5.2 

ELECTRICAL INSTALLATION IN HAZARDOUS AREA 

5.2.1 

GENERAL INFORMATION AND INSTRUCTIONS 

 

Cautions 

  Mounting, electrical installation, start-up and maintenance of this device may only be 

carried out by trained persons authorized by the operator of the facility. Persons must 
read and understand this manual before carrying out its instructions. 

  This device may only be operated by persons who are authorized and trained by the 

operator of the facility. All instructions in this manual are to be observed. 

  Make sure the measuring system is correctly wired up according to the wiring diagrams. 

Protection against accidental contact is no longer assured when the enclosure cover is 
removed or the panel cabinet is opened (danger from electrical shock). The enclosure 
may only be opened by trained persons authorized by the operator of the facility. 

  To maintain the degree of protection of at least IP65 in accordance with IEC 60529, 

suitable cable entries and blanking elements must be used and correctly installed. 

  Take careful notice of the "Safety rules, instructions and precautionary measures" in the 

front of this manual. 

  Chapter 4 shows general information regarding the electrical installation of your indicator.  

This chapter gives additional specific information regarding Intrinsically safe installation 
and overrules the information given in chapter 4. 

  When installing this device in hazardous areas, the wiring and installation must comply 

with the appropriate installation standards for your industry. 

 

 

 

Safety instructions 

  For the combined connection of the different supply, input and output circuits, the 

instructions in this manual must be observed.  

  Precautions shall be taken to avoid the risk of electrostatic discharge (ESD) and 

propagating brush discharges. 

  For reasons of ESD and safety, always ground the metal enclosure properly as indicated 

in section “4.5. Electrical installation” of this manual. 

  Do not blend metal front covers with non-metallic rear covers, vice versa and / or cable 

glands. A metal cover on a non-metallic rear cover could lead to ESD. A metal cable 
gland in a non-metallic enclosure could invalidate isolation.

 

  For enclosures and windows with a high surface resistance, potential charging hazard 

exists. Do not rub these surfaces of the indicator. Clean window and enclosure only with a 
lint-free cleaning cloth made damp with a mild soap solution.

 

 

 

 

Please note 

  Certificates and related documents are available on our website or from your distributor. 

  Carefully study the configuration examples with wiring diagrams per classification in the 

following paragraphs. 

5.2.2 

INSTALLATIONS BASED ON FM OR CSA CERTIFICATE 

 

Installation instructions 

  For installation in the 

US

: this Intrinsically Safe device must be installed in accordance 

with the National Electrical Code, NFPA 70, Article 504 and ANSI/ISA-RP 12.6 and 
product certificate FM16US0177X or CSA.08.2059461. 

 

  For installation in 

Canada

: this Intrinsically Safe device must be installed in accordance 

with the Canadian Electrical Code, Part 1 Appendix F and product certificate 
CSA.08.2059461.

 

Covered markings 

  Intrinsically Safe for Class I/II/III, Division 1, Groups A,B,C,D,E,F,G, Temperature class T4

 

  Class I, Zone 0, AEX ia IIC T4 

Safety instructions 

  Please consult the control drawing for this F0-Series model on the following page. 

  Read paragraph 6.3 for battery replacement instructions. 

Specific conditions of use 

  When the enclosure of the indicator is made of aluminum alloy, when used in a potentially 

explosive atmosphere requiring apparatus of equipment protection level Ga, the indicator 
shall be installed so, that even in the event of rare incidents, an ignition source due to 
impact or friction sparks between the enclosure and iron/steel is excluded.

 

Содержание F013-A

Страница 1: ...ALIZER WITH HIGH LOW FLOW RATE ALARMS Signal input flowmeter 0 4 20mA Alarm output one flow rate alarm Options Intrinsically Safe F Series Field mounted indicators for safe and hazardous areas More in...

Страница 2: ...ot be disposed of into the general waste system or into a landfill At the end of its life equipment shall be disposed of according to the local regulations regarding waste of the electrical and the el...

Страница 3: ...amage of the F013 A or connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F013 A or connected...

Страница 4: ...al directions 18 4 2 Installation surrounding conditions 18 4 3 Handling the F Series enclosure 19 4 3 1 Identification 19 4 3 2 Opening Removing the cover 21 4 3 3 Closing Replacing the cover 21 4 4...

Страница 5: ...5 4 Configuration examples Intrinsically Safe applications 39 5 4 1 F013 A OT PX XI ZB Ex ia IIC IIIC 39 5 4 2 F013 A OT PD XI ZB Ex ia IIC IIIC 39 5 4 3 F013 A OT PL XI ZB Ex ia IIC IIIC 40 6 MAINTEN...

Страница 6: ...he sensor several options are available Fig 1 Typical application for the F013 A Configuration of the F013 A The F013 A has been designed to be implemented in many types of applications For that reaso...

