HF074AEN_v0403_04 Atex_IECEx_CSA_FM
Page 31
Configuration example no. 2
Fig. 17: Configuration example Intrinsically Safe.
Configuration example no. 3
Fig. 18: Configuration example Intrinsically Safe.
Configuration example IIA - IIB and IIC application - F074-A-OT-PD-XI-ZB
TERMINAL CONNECTORS
F0-series
HAZARDOUS AREA
SAFE AREA
*Sensor supply voltage for analog flowmeter type A / U: Terminal 6: as input voltage terminal 5 (internally linked).
Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.
12
Common ground
Signal
C
irc
ui
t depends
on
ty
pe
of
si
gnal
7
8
Common ground
6
4
5
Common ground
Main supply
Supply *
9
10
Common ground
Supply backlight
Power supply type PD: 16-30V DC
Backlight option: type ZB
+
-
Power supply
For example
MTL5025
+
-
Power supply or
switch interface
For example
MTL5025
MTL5011B
+
-
Power supply
For example
MTL5025
= max. 30 V
= max. 200 mA
= max. 1,2 W
Uo
Io
Po
= max. 30 V
= max. 200 mA
= max. 1,2 W
Uo
Io
Po
= max. 30 V
= max. 200 mA
= max. 0,75 W
Uo
Io
Po
Note: above values are safety values.
Consult the technical specification for operational values.
Alarm output type OT: passive transistor
I.S. level sensor - input type A: (0)4-20mA
e.g. relay
Intrinsically Safe apparatus
Configuration example IIA - IIB and IIC application - F074-A-OT-PL-XI-ZB
TERMINAL CONNECTORS
F0-series
12
Common ground
Signal
C
irc
ui
t de
pends
on
ty
pe of
si
gnal
7
8
Common ground
9
10
Common ground
Supply backlight
HAZARDOUS AREA
SAFE AREA
+
-
Power supply or
switch interface
For example
MTL5025
MTL5011B
+
-
Power supply
For example
MTL5025
= max. 30 V
= max. 200 mA
= max. 1,2 W
Uo
Io
Po
= max. 30 V
= max. 200 mA
= max. 0,75 W
Uo
Io
Po
Note: above values are safety values.
Consult the technical specification for operational values.
+
-
Power supply
For example
MTL5025
= max. 30 V
= max. 93 mA
= max. 0,92 W
Uo
Io
Po
Backlight option: type ZB
Sensor supply is not available: unit is input loop powered (type PL).
Please note: type PL may be used in combination with the battery (type PC). PL will power the unit; the battery will be disabled automatically till power is disconnected.
Alarm output type OT: passive transistor
I.S. level sensor - input type A-PL: 4-20mA loop powered
e.g. relay
Intrinsically Safe apparatus