05-450
Users Manual
6
Temperature range
.................................................. -20
°
C to 50
°
C (-4
°
F to 122
°
F). May be certified for operation from
-40
°
C to 65
°
C (-40
°
F to 150
°
F)
Maximum relative humidity
.................................... Less than 95% (non-condensing)
Size
Electronics (H x W x D) .......................................... 24.6 cm x 18.7 cm x 6.4 cm (9.7 in x 7.4 in x 2.5 in)
Detectors (H x W x D) ............................................ 33 cm x 43.2 cm x 21.6 cm (13 in x 17 in x 13 in)
Weight
Electronics ............................................................. 2.36 kg (5.2 lb)
Detectors ............................................................... 14.5 kg (32 lb)
Indoor use only
Maximum altitude
..................................................... 5000 m (120 V nominal), 2000m (220 V nominal)
Safety
........................................................................ IEC 61010-1, Overvoltage category II, Pollution degree 2.
Electromagnetic Compatibility (EMC)
.................... IEC 61326-1 (Basic EM environment); CISPR 11, Group 1, Class A
Group 1 equipment: group 1 has intentionally generated and/or use
conductively coupled radio-frequency energy which is necessary for
the internal functioning of the equipment itself.
Class A equipment is equipment suitable for use in all
establishments other than domestic and those directly connected to
a low voltage power supply network which supplies buildings used
for domestic purposes. Caution - There may be potential difficulties
in ensuring electromagnetic compatibility in other environments, due
to conducted and radiated disturbances.
USA (FCC)
................................................................ 47 CFR 15 subpart B, this product is considered an exempt device
per clause 15.103
Korea (KCC)
............................................................. Class A Equipment (Industrial Broadcasting & Communication
Equipment)
This product meets requirements for industrial (Class A)
electromagnetic wave equipment and the seller or user should take
notice of it. This equipment is intended for use in business
environments and not to be used in homes.
Driver Option Specification
Power Required
........................................................ 7.5 V dc at 100 mA; minimum V
in
= 5.5 V and maximum V
in
= 15 V
Terminating Resistor
............................................... 250
Ω
Recorder Output Connections (9-pin D-sub connector)
Pin 5 is SIG, current output (was voltage output)
Pin 6 is LGND, Isolated Loop Return or Loop Ground
Board Header Pinout
P1-1) .................................................................. Loop GND (Isolated)
P1-2) .................................................................. 4 mA to 20 mA current output (Isolated)
P2-1) .................................................................. +7.5 V dc , RAWDC from main circuit board (LMI PN: 5396-160)
(May range from +5.5 V dc to 15 V dc)
P2-2) .................................................................. GND
P2-3) .................................................................. RCDR voltage in or analog input (0 V dc -1.25 V dc)
Содержание 05-450
Страница 8: ...05 450 Users Manual iv...
Страница 10: ...05 450 Users Manual 2 huk01 eps Figure 1 Front Panel...
Страница 29: ...Digital Doorway Monitor Drawings 21 M3503_3530_375 30 Enclosure Figure 5 Detector Enclosure 385x106...
Страница 30: ...05 450 Users Manual 22 375 30_3530 Detector Mounting Figure 6 Detector Mounting 385x120...
Страница 32: ...05 450 Users Manual 24...