IPS WIRELESS SELD-102 Node ENGLISH 702-3001 07-17 

 

 

 

 

Page 

8

 of 

22

 

 

       

 

 

 

flowserve.com

 

 

Low or high alarm 

Each parameter has a separate low and high alarm 
threshold. 
 

Table 4: LED indicator lights description 

LED 

State 

Description 

GREEN 

3 triple-
flashes 

Indicates that unit has been powered on 

GREEN 

Flash 
every 10 
seconds 

Normal operation 

– sensor values are 

within acceptable limits 

RED 

Flash 
every 10 
seconds 

Current alarm 

– one of the 

measurements has exceeded its 
alarm limit (if programmed) and has 
not returned within the acceptable 
range 

RED & 
GREEN 

Flash 
every 10 
seconds 

Past Alarm 

– one of the measurements 

previously exceeded its alarm limit (if 
programmed), but has now returned 
within the acceptable range 

 

 
3.4  Performance and operation limits 

This product has been selected to meet the 
specification of your purchase order. 
 
The following data is included as additional 
information to help with your installation.  This is 
typical information and if required, a definitive 
statement for your application can be obtained from 
Flowserve. 
 

 

 SELD-102 Node material 

compatibility is the responsibility of the end user. 
 

3.3.1  Sensor specifications 

Refer to section 1.8  Specifications for available 
sensor specifications. 
 

3.3.2  Battery 

 

Power is provided by a user-

replaceable lithium battery pack S1-1061, located 
in the inner portion of the transmitter housing. 
Battery life is dependent upon data transmittal 
intervals.  Battery voltage should normally be 
between 2.8 and 3.6 VDC.  If it is lower than this, 
the battery will need to be replaced.  The battery 
voltage can be read at the receiver or through the 
PSP software when connected directly to the 
SELD-102 Node unit (refer to PSP software user 
instructions for details on how to do this).  See 
table Table 5:  SELD-102 Node approximate 
battery life at various measurement intervals under 
ideal conditions 
for approximate battery life times 
for the SELD-102 Node. 

 

 

The battery pack is 

NOT

 re-chargeable and 

shall only be replaced by contacting your local 
sales representative  
(Battery pack part number: 

S1-xxxx)

 
 

Table 5:  SELD-102 Node approximate battery 
life at various measurement intervals under 
ideal conditions 

Measurement Interval 

Estimated Battery Life

 

5 seconds 

2 weeks 

10 seconds 

1 month 

30 seconds 

3.5 months 

1 minute 

7 months 

2 minutes 

1.2 years 

5 minutes 

3 years 

10 minutes 

6 years 

Note: The battery life of the SELD-102 Node is 
dependent on the type of sensor installed in the 
unit. 
 

 
4  MAINTENANCE 

The only field maintenance required on the SELD-
102 Node unit is replacement of the battery.  The 
SELD-102 Node can also be turned off when not in 
use for extended periods of time to conserve 
battery life. 
 

4.1  Tools required 

 

Allen Wrenches 1/8” and 3/16”. 

 

Tools required to install the various mounting 
configurations are conditional based on the 
type of mounting and location 

 

Phillips head torque screw driver 

 

4.2  Turning unit on/off 

 

The SELD-102 Node unit will ship with the battery 
plugged in.  To turn the unit on, the enclosure must 
be removed and the battery un-plugged.  To turn 
the IPS Node unit back on, plug-in the battery. 
 

 

 
 
 

Unplug to 

power down 

Содержание IPS Wireless SELD-102

Страница 1: ...Installation Operation Maintenance Single Port Condition Monitor and Wireless Transmitting Unit PCN 702 3001 07 17 E Original Instructions These instructions must be read prior to installing operating using and maintaining this equipment 702 3001 ...

Страница 2: ...RUCTIONS 6 3 DESCRIPTION 6 3 1 OPTIONS AND MODEL NUMBERS 7 3 2 DEFAULT CONFIGURATION 7 3 3 ALARM MODE 7 3 4 PERFORMANCE AND OPERATION LIMITS 8 4 MAINTENANCE 8 4 1 TOOLS REQUIRED 8 4 2 TURNING UNIT ON OFF 8 4 3 BATTERY REPLACEMENT 9 5 CUSTOM CONFIGURATION PROGRAMMING 9 6 INSTALLATION 10 6 1 TOOLS REQUIRED 10 6 2 PRELIMINARY OPERATIONAL CHECK 10 6 3 MOUNTING 10 6 4 CONNECTING SENSORS AND POWER UP 11...

Страница 3: ...uipment Directive PED and Equipment for Potentially Explosive Atmospheres ATEX Where applicable the Directives and any additional Approvals cover important safety aspects relating to machinery and equipment and the satisfactory provision of technical documents and safety instructions Where applicable this document incorporates information relevant to these Directives and Approvals To confirm the A...

Страница 4: ...assembly process 1 6 2 Personnel qualification and training All personnel involved in the operation installation inspection and maintenance of the unit must be qualified to carry out the work involved If the personnel in question do not already possess the necessary knowledge and skill appropriate training and instruction must be provided If required the operator may commission the manufacturer su...

Страница 5: ...ived from factory and remove protective wrapping from SELD 102 Node units and accessories Inspect all hardware for damage Report any damage to shipping carrier immediately Ensure you have received the correct sensors and mounting accessories for your application Cross check hardware received versus packing slip and purchase order Record unit serial numbers for future reference 2 1 2 Electrostatic ...

Страница 6: ... DESCRIPTION The SELD 102 Node X where X designates a specific hardware configuration per order model is a wireless transmitting unit designed to monitor one single or combination sensor input and wirelessly transmit the data to a receiver The SELD 102 Node also provides two LED indicator lights for a quick visualization of equipment health See 6 5 LED Indications The SELD 102 Node is a self power...

Страница 7: ... complete list of the different sensors that can be built in to each SELD 102 Node is shown below along with the appropriate model number Table 2 Board Numbers Option Sensor Type 4 20 BP 4 20mA Analog Input Sensor P Pressure Sensor P T Pressure Temperature Sensor DP Differential Pressure Sensor SW BP Discrete Sensor monitors dry contact closure TRTD Temperature 1000 Ohm Platinum RTD type Sensor VV...

Страница 8: ...ween 2 8 and 3 6 VDC If it is lower than this the battery will need to be replaced The battery voltage can be read at the receiver or through the PSP software when connected directly to the SELD 102 Node unit refer to PSP software user instructions for details on how to do this See table Table 5 SELD 102 Node approximate battery life at various measurement intervals under ideal conditions for appr...

Страница 9: ...ging the battery Figure 3 SELD 102 Node unit battery with unit external housing removed Figure 4 SELD 102 Node unit battery nuts holding battery in place 6 Install new battery pack part number S1 1061 Reinstall battery mounting nuts reconnect battery pack connector 7 Install tube back onto unit and tighten tube 8 Reinstall SELD 102 Node unit in the field 9 Dispose of old battery pack in accordance...

Страница 10: ...approval from the factory Ensure the SELD 102 Node is not subjected to excessive vibration unless a routine maintenance program includes verification of associated connections When installing a pressure sensor SELD 102 Node unit it is recommended that a block and bleed valve assembly be used for ease of maintenance Attach any sensors before mounting and securing the SELD 102 Node separately if req...

Страница 11: ...able 6 Specific Sensor Connection Instructions Sensor Type Connection Instructions 4 20mA This device is polarity sensitive The red wire must connect to the MOST positive power of the loop Reversed polarity will result in damage to the device Discrete Wiring carries no voltage but will detect a contact closure Change of state on the contacts will determine the state of the signal transmitted The S...

Страница 12: ...ring start up Recommended quantities of 2 year operational spares are listed below Table 8 S SELD 102 Node Spare Parts Part Number Description 2 Year Operational Spares S1 1061 Replacement Lithium Battery Pack 1 dependent on transmit interval selected M1 0124 Replacement Outer Tube Red PVC tube with clear lens dwg 100 2104 0 M1 0119 Quarter Turn Quick Disconnect Receptacle 0 M1 0120 Quick Disconne...

Страница 13: ...IPS WIRELESS SELD 102 Node ENGLISH 702 3001 07 17 Page 13 of 22 flowserve com 7 2 Drawings Figure 10 Example drawing for SELD 102 Node VA ...

Страница 14: ...f voltmeter connection to battery pack cables 8 1 2 Unit not configured correctly To perform the diagnostic steps for this issue the SELD 102 Node unit will need all sensors connected to it Refer to PSP software instructions to reload the original configuration into the SELD 103 unit 8 1 3 Unit out of range of receiver If communications from the SELD 102 Node unit to the receiver are still not suc...

Страница 15: ... WIRELESS SELD 102 Node ENGLISH 702 3001 07 17 Page 15 of 22 flowserve com If none of the above solutions are successful in getting data reception at the receiver contact the factory for additional support ...

Страница 16: ...for the application intended contact the manufacturer for advice The battery pack is NOT re chargeable and shall only be replaced by contacting your local sales representative Battery pack part number S1 1061 EXPLOSION HAZARD The unit must be powered OFF during the battery installation must be in a General Purpose Classified Area to prevent the possible ignition of a hazardous atmosphere WARNING S...

Страница 17: ...IPS WIRELESS SELD 102 Node ENGLISH 702 3001 07 17 Page 17 of 22 flowserve com 9 DECLARATION OF CONFORMITY TYPICAL ...

Страница 18: ...IPS WIRELESS SELD 102 Node ENGLISH 702 3001 07 17 Page 18 of 22 flowserve com ...

Страница 19: ...IPS WIRELESS SELD 102 Node ENGLISH 702 3001 07 17 Page 19 of 22 flowserve com ...

Страница 20: ...IPS WIRELESS SELD 102 Node ENGLISH 702 3001 07 17 Page 20 of 22 flowserve com ...

Страница 21: ...IPS WIRELESS SELD 102 Node ENGLISH 702 3001 07 17 Page 21 of 22 flowserve com ...

Страница 22: ...A and Canada Flowserve Corporation Pump 5215 North O Connor Blvd Suite 2300 Irving Texas 75039 5421 USA Telephone 1 937 890 5838 Europe Middle East Africa Flowserve Corporation Parallelweg 13 4878 AH Etten leur The Netherlands Telephone 31 76 502 8100 Latin America Flowserve Corporation Martin Rodriguez 4460 B1644CGN Victoria San Fernando Buenos Aires Argentina Telephone 54 11 4006 8700 Telefax 54...

Отзывы:

Похожие инструкции для IPS Wireless SELD-102