 M Bandwidt...

Страница 4: ...z Transients 435 II and 437 II only Transient waveforms 4x Voltage 4x Amps triggers Vrms Arms Pinst Mains Signaling 435 II and 437 II only Relative signaling voltage and absolute signaling voltage ave...

Страница 5: ...mV A 1x 5 A to 2000 A 1A 0 5 5 counts 1mV A 10x 0 5 A A to 200 A ac only 0 1 A 0 5 5 counts Hz Hz Fluke 434 50 Hz nominal 42 50 Hz to 57 50 Hz 0 01 Hz 0 01 Hz Fluke 434 60 Hz nominal 51 00 Hz to 69 00...

Страница 6: ...alue over 10 12 cycle period var Fundamental reactive power display Calculates reactive power on fundamental positive sequence components Capacitive and inductive load is indicated with capacitor and...

Страница 7: ...g and Monitor Mode for nominal voltage 50 V to 500 V Wiring configurations 1 NEUTRAL Single phase with neutral 1 SPLIT PHASE Split phase 1 IT NO NEUTRAL Single phase system with two phase voltages wit...

Страница 8: ...subject to change without notice Printed in U S A 8 2011 2643006D D EN Pub ID 11858 eng Modification of this document is not permitted without written permission from Fluke Corporation Flexible Curre...

Отзывы: