Reed-switch:
The E112-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce from the
reed-switch, it is advised to select REED LP - low-pass noise filter, which limits the maximum input
frequency (read par. 3.4.).
Common ground unit
low-pass filter
selection REED-LP
shielding
+ 3.0V DC
1M
EXTERNAL
INTERNAL
S1
GND
S2
Signal
REED
SWITCH
NAMUR-signal:
The E112-P is suitable for flowmeters with a Namur signal. The standard E112-P is not able to power the
Namur sensor, as an external power supply for the sensor is required. However, an 8.2V sensor supply
voltage can be provided through terminal P4. See paragraph 3.4. for more information.
INTERNAL
EXTERNAL
Namur signal input
S1
GND
S2
Signal
S3
Common ground unit
Namur
820 Ohm
shielding
P4
8.2V, 12V, 24V DC