Page 13
FW-F018-P-M_v0404_01_EN.docx
3.3.2
EXPLANATION OF SETUP-MENU 1 - TOTAL
SETUP
FUNCTIONS
AND
VARIABLES
1
TOTAL
1.1
UNIT
This setting determines the measurement unit for total and
accumulated total.
The following units can be selected:
L - m3 - kg - lb. - GAL - USGAL - bbl - ---- (no unit).
Alteration of the measurement unit will have consequences for
operator and SETUP-level values.
Please note that the K-factor has to be adapted as well; the
calculation is not done automatically.
1.2
DECIMALS
The decimal point determines for total and accumulated total the
number of digits following the decimal point.
The following can be selected:
0000000 - 111111.1 - 22222.22 - 3333.333
1.3
K-FACTOR:
With the K-factor, the flowmeter pulse signals are converted to a
quantity. The K-factor is based on the number of pulses generated by
the flowmeter per selected measurement unit (SETUP 1.1), for
example per cubic meter. The more accurate the K-factor, the more
accurate the functioning of the system will be.
Example 1:
Calculating the K-factor.
Let us assume that the flowmeter generates 2.4813 pulses per liter
and the selected unit is "cubic meters / m3". A cubic meter consists of
1000 parts of one liter which implies 2,481.3 pulses per m3. So, the
K-factor is 2,481.3. Enter for SETUP 1.3: "2481300" and for
SETUP 1.4 - decimals K-factor "3".
Example 2:
Calculating the K-factor.
Let us assume that the flowmeter generates 6.5231 pulses per gallon
and the selected measurement unit is gallons. So, the K-Factor is
6.5231. Enter for SETUP 1.3: "6523100" and for SETUP 1.4 decimals
K-factor "6".
1.4
DECIMALS K-FACTOR
This setting determines the number of decimals for the K-factor
entered (SETUP 1.3). The following can be selected:
0 - 1 - 2 - 3 - 4 - 5 - 6
Please note that this setting influences the accuracy of the K-factor
indirectly (i.e. the position of the decimal point and thus the value
given).
This setting has NO influence on the displayed number of digits for
total (SETUP 1.2)!