background image

User Instructions - Logix® 520MD+ Series Digital Positioner  

FCD LGENIM0105-00  

 

© Flowserve Corporation 

         

45 

 

 Field Trial Version – Printed October 28, 2011 

 
 

 
Possible  Solutions:  This  warning  will  clear  upon  completion 
of a successful partial stroke test. 
 

YYGG   

●●

●●

 

TEMPERATURE HIGH WARNING  
TEMPERATURE LOW WARNING  
 
Description:  The  temperature  of  the  internal  electronics  has 
exceeded  the  manufacturer  set  limits  of  -40°C  (-40° F)  to 
85°C  (176°F).    Low  temperature  may  inhibit  responsi veness 
and  accuracy.    High temperature  may  affect  performance  or 
limit the life of the positioner.   
 
Possible  Solutions:  Regulate  the  temperature  of  the 
positioner  by  shading  or  cooling  supply  gas.    Heat  the 
positioner if needed.    If the temperature reading is in error, 
replace the main board. 
 

YYGY   

●●

 

VALVE CLOSED TOO FAR WARNING  
VALVE OPENED TOO FAR WARNING 
 
Description: While the valve was in use, it closed or opened 
farther than it did at the last calibration by 0.5%. 
 
Possible  Solutions:  Check  the  feedback  arm  linkage  and 
ensure  the  valve  stem  connection  is  tight.    Recalibrate  the 
stroke.    If  the  process  cannot  be  interrupted  a  service 
technician may be able to adjust the calibration.  
 

YYGR   

●●

 

SUPPLY PRESSURE HIGH WARNING  
 
Description:  The  supply  pressure  is  above  the  user  set 
warning  limit.      Supply  pressure  that  exceeds  the  maximum 
rating on the actuator can become a potential hazard.  
 
Possible  Solutions:  Regulate  the  supply  pressure  at  the 
positioner  below  the  maximum  limit  recommended  for  your 
actuator.  Recalibrate pressure sensors.  Check the pressure 
sensor board connections.  Replace pressure sensor board if 
necessary.  
 

YYYG   

●●●

 

SUPPLY PRESSURE LOW WARNING  
 
Description:  The  supply  pressure  is  below  the  user  set 
warning  limit.    Low  supply  pressure  can  cause  poor  valve 
response  or  positioner  failure.    The  minimum  recommended 
supply pressure for proper operation is 1.3 bar (19 PSI).  
 
Possible  Solutions:  Regulate  the  supply  pressure  at  the 
positioner  above  1.3  bar  (19  PSI).    Ensure  system  air/gas 
supply  is  adequate.    Repair  kinked  or  restricted  supply 
tubing.    Check  for  pneumatic  leaks  in  the  actuator  and 
actuator  tubing.    Recalibrate  pressure  sensors.    Check  the 
pressure  sensor  board  connections  and  replace  pressure 
sensor board if necessary.   
 

YYYY   

●●●●

 

ACTUATION RATIO WARNING  
 
Description: The force required to control the system is close 
to the maximum available force.  Actuation Ratio is based on 
the  ratio  of  available  force  to  the  required  force  to  actuate.  
Control  may  be  lost  if  this  ratio  reaches  100%.  It  is  affected 
by  the  process  load,  friction,  spring  force,  and  available 
supply pressure. 
 

Possible  Solutions:  Increase  the  supply  pressure.    Reduce 
the friction.  Check the actuator spring.  Resize the actuator.  
Adjust user set limits.   
 

YYYR   

●●●

 

MEMORY ERROR WARNING  
 
Description: The microprocessor's memory has a problem.  
 
Possible  Solutions:  Error  may  clear  with  time.    If  error 
persists,  cycle  power  and  complete  a  QUICK-CAL.  If  the 
error  still  persists,  perform  a  factory  reset,  reprogram  or 
replace the main circuit board. 
 

YYRG   

●●

 

SOFTWARE ERROR WARNING 
  
Description:  There  has  been  a  watch  dog  time  out,  stack 
overflow warning, or CPU usage warning.  
 
Possible Solutions: If the problem persists, perform a factory 
reset.  If it still persists, reprogram or replace the main board.   
 

YYRY   

●●

 

AIR SUPPLY HUMID WARNING 
  
Description: The supply gas has high relative humidity which 
can  lead  to  condensation  on  electronic  components  and 
failure of electronic functions.    
 
Possible  Solutions:  Ensure  supply  gas  is  clean  and  dry. 
Check and clean the regulator filter. 
 

YYRR   

●●

●●

 

AIR  SUPPLY  ICING  WARNING  AIR  SUPPLY  ICING 
WARNING  
 
Description:  The  supply  gas  has  high  relative  humidity  and 
the  temperature  is  close  to  0  °C  (32  °F).    Under  th ese 
conditions ice may form in the pilot relay causing diminished 
or total loss of position control.   
 
Possible  Solutions:  Ensure  supply  gas  is  clean  and  dry.  
Check and clean the regulator filter. 
 

YRGG   

●●

 

PILOT RELAY RESPONSE WARNING  
 
Description:  The  pilot  relay  is  sticking  or  slow  to  respond.  
This affects the responsiveness, increases the chance of limit 
cycling and excessive air consumption. The pilot relay is part 
of the inner loop and consists of the driver module assembly 
with  piezo  (I-P  relay)  which  is  coupled  to  the  spool  valve  or 
poppet.    The  value  of  this  indicator  corresponds  with  inner 
loop  lag.    Delayed  response  can  be  caused  by  a  partially 
clogged piezo or debris, oil, corrosion, or ice on the spool, or 
low supply pressure.  
 
Possible  Solutions:  Check  response  of  the  valve.    If  OK, 
adjust  Pilot  Relay  Response  limits.    Check  supply  pressure.  
Check  the  spool  or  poppet  for  debris,  oil,  corrosion,  ice  on 
the  spool.    Clean  or  replace  the  spool  or  poppet  assembly.  
Replace  the  piezo  or  driver  module  assembly.    Maintain  a 
clean, water-free air/gas supply.   
 

YRGY   

 

FRICTION LOW WARNING  
 
Description: The friction has passed below the user set limit.  
Low  friction  is  an  indication  of  improperly  loaded  packing 

Содержание Logix 520MD+

Страница 1: ...Logix 520MD Series Installation Operation Maintenance Safety Manual Digital Positioner FCD LGENIM0105 00 ...

Страница 2: ...7 7 5 GROUNDING AND CONDUIT 17 7 6 ELECTROMAGNETIC COMPATIBILITY 18 7 7 INTRINSICALLY SAFE BARRIERS 18 7 8 MULTI FUNCTION CARD AO DO DI 18 7 9 SAFETY DISCRETE OUTPUT SAFETY DO 19 7 10 LIMIT SWITCHES 19 8 STARTUP 20 8 1 QUICK START INSTRUCTIONS 20 8 2 LOCAL USER INTERFACE OVERVIEW 20 8 3 CONFIGURATION SWITCH SETTINGS 20 8 4 STROKE CALIBRATION 21 9 POSITIONER FUNCTIONS NO DISPLAY REQUIRED 23 9 1 LIV...

Страница 3: ...rsonal protective and lifting devices must be used as warranted FLOWSERVE products are often used in problematic applications e g extremely high pressures dangerous toxic or corrosive mediums In particular valves with bellows seals point to such applications When performing service inspection or repair operations always ensure that the valve and actuator are depressurized and that the valve has be...

Страница 4: ...with FLOWSERVE manufactured replacements as outlined in this manual WARNING Substitution of with non factory positioner components may impair intrinsic safety WARNING Before products are returned to FLOWSERVE for repair or service FLOWSERVE must be provided with a certificate which confirms that the product has been decontaminated and is clean FLOWSERVE will not accept deliveries if a certificate ...

Страница 5: ...t passes through a characterization limits modifier block This function is done in software which allows for in the field customer adjustment The characterization block can apply no adjustment Linear one of several pre defined characterization curve adjustments including several Equal Percent or a 21 point Custom Characterization curve adjustment In Linear mode the input signal is passed straight ...

Страница 6: ...e desired position the spool valve will be at a middle position that balances the pressures above and below the piston in the actuator This is commonly called the null or balanced spool position Assume the input signal changes from 12 mA to 16 mA The positioner sees this as a command source of 75 percent With Linear characterization the Final Command becomes 75 percent Deviation is the difference ...

Страница 7: ...ral gas is not acceptable Air Consumption Single Acting Relay 0 069 Nm h 1 5 bar 0 041 SCFM 22 PSI 0 082 Nm h 4 1 bar 0 048 SCFM 60 PSI Double Acting Relay 0 297 Nm h 1 5 bar 0 175 SCFM 22 PSI 0 637 Nm h 4 1 bar 0 375 SCFM 60 PSI 3 3 Pneumatic Output Table 3 Pneumatic Output Output Pressure Range 0 to 100 of air supply pressure Output Air Capacity Single Acting Relay 9 06 Nm h 1 5 bar 5 33 SCFM 22...

Страница 8: ...00 mA Voltage 200VDC Temperature 40 to 105 C 40 F to 221 F Inductive Proximity P F SJ2 SN NAMUR NC Load current Plate 1 mA No Plate 3 mA Voltage 5 25 VDC Nominal 8 VDC Temperature 40 C to 100 C 40 F to 212 F Inductive Proximity P F SJ2 S1N NAMUR NO Load current Plate 1 mA No Plate 3 mA Voltage 5 25 VDC Nominal 8 VDC Temperature 25 C to 100 C 13 F to 212 F Inductive Sensor P F NJ2 V3 N NAMUR NC Loa...

Страница 9: ...n each shipping container When lifting a valve system from the shipping container position lifting straps to avoid damage to mounted accessories Systems with valves up to six inches may be lifted by actuator lifting ring On larger systems lift unit using lifting straps or hooks through the yoke legs and outer end of body WARNING When lifting a valve actuator assembly with lifting straps be aware t...

Страница 10: ...g flush with mounting pad 5 Slip the large end of the teardrop shaped mounting hole in the back of the positioner bracket assembly over the mounting bolt Slide the small end of the teardrop under the mounting bolt and align the lower mounting hole 6 Insert the lower mounting bolt and tighten the bolting 7 Position the take off arm mounting slot against the stem clamp mounting pad Apply Loctite 222...

Страница 11: ...User Instructions Logix 520MD Series Digital Positioner FCD LGENIM0105 00 Flowserve Corporation 11 Field Trial Version Printed October 28 2011 5 2 Mounting Positioner to Flow Top Linear Valves Text here ...

Страница 12: ... Instructions Logix 520MD Series Digital Positioner FCD LGENIM0105 00 Flowserve Corporation 12 Field Trial Version Printed October 28 2011 5 3 Mounting Positioner to Standard Valtek Rotary Valves Text here ...

Страница 13: ...User Instructions Logix 520MD Series Digital Positioner FCD LGENIM0105 00 Flowserve Corporation 13 Field Trial Version Printed October 28 2011 5 4 Mounting Positioner to NAMUR Rotary Valves Text here ...

Страница 14: ...le Acting Actuators below 6 2 Connect Supply Port The positioner ports are threaded with either G or NPTF as indicated on the housing In order to maintain the recommended air quality a coalescing filter should always be installed in the supply gas line An air filter is highly recommended for all applications where dirty air is a possibility The positioner passage ways are equipped with small filte...

Страница 15: ...l Positioner FCD LGENIM0105 00 Flowserve Corporation 15 Field Trial Version Printed October 28 2011 6 5 Pneumatic Terminals Figure 6 Pneumatic Connections Port Single Acting Poppet Style Relay Double Acting Spool Style Relay Supply B Y1 Y2 A Y1 ...

Страница 16: ...0 VDC drop across the positioner at maximum loop current The operating current range is from 3 8 to 24 mA In order to determine if the loop will support the Logix 520MD perform the calculation in the following equation The Available Voltage must be greater than 10VDC in order to support the Logix 520MD Also see Table 1 Input Signal Equation 1 Available Voltage Controller Voltage Current Current R ...

Страница 17: ...ed for runs less than 5000 feet For cable runs longer than 5000 feet 20 AWG cable should be used The input loop current signal to the Logix 3200MD digital positioner should be in shielded cable Shields must be tied to a ground at only one end of the cable to provide a place for environmental electrical noise to be removed from the cable In general shield wire should be connected at the source not ...

Страница 18: ...on 7 8 Multi Function Card AO DO DI The Multi Function Card can act as an Analog Output AO a Discrete Output DO or a Discrete Input DI Connections to the Multi Function Card are made directly to the card terminals For detailed information about voltage and current limits see Table 12 Auxiliary Card Status below For AO and DO functions wire the MFC in series with a 10 to 40 VDC power supply includi...

Страница 19: ...imits see Table 12 Auxiliary Card Status above Figure 13 Safety Discrete Output Circuit 7 10 Limit Switches Limit switches provide an independent verification of the position of the feedback shaft Wire the limit switches according to the following table For more information see table Table 10 Limit Switch Specifications on page 8 Table 13 Limit Switch Connections Terminal See Figure 14 Switch 1 2 ...

Страница 20: ... Up o Down o Back Selectable GAIN Switch Rotary Used to manually fine tune the performance LED Indicators Red Yellow and Green Indicate status alarms and warnings Display Optional Provides a full menu of detailed information and configuration options Figure 15 Local User Interface 8 3 Configuration Switch Settings Before placing the unit in service set the Configuration Switches to the desired con...

Страница 21: ...he Selectable Gain Switch during a Quick Cal allows the user to use and preserve manually adjusted gains See section 8 4 Stroke Calibration for more details NOTE The gain switch is live meaning that regardless of the Auto Tune selection the gain settings can be adjusted at any time during operation by changing the selectable GAIN switch position Figure 16 Selectable GAIN Switch 8 3 6 Quick Calibra...

Страница 22: ... to E Then perform a Quick Cal During the Quick Cal custom tuning parameters will be determined based on measured response parameters The gains can then be fine tuned by adjusting the Selectable GAIN Switch Selecting D C or B will progressively provide a more stable response Selecting F through J will progressively provide a more active response In most cases selecting E will give the best results...

Страница 23: ... remote command changes and make sure the valve is properly isolated 9 3 Command Source Reset Performing a command source reset will reset the command source to analog if it has been inadvertently left in digital mode This is done by holding down both the Up and Down buttons then briefly pressing the ACCCEPT QUICK CAL button 9 4 Factory Reset To perform a factory reset hold ACCEPT QUICK CAL button...

Страница 24: ... slot 2 DIP Switch Override This indicates that the Configuration DIP Switches do not reflect the actual configuration of the positioner This can happen if a Configuration Switch is changed after a Quick Cal or if the configuration is was changed from the DTM Performing a Quick Cal will reset the configuration to what the Configuration Switches show which may not be desirable in this case Ensure t...

Страница 25: ... held at a constant position for extended periods of time the Continuous Stroke Test can provide assurance that the valve is still responsive When CST is on the positioner will cause a very small amount of valve movement From this movement the positioner can find information about the health of the valve actuator and positioner This is not recommended for valves intended for high accuracy or stabi...

Страница 26: ...Tuning Characterization Pressure Control Soft Limits Cutoff High Soft Limit Low Soft Limit Upper Position Cutoff Lower Position Cutoff Set Date Time User Preferences All Units Pressure Units Force Units Temperature Units Air Flow Units Actuator Area Units Date Format Number Format LCD Orientation Burst Mode ON OFF Positioner Revs EC Major Rev EC Minor Rev EC Build Date and Time Universal Rev Hardw...

Страница 27: ...shows current and past alarms warnings alerts and calibrations Current Alarms displays all events that are actively sounding Event History displays past 32 events including alarms warnings alerts and calibrations The event that occurred most recently is displayed first event 32 with later events recorded below Each event has a time stamp and shows if it was turning on or off 10 3 3 Partial Stroke ...

Страница 28: ...ypically responsiveness is different in each direction NOTE Only those with specific training in PID tuning algorithms should attempt to adjust the tuning by manually changing the PID values Open Stroke Time is the fastest time it took the valve to stroke from 0 to 100 during Quick Cal Changing this parameter will affect the responsiveness of the valve in the opening direction Close Stroke Time is...

Страница 29: ... de energized state regardless of the Soft Limits Upper Position Shutoff and Lower Position Shutoff This feature also called Minimum Position Cutoff or MPC is 0 10 20 30 40 50 60 70 80 90 100 0 10 20 30 40 50 60 70 80 90 100 Final Command Command Input Linear MaxFlo Linear MaxFlo Valdisk Linear Valdisk ShearStream Linear ShearStream Custom Table 16 Characteristic Curve Data Command Input Final Com...

Страница 30: ...ecimal Point LCD Orientation Use this selection to turn the turn the display upside down 180 degrees Use this feature when the positioner is mounted upside down 10 3 11 Configuration Burst Mode Burst Mode continuously transmits HART information On Off Use this feature to turn burst mode on and off 10 3 12 Configuration Positioner Revs Positioner revisions are shown in this menu SW Rev The revision...

Страница 31: ...ion switch on the positioner For example if the switch is set to 4 mA the Set 0 current must be less than the Set 100 current If Set As DO Card Use DTM The DO is highly configurable Use the ValveSight DTM to set the function of the DO If Set As DI Card Set to No Action Use this option if only an acknowledgement of the DI state is desired Set to Trigger PST Use this option to initiate a partial str...

Страница 32: ...m the HART Communication Foundation or from your Flowserve representative 11 3 Burst Mode Burst Mode is available with a handheld device In the menu of the handheld select the Burst Mode feature under the Configuration Menu 11 4 Change from HART 6 to HART 5 The Logix 520MD positioner comes standard with the HART 6 communication protocol Follow this procedure to change to HART 5 by removing the HAR...

Страница 33: ...DTM also comes in two versions Basic and Advanced The Basic DTM provides an intuitive easy to use user interface to the positioner It includes calibration configuration auxiliary card information and off line diagnostic tests A dashboard gives a quick view of important information The Advanced DTM provides a view of the positioner s full health analysis and interfaces to all of the positioner s Pr...

Страница 34: ... point can be adjusted Four types of Limit Switches can be used with the Logix 520MD 13 2 Limit Switch Types Mechanical switches are triggered by the use of a mechanical cam and followers Reed switches are triggered by a magnetic force No physical contact occurs Inductive Slot switches are triggered when the sensor detects a ferromagnetic vane inserted between the coils No physical contact occurs ...

Страница 35: ...th a 4 mA signal the AO will show a 4 mA signal when closed If the valve closes with a 20 mA signal the AO will show a 20 mA signal when closed 14 2 Discrete Output DO Use the Discrete Output function of the MFC to indicate a variety of conditions such as alarms warnings position limits etc The current is normally high and drops low when one of the pre configured states occurs Configuration of the...

Страница 36: ...nformation IOM Section Safety DO Specifications 3 6 Safety Discrete Output Electronic Connections 7 9 Safety Discrete Output Safety DO DO Status Table 12 Auxiliary Card Status Figure 22 Safety Discrete Output Card The Safety DO card uses a relay type circuit which can be closed or open Normally the circuit is closed An open circuit indicates the positioner has detected one of the following errors ...

Страница 37: ... to the positioner For electrical connection diagrams see Table 13 Limit Switch Connections For electrical specifications see Table 10 Limit Switch Specifications WARNING For units installed in hazardous areas special installation cautions and procedures are required The installation of hazardous location electrical equipment must comply with the procedures contained in the certificates of conform...

Страница 38: ...rocessor though only one cable is used to connect both cards Removal 1 Make sure the valve is bypassed or in a safe condition 2 Disconnect the power to the positioner 3 Remove the main cover 4 Disconnect the two wire connection from the side of the Card 5 Unscrew and remove the auxiliary card clips 6 Gently slide the card from the slot If two cards are present remove both cards from the slots 7 Ge...

Страница 39: ...screws 6 Calibrate Figure 27 Main Board Screws Figure 28 Main Board Connectors 16 6 Replacing the Pressure Sensor Board Removal 1 Remove the main board See procedure above Disconnecting the hall sensor and feedback cables is not required 2 Unscrew the 6 screws holding the pressure sensor board in place 3 Remove the pressure sensor board Installation 1 Place the pressure sensor o rings in the three...

Страница 40: ...pply plug screw and o ring 5 Remove the Manifold gasket Installation 1 Place the Manifold gasket 2 Place the supply plug o ring and screw 3 Place the single acting relay 4 Place the two relay assembly screws 5 Replace other components and calibrate Figure 32 Single Acting Relay Assembly Spool Clip Spring Block Base Double Acting Relay Manifold Assembly Manifold Screws 2 Manifold Gasket 2 of 2 Spoo...

Страница 41: ...ration error Recalibrate Valve position reading is not what is expected 1 Stem position sensor mounting is off 180 degrees 2 Stroke not calibrated 3 Tight shutoff MPC Minimum position cutoff is active 4 Custom characterization or soft stops are active 1 Reposition the sensor 2 Perform a Stroke calibration Quick Cal 3 Verify Tight Shutoff settings 4 Verify custom characterization or soft stop limit...

Страница 42: ...face Off GGYG Low Battery WRN YRRG Main Board Fail WRN RYRR Memory Error WRN YYYR No Motion Time Out RGYY Opened Too Far WRN YYGY Piezo Volts ALM RRRY Piezo Volts High ALM RRRY Piezo Volts High WRN YRRY Piezo Volts Low ALM RRRY Piezo Volts Low WRN YRRY Piezo Volts WRN YRRY Pilot Cycles WRN YGGY Pilot Response ALM RRGG Pilot Response WRN YRGG Pilot Travel WRN YGGY Pneumatic Leak WRN YRYR Position A...

Страница 43: ...button is briefly pressed 2 The Squawk mode is turned off remotely 3 More than one hour has passed since the command was issued GYGY SOFT STOP HIGH LIMIT ALERT SOFT STOP LOW LIMIT ALERT Description The Final Command would move the valve beyond the user set Soft Limit but the internal software is holding the position at the limit The function is similar to a mechanical limit stop except it is not a...

Страница 44: ...LVE CYCLES WARNING VALVE TRAVEL WARNING Description The cycle or travel limit of the valve actuator bellows or pilot relay has been exceeded Each cycle represents two reversals of the direction of valve movement The cycle counting criterion and count limit for the valve actuator and bellows are set by the user to track the usage of the valve assembly Possible Solutions Follow routine procedures fo...

Страница 45: ...ctuation Ratio is based on the ratio of available force to the required force to actuate Control may be lost if this ratio reaches 100 It is affected by the process load friction spring force and available supply pressure Possible Solutions Increase the supply pressure Reduce the friction Check the actuator spring Resize the actuator Adjust user set limits YYYR MEMORY ERROR WARNING Description The...

Страница 46: ...pool valve for excessive wear YRRG LOW BATTERY WARNING Description The battery for the real time clock is low The battery is designed for a 15 year life with the positioner unpowered The battery is not required for the positioner to control properly but is used only to maintain the time and date upon loss of power The time and date affect the time stamps of alarms warnings and other events This wa...

Страница 47: ...rated The unit will not respond to commands and will remain in the failsafe position until a calibration is successfully completed Possible Solutions Perform a Stroke Calibration QUICK CAL by holding the QUICK CAL ACCEPT button down for 3 seconds or perform a Pressure or Friction calibration if desired See the Calibration section of the IOM for warnings RGRY STROKE SHIFT Description The 0 and 100 ...

Страница 48: ...or board connections Recalibrate the pressure sensors If the problem persists replace the pressure sensor board RYRR MAIN BOARD ELECTRONIC FAILURE WARNING Description There has been an oscillator fault position sensor ADC failure supply voltage error reference voltage error shunt voltage error or piezo voltage error Possible Solutions This may be caused by transient conditions If the error persist...

Страница 49: ...ator for loose components RRYR DRIVER MODULE ALARM Description The pilot relay can t open the pilot relay can t shut or the Hall sensor circuit has failed Possible Solutions Check the internal wiring connections Replace the pilot relay RRRY PIEZO VOLTAGE HIGH ALARM Description The voltage driving the piezo is above the alarm limit This could indicate an error with the relay or the main board The p...

Страница 50: ...r Instructions Logix 520MD Series Digital Positioner FCD LGENIM0105 00 Flowserve Corporation 50 Field Trial Version Printed October 28 2011 18 POSITIONER DIMENTIONS 18 1 Positioner Dimensions Figures here ...

Страница 51: ...User Instructions Logix 520MD Series Digital Positioner FCD LGENIM0105 00 Flowserve Corporation 51 Field Trial Version Printed October 28 2011 18 2 Positioner Dimensions with Options Figures here ...

Страница 52: ...le Relay 2 Four way Double Acting Spool Style Relay 3 Position Indicator No Indicator 0 F Flat F Domed D Special Options No special options 0 0 Optional Mechanical Add Ins Manifold No Manifold 00 AG Gauge Manifold Aluminum AG VDI VDE 3847 Semi Integrated Manifold Aluminum VE Gauges No Gauges 0 2 Supply Output Output SS with Brass Internals psi bar kPa Valtek Standard qty 3 1 Supply Output Output S...

Страница 53: ......

Страница 54: ...9 000 283456 999 000 283457 999 000 9 10 Pilot Relay Module Single Acting Poppet Double or Single Acting Spool 283458 999 000 283459 999 000 11 12 13 14 15 16 Switches Mechanical Switch Reed Switch P F SJ2 SN P F SJ2 S1N P F NJ2 V3 N P F NBB2 V3 E2 2 wire configuration TBD TBD TBD TBD TBD TBD 19 3 Mounting Kits Table 25 Mounting Kits Description Part no IEC 534 part 6 FloTop Kämmer KA Kämmer KP an...

Страница 55: ...ner Loop 6 Installation 10 L Language 31 LCD Board 38 LCD Menu 24 Limit Switch 8 19 34 37 Local Control Of Valve Position 23 Local User Interface 20 M Main Board 39 Maintenance 37 Minimum Close Time 28 Minimum Open Time 28 Mounting 10 Mounting Kits 54 Multi Function Card 18 31 35 O Outer Loop 5 P Partial Stroke Test 26 27 33 43 Performance 8 Pneumatic Leak 24 27 33 42 Positioner Dimensions 50 Pres...

Страница 56: ...a 65 6879 8900 Flowserve Corporation has established industry leadership in the design and manufacture of its products When properly selected this Flowserve product is designed to perform its intended function safely during its useful life However the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of indus...

Отзывы: