3. Specifications

3.1. Technical Data

Associated Flow Sensor: Hall effect (F3.01.H.XX Compact version)
Supply voltage: 12 to 24 VDC regulated
Output signal: square wave
Output frequency: 45Hz per m/s nominal (13.7 Hz per ft/s nominal)
Output type: transistor NPN open collector
Output current: 10 mA max.
Relay Output: mechanical SPDT contact, 3 A @ 30 VDC, 3 A @ 250VAC resistive load
Flow trip point: 0.15 to 1 m/s (0.5 to 3 ft/s) freely adjustable
Local Status Indicator: GREEN Led = Flow RED Led = No Flow
Enclosure: IP65
Operating temperature: 0 to 60°C (32 to 140°F)
Relative humidity: 0 to 95% non-condensing
Housing material: PVC

Standards & Approvals

Manufactured under ISO 9002
CE

3.2. Dimensions

K315 KIT

F3.15 Sensor with O.C. output & MIN alarm

L0 = 68.3 mm (2.69 in)
L1 = 98.5 mm (3.88 in)

Содержание K315

Страница 1: ...or INSTRUCTION MANUAL EN 10 11 Table of Contents 1 Introduction 2 Safety Instructions 2 Unpacking 2 2 Description 2 3 Specifications 3 Technical Data 3 Dimensions 3 4 Installation 4 Sensor Assembly 4...

Страница 2: ...ensured Do not exceed published specifications using this instrument To clean the device use only chemical compatible products 1 2 Unpacking Please verify that the product is complete and without any...

Страница 3: ...ollector Output current 10 mA max Relay Output mechanical SPDT contact 3 A 30 VDC 3 A 250VAC resistive load Flow trip point 0 15 to 1 m s 0 5 to 3 ft s freely adjustable Local Status Indicator GREEN L...

Страница 4: ...4 1 Sensor Assembly Screw down completely the electronic box to have a perfect sealing between the sensor and the box 4 2 Wiring Unscrew the top cover to reach the electrical connections All wiring c...

Страница 5: ...than one wire to a single terminal Remove the upper part of the terminals for an easy cabling Insert wire tip or ferrule completely into the terminal and fix with the screw until finger tight Sensor W...

Страница 6: ...ntil the led becomes green not necessary if the led is already green 4 Turn the potentiometer in the opposite direction anti clockwise until the led turns red You must stop turning the potentiometer a...

Страница 7: ...n terminal holes sec 4 2 Wiring Flow velocity it must be 0 15m s Relay no activated No or wrong power supply Incorrect cabling Incorrect setting alarm Verify Power supply sec 4 2 Wiring Wire insertion...

Отзывы: