Model Number: 5KS405SAA2177 / Version: v17012877.01
Friday, January 06, 2017
Visit us: www.gemotors.com
Page 5 of 9
Performance Characteristics
1st Winding 1st Connection
Design: 40BD1066A
Marks:
PROJECT# 1244763-2 CARTER & VERPLANCK
LOAD %
125.0
115.0
100.0
75.0
50.0
25.0
0.0
% EFF
95.21
95.42
95.80
95.84
95.47
93.17
0.00
% PF
84.33
84.07
83.00
79.54
70.57
48.60
3.40
AMPS
145.70
134.17
118.00
92.09
69.46
51.67
43.35
TORQ(FL)#FT
294.09
TORQ(LR)%FL
146.18
TORQ(BD)%FL
227.93
AMPS(LR)
588.93
PF AT START
0.30
This motor is capable of two cold or one hot start with a maximum connected load inertia of 2826.0 Lb-Ft Sq (119.1 Kg-
meter Sq) at 100% voltage, where the load torque varies with the square of the speed. Acceleration time with maximum
inertia and the above load type is 55 seconds. Safe stall time at 100% voltage is 109 seconds cold, 66 seconds hot.
Rotor inertia is 24.97 Lb-Ft Sq (1.052 Kg-meter Sq).
Open Circuit A-C: 0.846
Short Circuit D-C: 0.034
Short Circuit A-C: 0.053
X/R Ratio: 12.973
Stator Slots: 72
Rotor Slots: 58