Страница 7: ...total 2 3 OPERATOR INFORMATION AND FUNCTIONS In general the F013 A will always function at Operator level The information displayed is dependent upon the SETUP settings The signal from the connected...

Страница 8: ...value 3 confirm the new alarm value by pressing ENTER Fig 4 Example of display information during programming minimum FLOW RATE When a value was changed but ENTER has not been pressed yet the change...

Страница 9: ...ill active Make sure that the unit is not being used for any application when altering the settings 3 2 1 ENTERING SETUP LEVEL Configuration of the F013 A is done at SETUP level which can be reached a...

Страница 10: ...ch function that needs to change navigate to that function and follow the steps indicated below During the programming sequence the display will deactivate the SETUP indicator and activate the PROGRAM...

Страница 11: ...key During the programming sequence this key is used to confirm the new value and return to SETUP level To cancel the operation either press the PROG key for 3 seconds or wait for 20 seconds the progr...

Страница 12: ...3 ALARM 3 1 FLOWZERO default no relays ignore 3 2 ALARM LOW 0000 000 9 999 999 3 3 ALARM HIGH 0000 000 9 999 999 3 4 DELAY ALARM LOW 0 1 999 9 seconds 3 5 DELAY ALARM HIGH 0 1 999 9 seconds 3 6 ALARM...

Страница 13: ...le 2 Calculating the span Let us assume that the flowmeter generates 20mA at a flow rate of 2 481 3 Liters minute and the selected unit is m3 The rate per second is 2 481 3 60 is 41 355 L sec This is...

Страница 14: ...gnore or disable the low flow rate alarm The following settings can be selected DEFAULT in case of a low flow rate alarm and no signal it will switch the alarm output and indicate the alarm on the dis...

Страница 15: ...m brightness 3 3 6 EXPLANATION OF SETUP MENU 5 POWER MANAGEMENT When used with the internal battery option the user can expect reliable measurement over a long period of time The F013 A has several sm...

Страница 16: ...r value Response time to step change in analog input value seconds 50 75 90 99 01 filter disabled filter disabled filter disabled filter disabled 02 0 3 0 5 1 0 1 8 03 0 5 1 0 1 5 3 0 05 1 0 1 8 2 8 5...

Страница 17: ...ettings can be selected CALIBRATE with this setting the input will be calibrated with the actual 20mA value After pressing enter CAL SET will be displayed as soon as the calibration is completed From...

Страница 18: ...e g F013 A XF Follow the electrical installation instructions as shown in chapter 4 and the mechanical installation instructions of the enclosure that are supplied separately Type XI Suitable for int...

Страница 19: ...y your F0 Series device all field mount enclosures have a weatherproof identification label placed on the outside of the unit Fig 7 Identification Example of F0 Series identification label safe area I...

Страница 20: ...fe area Type PM or PF Serial number and year of production The serial number can be reviewed on the identification label or in SETUP menu Others The production date is either shown separately on the l...

Страница 21: ...heir mating parts and the front cover is now completely separate 4 3 3 CLOSING REPLACING THE COVER To replace the cover on the F Series enclosure follow this procedure 1 Re insert all terminals to the...

Страница 22: ...rt B after H HBx Fig 10 Dimensions Aluminum and stainless steel enclosures 75 mm 2 95 130 mm 5 12 112 mm 4 40 60 mm 2 36 120 mm 4 72 M20 x 1 5 PG9 PG9 30mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30...

Страница 23: ...mm 5 12 112 mm 4 40 60 mm 2 36 120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 2...

Страница 24: ...ng the mounting plate please follow the instructions that came with the accessories Alternatively the unit can be panel mounted by using only the front cover Wall mount by using the openings on the ou...

Страница 25: ...ack panel The metal front panel is connected to the Protective Earth by the mounting screws and serrated washers The wire screens shield are meant to prevent electromagnetic interference and shall be...

Страница 26: ...tional Rules and Regulations When a power supply is connected to the field wiring connections please also consider the demands for power supply wiring shown in paragraph 4 5 4 The installation must co...

Страница 27: ...Terminal 7 sensor supply 8 2V 12V or 24V Type PF and PM offer a power supply for the sensor The flowmeter can be externally powered with 8 2V 12V or 24V DC max 400mA 24V The voltage is selected with...

Страница 28: ...wire can be connected to the common ground terminal See paragraph 4 5 3 Type PL input loop power Model F013 A PL is powered from the 4 20mA sensor signal Fig 16 Terminal connections Analog signal inp...

Страница 29: ...current 30mA Connect the to terminal 9 and the to terminal 10 Fig 18 Terminal connections Backlight ZB 4 7 TERMINAL CONNECTORS SAFE AREA APPLICATIONS TYPE PF PM Take careful notice of all safety and...

Страница 30: ...ies are connected can cause ground loop currents that could damage the equipment See paragraph 4 5 2 Protective Earth PE connections for more information 4 7 2 TERMINALS 3 4 ALARM OUTPUT Type OT A pas...

Страница 31: ...013 A requires a 0 4 20mA flowmeter signal which will be processed 4 times a second with a 16 bit accuracy The input is not isolated The screen of the signal wire can be connected to the common ground...

Страница 32: ...r F0 Series device all field mount enclosures have a weatherproof identification label placed on the outside of the unit Fig 24 Identification Example of F0 Series identification label intrinsic safet...

Страница 33: ...sh discharges For reasons of ESD and safety always ground the metal enclosure properly as indicated in section 4 5 Electrical installation of this manual Do not blend metal front covers with non metal...

Страница 34: ...uits connected to terminals 1 and 2 4 and 6 7 and 8 11 and 12 the input parameters of the connected hazardous location apparatus must meet the following requirements Vmax The Voc of the of the circuit...

Страница 35: ...ircuit For the circuits connected to terminals 1 and 2 4 and 6 7 and 8 11 and 12 the input parameters of the connected hazardous location apparatus must meet the following requirements Vmax The Voc of...

Страница 36: ...cuits precautions must be taken to separate the Intrinsically safe circuits in accordance with EN 60079 11 For electrical data consult Annex 1 for this F0 Series model on the following page Substituti...

Страница 37: ...c safety Ex ia IIC IIIC only for connection to a certified intrinsically safe circuit with following maximum values Ui 30 V Ii 200 mA Pi 1 2 W Li 0 mH Ci 0 nF External supply output circuit Type PD te...

Страница 38: ...ea Type PX as standard all intrinsically safe products are supplied with terminal 4 and 5 to power the product externally Type PC offers additional to type PX an internal Intrinsically Safe lithium ba...

Страница 39: ...may be used in combination with the battery Type PC PX will power the F013 A the battery will be disabled automatically until the power is disconnected 5 4 2 F013 A OT PD XI ZB Ex ia IIC IIIC Fig 28 F...

Страница 40: ...ly backlight HAZARDOUS AREA SAFE AREA Power supply or switch interface For example MTL5025 MTL5011B Power supply For example MTL5025 max 30 V max 200 mA max 1 2 W Uo Io Po max 30 V max 200 mA max 0 75...

Страница 41: ...play update uses significantly more power Pulse output Low temperatures the available power will be less due to battery chemistry Check periodically The condition of the casing cable glands and front...

Страница 42: ...ons Intrinsically safe applications Type PC Only batteries of type FW LiBAT 021 that hold the Ex marking as shown below are suitable replacements and certified for use in hazardous areas Before replac...

Страница 43: ...the battery connector to prevent a short circuit Fig 32 Battery replacement procedure Install the new battery as follows 1 Make sure the new battery is undamaged in good condition and suitable for us...

Страница 44: ...31mm 1 22 IP65 TYPE 4X Plastic GRP panel mount enclosure Weight 450gr Aluminum Stainless Steel panel mount enclosure Weight 600gr Field wall mount enclosures Dimensions with extended back Classificat...

Страница 45: ...totals every minute Data retention at least 10 years Password Configuration settings can be password protected Hazardous area option Intrinsically safe Type XI ATEX approval KEMA 05ATEX1168 X II 1 G...

Страница 46: ...ve transistor output not isolated Load max 50V DC 300mA Operational Operator functions Displayed functions total and or flow rate total and accumulated total total can be reset to zero by pressing the...

Страница 47: ...known If the pass code is not 1234 there is only one possibility left call your supplier ALARM When the alarm flag starts to blink an internal alarm condition has occurred Press the select button seve...

Страница 48: ...anager Technology Bo 6 5 60 AA e hel he etherlands oltawe 5 66 A e hel he etherlands luidwell B is 001 certified b A ertification B eander 1051 6 5 Arnhem he etherlands eghel ebruary 2 22 e luidwell d...

Страница 49: ...losures 22 23 display update time 15 flow rate decimals 13 measuring unit 13 Span 13 14 time unit 13 flowmeter 16 Flowrate alarm 8 functional description 6 high current 47 input signal 28 intrinsic sa...

Страница 50: ...PL PX 28 Fig 16 Terminal connections Analog signal input 28 Fig 17 Terminal connections Passive transistor output Type OT 29 Fig 18 Terminal connections Backlight ZB 29 Fig 19 Overview of terminal co...

Страница 51: ...Page 51 FW F013 A M_v0404_01_EN docx...

Страница 52: ...set rate min max operator level 4 3 backlight off 4 4 backlight alarm off 4 5 brightness 5 5 POWER MANAGEMENT 5 1 LCD new 1 sec 5 2 mode operational 6 FLOWMETER 6 1 formula interpolation 6 2 filter 01...

Отзывы: