 11   12 

an approved 

associated 

apparatus 

 4   5   6 

an approved 

associated 

apparatus 

 9   10 

an approved 

associated 

apparatus 

 7   8 

an approved 

associated 

apparatus 

optional 

hazardous 

location 

apparatus 

Certification F0-SERIES 

 Type -XI  

 

Certificate number: CSA.08.2059461 

Intrinsically Safe for Class I/II/III, Division 1 
Groups A,B,C,D,E,F,G. Temperature class T4 

Class I, Zone 0, AEx ia IIC T4 

 

 

Project ID: 3033306 
Intrinsically Safe for Class I/II/III, Division 1 

Groups A,B,C,D,E,F,G. Temperature class T4 
Class I, Zone 0, AEx ia IIC T4 

 

 

 

HAZARDOUS AREA

 

 

 

 

SAFE AREA

 

  

 

Control drawing number:  FWCD-0001 

Revision: 1.1 

Date: May 5

th

, 2014 

  

optional 

hazardous 

location 

apparatus 

 1 

 

3

 

 2 

an approved 

associated 

apparatus 

Control Drawing F0xx-A-XI 

The installation must comply with national requirements (e.g. in Canada, the Canadian Electrical Code, Part 1 
Appendix F and in USA, the National Electrical Code, NFPA 70, Article 504 and ANSI/ISA-RP 12.6). 

Warning: Substitution of components may impair intrinsic safety. 

For the circuits connected to terminals 1 and 2, 4 and 5, 7 and 8, 9 and 10, the output parameters of the 
connected barriers (up to 4) or hazardous location apparatus must meet the following requirements: 

Voc  

≤   The lowest Vmax of the CSA / FM Approved apparatus in the circuit 

Isc  

≤   The lowest Imax of the CSA / FM Approved apparatus in the circuit 

Pmax  

≤   The lowest Pmax of the CSA / FM Approved apparatus in the circuit 

Ca  

≥   The sum of the cable capacitance and the internal capacitance Ci of each CSA / FM Approved 

apparatus installed in the circuit 

La  

≥   The sum of the cable inductance and the internal inductance Li of each CSA / FM Approved 

apparatus installed in the circuit 

For the circuits connected to terminals 1 and 2, 4 and 6, 7 and 8, 11 and 12, the input parameters of the 
connected hazardous location apparatus must meet the following requirements: 

Vmax  

≥   The Voc of the of the circuit 

Imax  

≥   The Isc of the circuit 

Pmax  

≥   The Pmax of the circuit 

Ci  

≤   The difference between the Ca of the circuit and the sum of the cable capacitance and the internal 

capacitance Ci of all other CSA / FM Approved apparatus installed in the circuit 

Li  

≤   The difference between the La of the circuit and the sum of the cable inductance and the internal 

inductance Li of all other CSA / FM Approved apparatus installed in the circuit 

Hazardous Location Apparatus 

– switches, thermocouples or non-inductive resistance devices, or CSA / FM – 

Certified Apparatus 

– should be connected in accordance with the manufacturer’s installation instructions. 

The cable parameters are determined by the parameters of the system into which the F0-Series General Purpose 
Indicators is connected. 

Only certified Intrinsically Safe Fluidwell battery type FW-LiBat-0xx may be used and replaced in hazardous area. 

The entity parameters for F0-Series General Purpose Indicators, model F0xx-A-XI, are as follows: 

Terminals 1 and 2 

– Input parameters: 

Vmax   =   30 V 

Ci   =   0 nF 

Imax  

=   150 mA 

Li   =   0 mH 

Pmax   =   0.92 W 

 

Terminal 3 

– Internally not connected 

Terminal 4 and 5 

– Input parameters – Type -PD/-PX  

Vmax   =   30 V 

Ci   =   0 nF 

Imax  

=   200 mA 

Li   =   0 mH 

Pmax   =   1.2 W 

 

Terminal 4 and 6 

– Output parameters – Type -PD  

Voc, Isc, Pmax, Ca and La are equal to those of the 
circuitry connected between terminals 4 and 5. 

Terminal 7 and 8 

– Input parameters – Type -OT 

Vmax   =   30 V 

Ci   =   0 nF 

Imax  

=   200 mA 

Li   =   0 mH 

Pmax   =   1.2 W 

Terminal 9 and 10 

– Input parameters – Type -ZB 

Vmax   =   30 V 

Ci   =   0 nF 

Imax  

=   200 mA 

Li   =   0 mH 

Pmax   =   0.75 W 

Terminal 11 and 12 

– Input parameters – Type -AH 

Vmax   =   30 V 

Ci   =   6.1 nF 

Imax  

=   100 mA 

Li   =   0 mH 

Pmax   =   0.75W 

common ground 

TERMINAL CONNECTORS F0-SERIES 

5.2.3 

ELECTRICAL DATA 

– CONTROL DRAWING 

 

Содержание F053-A

Страница 1: ...ATOR WITH HIGH LOW PRESSURE ALARMS Signal input sensor 0 4 20mA Alarm output one pressure alarm Options Intrinsically Safe F Series Field mounted indicators for safe and hazardous areas More info www...

Страница 2: ...ot be disposed of into the general waste system or into a landfill At the end of its life equipment shall be disposed of according to the local regulations regarding waste of the electrical and the el...

Страница 3: ...amage of the F053 A or connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F053 A or connected...

Страница 4: ...ding conditions 17 4 3 Handling the F Series enclosure 18 4 3 1 Identification 18 4 3 2 Opening Removing the cover 20 4 3 3 Closing Replacing the cover 20 4 4 Mechanical installation 21 4 4 1 Dimensio...

Страница 5: ...mples Intrinsically Safe applications 38 5 4 1 F053 A OT PX XI ZB Ex ia IIC IIIC 38 5 4 2 F053 A OT PD XI ZB Ex ia IIC IIIC 38 5 4 3 F053 A OT PL XI ZB Ex ia IIC IIIC 39 6 MAINTENANCE 40 6 1 General d...

Страница 6: ...sor several options are available Fig 1 Typical application for the F053 A Configuration of the F053 A The F053 A has been designed to be implemented in many types of applications For that reason a SE...

Страница 7: ...ion CLEAR key This key is used to SELECT the displayed information 2 3 OPERATOR INFORMATION AND FUNCTIONS In general the F053 A will always function at Operator level The information displayed is depe...

Страница 8: ...Pressure alarm When the actual pressure is outside the allowed range an alarm message will be displayed indicating the type of alarm LO PRESSURE HI PRESSURE The alarm is terminated automatically as so...

Страница 9: ...ill active Make sure that the unit is not being used for any application when altering the settings 3 2 1 ENTERING SETUP LEVEL Configuration of the F053 A is done at SETUP level which can be reached a...

Страница 10: ...ch function that needs to change navigate to that function and follow the steps indicated below During the programming sequence the display will deactivate the SETUP indicator and activate the PROGRAM...

Страница 11: ...key During the programming sequence this key is used to confirm the new value and return to SETUP level To cancel the operation either press the PROG key for 3 seconds or wait for 20 seconds the progr...

Страница 12: ...RM HIGH 0000 000 9 999 999 2 4 DELAY ALARM LOW 0 1 999 9 seconds 2 5 DELAY ALARM HIGH 0 1 999 9 seconds 2 6 ALARM OUTPUT high low both off 3 DISPLAY 3 1 SET ALARM operator setup 3 2 BACKLIGHT optional...

Страница 13: ...ssure signal is zero below 4mA then it is possible to ignore or disable the low pressure alarm The following settings can be selected DEFAULT in case of a low pressure alarm and no signal it will swit...

Страница 14: ...over a long period of time The F053 A has several smart power management functions to extend the battery life time significantly Two of these functions are available SETUP FUNCTIONS AND VARIABLES 4 PO...

Страница 15: ...1 8 03 0 5 1 0 1 5 3 0 05 1 0 1 8 2 8 5 3 10 1 8 3 5 5 6 11 20 3 5 7 0 11 23 30 5 3 10 17 34 50 8 8 17 29 57 75 13 26 43 86 99 17 34 57 114 5 3 CUT OFF To ignore pressure drift a low level cut off can...

Страница 16: ...nalog value must be less than the calibrated value for reliable measurements DEFAULT with this setting the factory value is re installed CAL SET to select the last calibrated value 3 3 7 EXPLANATION O...

Страница 17: ...e g F053 A XF Follow the electrical installation instructions as shown in chapter 4 and the mechanical installation instructions of the enclosure that are supplied separately Type XI Suitable for int...

Страница 18: ...y your F0 Series device all field mount enclosures have a weatherproof identification label placed on the outside of the unit Fig 7 Identification Example of F0 Series identification label safe area I...

Страница 19: ...fe area Type PM or PF Serial number and year of production The serial number can be reviewed on the identification label or in SETUP menu Others The production date is either shown separately on the l...

Страница 20: ...heir mating parts and the front cover is now completely separate 4 3 3 CLOSING REPLACING THE COVER To replace the cover on the F Series enclosure follow this procedure 1 Re insert all terminals to the...

Страница 21: ...rt B after H HBx Fig 10 Dimensions Aluminum and stainless steel enclosures 75 mm 2 95 130 mm 5 12 112 mm 4 40 60 mm 2 36 120 mm 4 72 M20 x 1 5 PG9 PG9 30mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30...

Страница 22: ...mm 5 12 112 mm 4 40 60 mm 2 36 120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 2...

Страница 23: ...ng the mounting plate please follow the instructions that came with the accessories Alternatively the unit can be panel mounted by using only the front cover Wall mount by using the openings on the ou...

Страница 24: ...ack panel The metal front panel is connected to the Protective Earth by the mounting screws and serrated washers The wire screens shield are meant to prevent electromagnetic interference and shall be...

Страница 25: ...tional Rules and Regulations When a power supply is connected to the field wiring connections please also consider the demands for power supply wiring shown in paragraph 4 5 4 The installation must co...

Страница 26: ...PM Terminal 7 sensor supply 8 2V 12V or 24V Type PF and PM offer a power supply for the sensor The sensor can be externally powered with 8 2V 12V or 24V DC max 400mA 24V The voltage is selected with t...

Страница 27: ...53 A Type PB PD PL PX Fig 15 Overview of terminal connectors F053 A type PB PD PL PX 4 6 1 TERMINALS 1 2 SENSOR INPUT The F053 A requires a 0 4 20mA sensor signal which will be processed 4 times a sec...

Страница 28: ...th this option Max driving capacity 300mA 50V DC Fig 17 Terminal connections Passive transistor output Type OT 4 6 4 TERMINAL 9 10 POWER SUPPLY BACKLIGHT TYPE ZB OPTION To power the backlight a voltag...

Страница 29: ...ies are connected can cause ground loop currents that could damage the equipment See paragraph 4 5 2 Protective Earth PE connections for more information 4 7 2 TERMINALS 3 4 ALARM OUTPUT Type OT A pas...

Страница 30: ...053 A requires a 0 4 20mA sensor signal which will be processed 4 times a second with a 16 bit accuracy The input is not isolated The screen of the signal wire can be connected to the common ground te...

Страница 31: ...r F0 Series device all field mount enclosures have a weatherproof identification label placed on the outside of the unit Fig 24 Identification Example of F0 Series identification label intrinsic safet...

Страница 32: ...sh discharges For reasons of ESD and safety always ground the metal enclosure properly as indicated in section 4 5 Electrical installation of this manual Do not blend metal front covers with non metal...

Страница 33: ...uits connected to terminals 1 and 2 4 and 6 7 and 8 11 and 12 the input parameters of the connected hazardous location apparatus must meet the following requirements Vmax The Voc of the of the circuit...

Страница 34: ...ircuit For the circuits connected to terminals 1 and 2 4 and 6 7 and 8 11 and 12 the input parameters of the connected hazardous location apparatus must meet the following requirements Vmax The Voc of...

Страница 35: ...cuits precautions must be taken to separate the Intrinsically safe circuits in accordance with EN 60079 11 For electrical data consult Annex 1 for this F0 Series model on the following page Substituti...

Страница 36: ...c safety Ex ia IIC IIIC only for connection to a certified intrinsically safe circuit with following maximum values Ui 30 V Ii 200 mA Pi 1 2 W Li 0 mH Ci 0 nF External supply output circuit Type PD te...

Страница 37: ...ea Type PX as standard all intrinsically safe products are supplied with terminal 4 and 5 to power the product externally Type PC offers additional to type PX an internal Intrinsically Safe lithium ba...

Страница 38: ...pplication F053 A OT PD XI ZB TERMINAL CONNECTORS F0 series HAZARDOUS AREA SAFE AREA Sensor supply voltage for analog flowmeter type A U Terminal 6 as input voltage terminal 5 internally linked Please...

Страница 39: ...backlight HAZARDOUS AREA SAFE AREA Power supply or switch interface For example MTL5025 MTL5011B Power supply For example MTL5025 max 30 V max 200 mA max 1 2 W Uo Io Po max 30 V max 200 mA max 0 75 W...

Страница 40: ...play update uses significantly more power Pulse output Low temperatures the available power will be less due to battery chemistry Check periodically The condition of the casing cable glands and front...

Страница 41: ...ons Intrinsically safe applications Type PC Only batteries of type FW LiBAT 021 that hold the Ex marking as shown below are suitable replacements and certified for use in hazardous areas Before replac...

Страница 42: ...the battery connector to prevent a short circuit Fig 32 Battery replacement procedure Install the new battery as follows 1 Make sure the new battery is undamaged in good condition and suitable for us...

Страница 43: ...31mm 1 22 IP65 TYPE 4X Plastic GRP panel mount enclosure Weight 450gr Aluminum Stainless Steel panel mount enclosure Weight 600gr Field wall mount enclosures Dimensions with extended back Classificat...

Страница 44: ...s Data retention at least 10 years Password Configuration settings can be password protected Hazardous area option Intrinsically safe Type XI ATEX approval KEMA 05ATEX1168 X II 1 G Ex ia IIC T4 Ga II...

Страница 45: ...solated Load max 50V DC 300mA Type OA One active 24V DC transistor output max 400mA per output requires type PF or PM Type OR One electro mechanical relay output max switch power 230V AC 0 5A requires...

Страница 46: ...ss code is unknown If the pass code is not 1234 there is only one possibility left call your supplier ALARM When the alarm flag starts to blink an internal alarm condition has occurred Press the selec...

Страница 47: ...anager Technology Bo 6 5 60 AA e hel he etherlands oltawe 5 66 A e hel he etherlands luidwell B is 001 certified b A ertification B eander 1051 6 5 Arnhem he etherlands eghel ebruary 2 22 e luidwell d...

Страница 48: ...n 9 contents 4 dimensions metal enclosures 21 22 display pressure 7 display update time 14 functional description 6 high current 46 input signal 27 intrinsic safety 31 Intrinsic safety 32 40 42 keys 7...

Страница 49: ...PD PL PX 27 Fig 16 Terminal connections Analog signal input 27 Fig 17 Terminal connections Passive transistor output Type OT 28 Fig 18 Terminal connections Backlight ZB 28 Fig 19 Overview of terminal...

Страница 50: ...Page 50 FW F053 A M_v0404_01_EN docx...

Страница 51: ...Page 51 FW F053 A M_v0404_01_EN docx...

Страница 52: ...f 3 4 brightness 5 4 POWER MANAGEMENT 4 1 LCD new 1 sec 4 2 mode operational 5 SENSOR 5 1 formula linear 5 2 filter 01 off 5 3 cut off 00 0 5 4 calibration low 0 4mA default 5 5 calibration high 20mA...

Отзывы: