Fuel Meter 
 

2 | 

P a g e                                                

flowtech-instruments.com

 

 

liquid  from  inlet  side,  to  show  the  outlet  pressure,  the  bottom  rotor  has  no  rotating  torque  even  it 
effected the liquid pressure, but the above gears will move by the rotating pressure. ln the status of the 
above gears driving gear, and the bottom gear is driven gear.  
Both of these two gears have rotating torque by the liquid press u/'e, and they move with the direction 
of the arrow to space. The gear space is opposite to, the bottom gear is driving gear, and above gear is 
driven gear. The bottom gear pushes the liquid out from the half-moon space under the liquid press 
pushes liquid volume four times of "measurement room". So, as long as the rotation of gears, the liquid 
volume can be counted. 
  

4.

 

Installation Guide 

1.

 

Flow  Meter  should  be  cleaned  before  installing  pipes.  If  the  liquid  containing  solid  particles  in  the 
upstream of the pipe, you must install filters. Only when the flow meter connected to the pipeline, can 
you remove the interface on the piston to prevent debris from entering the meter 

2.

 

No Specific requirements on the front and back of the flow meter pipeline, it can be installed horizontally 
or vertically. During the installation, this oval gear flow meter axis of rotation should be parallel to the 
ground. Please stick to the Picture 4 
 

 

3.

 

The direction of the flow meter installation should be the same as shown in the direction of the arrow 
with the liquid flow to the meter shell: installation position should pay attention to the ease of reading. 

4.

 

The flow meter should be installed on the output end of the pump. If installed in the suction side, the 
pressure loss of the flow meter filter will lead to the increase of the pump negative suction pressure, the 
liquid at the outflow of the pump shaft also causes the flow meter error increases, the flange of the pump 
suction side should be designed to prevent leakage, otherwise, it can also cause the error increases to the 
flow meter.  

5.

 

A filter should be installed at the front of the flow meter to prevent greater than 0.2mm tiny particles 
blocking the flow meter and the filter should be easy to clean 

6.

 

The flow meter is preferably mounted in front of the one-way valve only unidirectional flow of the liquid 
within the pipe to prevent the reverse rotation of the counting gear 

7.

 

The flow meter recommendations shown in Picture 5. The bypass valve can be installed in the vertical or 
the other direction of the pipeline from the top down, from bottom to top, right to left from left to right 

8.

 

When using the flow meter makes sure the internal filled with liquid. If the liquid to be measured mixed 
with a gas otherwise the measured gas and liquid mixing volume it will cause the measurement in error 
accuracy. If the liquid is mixed with gas and oil and gas separator must be installed. 

9.

 

When the flow rate traffic exceeds the specified maximum flow the speed of the oval gear increased and 
wear increases and the  pressure  loss increased dramatically and so it should be avoided though still 
measured at below the minimum flow the error increases the viscosity of a liquid slow meter 10Pa.s start 
the flow of about 1% of the maximum flow rate 

10.

 

When the flow meter is out the factory were used on the 7th mechanical oil calibration under ambient 
conditions  the  viscosity  of  the  oil  due  to  room  temperature  changes  and  about  13  Pa.s  at  room 
temperature. Theoretical volumetric flow meter measuring viscosity of the liquid changes does not affect 
the measurement accuracy because the measurement of the amount of leakage is generated in the gap, 

Содержание OFMM-025

Страница 1: ...Oval Gear Flow Meter Flowtech Measuring Instruments Pvt Ltd Email info flowtech instruments com flowtech01 gmail com Website flowtech instruments com Mobile Number 8469769988 9428876496 8160255957 ...

Страница 2: ...ification Model OFMM 025 OFS 025 OFMM 040 OFS 040 OFMM 050 OFS 050 Size 25MM 40MM 50MM Min Flow LPM 12 L Min 25 L Min 30 L Min Max Flow LPM 120 L Min 250 L Min 300 L Min Accuracy 0 5 0 5 0 5 Repeatability 0 03 0 03 0 03 Max Viscosity 1000 CPS 1000 CPS 1000 CPS Best Working Pressure 0 3 Mpa 0 3 Mpa 0 3 Mpa 3 Operating Principle The oval gear flow meter comprises oval shaped geared rotors which rota...

Страница 3: ... of the pump negative suction pressure the liquid at the outflow of the pump shaft also causes the flow meter error increases the flange of the pump suction side should be designed to prevent leakage otherwise it can also cause the error increases to the flow meter 5 A filter should be installed at the front of the flow meter to prevent greater than 0 2mm tiny particles blocking the flow meter and...

Страница 4: ... of the oval gear rotation 1 Installation is jammed when the gear impurities fall into the flow meter Reinstall removed after cleaning Installation follows the mark on the oval gear An annotated mark installed oval gear 2 The measured liquid impure filter clogging impurities Clearing filter to remove impurities 3 The measured pressure of the liquid is too small Increase the pressure Oval gear rota...

Страница 5: ...s at 90 degrees to each other and check their operation by turning either of the rotors If the rotors are not in mesh correctly or do not move freely remove one of the rotors and replace correctly at 90 degrees to the other rotor 3 Re check the operation of the rotors 4 Inspect the gears in the meter cap for wear Replace if required refer to exploded diagram 5 Replace the o ring into groove in the...

Отзывы: