22
Push cleaning device
4
Fig. 5
slowly into the mid position in order to simulate a malfunction.
The amber system LED is flashing and the relay contact Alarm 2 opens. Error code e or e2 is
indicated.
Push cleaning device
4
Fig. 5
back into its initial position.
The equipment must switch back to normal operation.
Functional test
Start, Operation, Alarm and Function Test
– continued –
If the alarm limits and 2 are exceeded, the adjusted time delay is activated.
LED Alarm and LED Alarm 2 are flashing. After the time delay LED Alarm and LED Alarm 2 are
permanently illuminated. The relay contacts Alarm and Alarm 2 open.
Alarm 2 is also indicated when
■
the separator is switched off,
■
the purging valve Clw is opened and
■
if the sensor ORG 2 signals a malfunction
Depending on the reason that caused Alarm 2, the equipment
state “ppm>Limit”, “Separator OFF” or “Clear Water On” will
be indicated in the measurement window.
Alarm 1 and 2
OIL CONTENT :
ppm
State: ppm > Limit
16
UTC 10:46
2006-12-06
Содержание GESTRA OR 52-7
Страница 1: ...Installation Instructions 818788 00 Oil Turbidity Detector OR 52 7 GESTRA Steam Systems OR 52 7...
Страница 30: ...30 Annex Type approval certificate...
Страница 31: ...31 Annex continued Type approval certificate continued...
Страница 32: ...32 Annex continued Type approval certificate continued...
Страница 33: ...33 Annex continued Type approval certificate continued...
Страница 34: ...34 Annex continued EG Baumusterpr fbescheinigung Modul B...
Страница 35: ...35 Annex continued EG Baumusterpr fbescheinigung Modul B Fortsetzung...
Страница 36: ...36 Annex continued Type Examination Certificate Module B...
Страница 37: ...37 Annex continued Type Examination Certificate Module B...
Страница 38: ...38 Annex continued Declaration of Conformity...
Страница 39: ...39 For your notes...