E126-P-EG
User Manual
FW_E126-P-EG_M_v0301-01_EN
Page 53
6.4.12 TERMINALS S4-S5: TEMPERATURE INPUT (0)4-20MA - TYPE TA
The E126-P-EG type TA option requires a (0) 4-20 mA signal from the temperature sensor. The
input is not isolated. See
Menu 5: Temperature - with type TA (4-20mA) [»27]
temperature input.
When the sensor supply voltage P3 is set to 24 V, this voltage can also be used to power the
temperature sensor.
S4
S5 - Signal
Common system ground
R
┴
P3
↓
+
J1-J2
24V
MEM
Fig. 37:
Terminals S4-S5 and P3: (0) 4-20 mA temperature input (typical) - Type TA
6.4.13 TERMINALS E1-E2: PRESSURE INPUT (0)4-20 MA
The E126-P-EG requires a (0)4-20mA signal from the pressure sensor. The input is not isolated.
See
6: PRESSURE
for configuring the pressure input.
When the sensor supply voltage P3 is set to 24 V, this voltage can also be used to power the
pressure sensor.
E1
E2 - Signal
Common system ground
R
┴
P3
↓
+
J1-J2
24V
MEM
Fig. 38:
Terminals E1-E2 and P3: Pressure input (0)4-20 mA