Installation Instructions 818788-00

Oil & Turbidity Detector
OR 52-7

GESTRA Steam Systems

OR 52-7

Содержание GESTRA OR 52-7

Страница 1: ...Installation Instructions 818788 00 Oil Turbidity Detector OR 52 7 GESTRA Steam Systems OR 52 7...

Страница 2: ...edure Factory setting 17 Warning 17 Checking electrical connection 17 Checking installation 17 First commissioning 18 Programming mode 19 Other parameter settings 20 Technical Data Measuring transduce...

Страница 3: ...d 23 Note 23 Data indication 23 Operating steps see Fig 8 23 Note 24 Operating flowchart 24 Start Operation Alarm and Function Test Start and operation 21 Alarm 1 and 2 22 Functional test 22 Calibrati...

Страница 4: ...C 107 49 Danger The solenoid of the solenoid valve Clw can reach up to 80 C during operation The terminal strips of the measuring transducer ORT 7 can be live during operation This presents the risk o...

Страница 5: ...e elements The constant light beam generated in the measuring sensor passes through the transparent liquid Any foreign matter which is not dissolved scatters the beam with emulsified oils scattering t...

Страница 6: ...licone Oil seal rings Perbunan Housing 0 6025 galvanised Cleaning ring EPDM sponge rubber Light emitter Glow lamp 12 V 10 W BA 15s Electric connection via 4 m connecting cable fitted with four pole co...

Страница 7: ...basic circuit board for monitoring the operating voltages Data storage DataFlashcard 8 MB Measuring range 0 to 25 ppm ppm parts per million Actual value output 0 or 4 mA 0 ppm 20 mA 25 ppm Limits for...

Страница 8: ...5 Bremen Telefon 49 0 421 3503 0 Telefax 49 0 421 3503 393 E Mail gestra ag flowserve com 0736 Oil content meter OR 52 7 15ppm Alarm approved by SEE BG according IMO Resolution MEPC 107 49 Approval No...

Страница 9: ...chnical Data continued Dimensions OR 52 7 Measuring sensor ORG 12 Measuring transducer ORT 7 Fig 2 approx 200 approx 170 approx 225 ON ALARM 1 ALARM 2 SYSTEM GESTRA ORT 7 OK P 240 260 110 160 Depth 91...

Страница 10: ...hat the fluid flow always passes through the sensor under all operating conditions and that any by passing of the oil separator is prevented If it is not possible to provide the sampling point in a ve...

Страница 11: ...7 OK P Three way control valve Overboard line To bilge To bilge Pressure maintaining valve if required Mount vacuum breaker above the oil separator 10 x 1 mm copper or stainless steel pipe Inlet Outl...

Страница 12: ...nected contactors and actuators with RC combinations in accordance with manufacturers specifications in order to suppress interferences Make sure that the disconnecting switch Fig 4 is easily accessib...

Страница 13: ...If the turbidity of the effluent is too high alarm caused by ingress of oil or dirt particles introduced into the system during start up the three way valve will divert the contaminated water to the...

Страница 14: ...14 Functional Elements Measuring sensor ORG 12 Fig 5 7 ON ALARM 1 ALARM 2 SYSTEM GESTRA ORT 7 OK P 1 5 4 3 2 6 8...

Страница 15: ...15 Functional Elements continued Measuring transducer ORT 7 Fig 6 ON ALARM 1 ALARM 2 SYSTEM GESTRA ORT 7 OK P 4 0 9 Fig 7 VDR4 VDR5 VDR3 L3 P2 P1 P3 C24 C25 C26 R34...

Страница 16: ...e Clew 4 Cleaning device 5 Drying cartridge 6 Throttling device 7 Measuring transducer ORT 7 8 Cable glands 9 LCD display 0 System LED Keypad LED Mains voltage ON LED Alarm 1 and 2 Terminating resisto...

Страница 17: ...f severe injuries due to electric shock Cut off power supply before opening the housing lid Checking electrical connection Before commissioning the equipment n Check the connection of the supply volta...

Страница 18: ...and the equipment state ppm Limit is indicated 5 Press now key The purging valve opens and Alarm 2 is indicated The equipment state Clear Water ON appears Rinse the measuring transducer ORG 12 for at...

Страница 19: ...P change to activate the parameter chan ge To quit the programming mode without any changes press key OK OK back The window that was active before you switched the mode will reappear 4 After having ac...

Страница 20: ...ort is described in a separate operating manual Parameter Output 0 4 20 mA Value 4 mA prev next back OK P change Parameter Datalog Export Start prev next back OK P change Parameter Alarm2 Limit Value...

Страница 21: ...ted If however the value continues to exceed 15 ppm the message Alarm 2 remains active and the equipment state ppm Limit is indicated 5 Press now key The purging valve opens and Alarm 2 is indicated T...

Страница 22: ...mits 1 and 2 are exceeded the adjusted time delay is activated LED Alarm 1 and LED Alarm 2 are flashing After the time delay LED Alarm 1 and LED Alarm 2 are permanently illuminated The relay contacts...

Страница 23: ...The measuring transducer features therefore a data logging function The state of the equipment Log MSG Oil content Alarm 2 Clear Water and Separator and in addition every change of state State change...

Страница 24: ...0 16 ppm Ala On Off Sep On all Off Sep On week Off Sep On day Off Sep On month OK back OK back OK back OK back OK back OK back Time Date Pos Oil Clw dT Log Msg State change Time Date Pos Oil Clw dT Lo...

Страница 25: ...e Possibly caused by Remedy e1 Light Ctrl ov Glow lamp in light emitter contaminated Replace light emitter Dirt deposits on glass cylinder Clean glass cylinder Excessive turbidity Provide mechanical c...

Страница 26: ...2 must be exchanged Please order a replacement for the measuring transducer ORG 12 stock code 389 427 indicating the serial number in good time before the IOPP certificate expires Before exchanging th...

Страница 27: ...light emitter receiver 1 Undo fixing screw and remove connector from light emitter receiver 2 Unscrew union nut outside of the light emitter receiver tube and detach the emitter receiver from the body...

Страница 28: ...y Drying cartridge 1 Gasket for connector GDM 3 21 2 O ring 25 x 3 housing lid glass cylinder 2 O ring 30 x 2 housing lid glass cylinder 2 O ring 37 x 2 housing lid glass cylinder 2 O ring 48 x 2 5 ho...

Страница 29: ...Removal 1 Cut off power supply 2 Disconnect all wires and draw the cables through the cable gland 3 Remove the measuring sensor and the measuring transducer Disposal Dismantle the oil turbidity detec...

Страница 30: ...30 Annex Type approval certificate...

Страница 31: ...31 Annex continued Type approval certificate continued...

Страница 32: ...32 Annex continued Type approval certificate continued...

Страница 33: ...33 Annex continued Type approval certificate continued...

Страница 34: ...34 Annex continued EG Baumusterpr fbescheinigung Modul B...

Страница 35: ...35 Annex continued EG Baumusterpr fbescheinigung Modul B Fortsetzung...

Страница 36: ...36 Annex continued Type Examination Certificate Module B...

Страница 37: ...37 Annex continued Type Examination Certificate Module B...

Страница 38: ...38 Annex continued Declaration of Conformity...

Страница 39: ...39 For your notes...