SAFETY

 

PRECAUTIONS/INSTALLATION

 

Step

 

Three

 

Make

 

a

 

Fail

Safe

 

System:

 

 

Design

 

a

 

fail

safe

 

system

 

that

 

accommodates

 

the

 

possibility

 

of

 

relay

 

or

 

power

 

failure.

   

If

 

power

 

is

 

cut

 

off

 

to

 

the

 

controller,

 

it

 

will

 

de

energize

 

the

 

relay.

   

Make

 

sure

 

that

 

the

 

de

energized

 

state

 

of

 

the

 

relay

 

is

 

the

 

safe

 

state

 

in

 

your

 

process.

  

For

 

example,

 

if

 

controller

 

power

 

is

 

lost,

 

a

 

pump

 

filling

 

a

 

tank

 

will

 

turn

 

off

 

if

 

it

 

is

 

connected

 

to

 

the

 

Normally

 

Open

 

side

 

of

 

the

 

relay.

   

While

 

the

 

internal

 

relay

 

is

 

reliable,

 

over

 

the

 

course

 

of

 

time

 

relay

 

failure

 

is

 

possible

 

in

 

two

 

modes:

 

under

 

a

 

heavy

 

load

 

the

 

contacts

 

may

 

be

 

“welded”

 

or

 

stuck

 

into

 

the

 

energized

 

position,

 

or

 

corrosion

 

may

 

buildup

 

on

 

a

 

contact

 

so

 

that

 

it

 

will

 

not

 

complete

 

the

 

circuit

 

when

 

it

 

should.

   

In

 

critical

 

applications,

 

redundant

 

backup

 

systems

 

and

 

alarms

 

must

 

be

 

used

 

in

 

addition

 

to

 

the

 

primary

 

system.

   

Such

 

backup

 

systems

 

should

 

use

 

different

 

sensor

 

technologies

 

where

 

possible.

   

While

 

this

 

manual

 

offers

 

some

 

examples

 

and

 

suggestions

 

to

 

help

 

explain

 

the

 

operation

 

of

 

FLOWLINE

 

products,

 

such

 

examples

 

are

 

for

 

information

 

only

 

and

 

are

 

not

 

intended

 

as

 

a

 

complete

 

guide

 

to

 

installing

 

any

 

specific

 

system.

  

Components:

 

 

 

LC52

1001

  

‐ 

Single

 

input

 

with

 

dual

 

relays,

 

3.5

 

digit

 

LED

 

display

 

and

 

repeater

 

output.

 

 

Owner’s

 

Manual

 

 

Panel

 

DIN

 

Rail

 

Mounting:

  

The

 

controller

 

may

 

be

 

mounted

 

by

 

either

 

a

 

back

 

panel

 

using

 

two

 

screws

 

through

 

mounting

 

holes

 

located

 

at

 

the

 

corners

 

of

 

the

 

controller

 

or

 

by

 

snapping

 

the

 

controller

 

on

 

35

 

mm

 

DIN

 

Rail.

 

         

 

Note:

  

Always

 

install

 

the

 

controller

 

in

 

a

 

location

 

where

 

it

 

does

 

not

 

come

 

into

 

contact

 

with

 

liquid.

 

 
 

 

 

Содержание DataPoint LC52 Series

Страница 1: ...Rev A2 LC900007 1 of 18 DataPoint Continuous Relay Controller LC52 Series Manual CALL TOLL FREE 877 742 2878 FOR SALES AND SUPPORT CLICK HERE TO RETURN TO WEBSITE ...

Страница 2: ...its Fail Safe relay control of pumps valves or alarms with a 0 15 to 60 second delay Polypropylene enclosure can be DIN rail mounted or back panel mounted Easy setup with push button calibration for display and relay settings AC powered Table of Contents Specifications 3 Dimensions 3 Safety Precautions 4 Make a Fail Safe System 5 Components 5 Installation 5 Getting Started 6 Features of the Single...

Страница 3: ...VDC 25mA primary 28 VDC 50mA secondary Contact type 1 SPDT 1 Latched SPDT Contact rating 250 VAC 12A Hp Contact output Selectable NO or NC Contact latch ON or OFF Contact configuration 1 High or low level alarm 2 High and low level alarm 3 Automatic fill or empty 4 Automatic fill or empty with alarm Contact delay 0 15 60 seconds Fail safety Power fail safe Repeater output 4 20 mA 12 36 VDC Ambient...

Страница 4: ...al electrical codes Flammable or Explosive Applications The LC52 series continuous relay controllers should not be used with explosive or flammable liquids which require an intrinsically safe or explosion proof rating If you are unsure of the suitability of a controller for your installation consult your Flowline representative for further information Install In a Dry Location The controller housi...

Страница 5: ...contact so that it will not complete the circuit when it should In critical applications redundant backup systems and alarms must be used in addition to the primary system Such backup systems should use different sensor technologies where possible While this manual offers some examples and suggestions to help explain the operation of FLOWLINE products such examples are for information only and are...

Страница 6: ...lay from 0 15 to 60 seconds can be set before the relay responds to the sensor input Typical applications for single input relays are high level or low level switch alarm operations opening a drain valve whenever liquid level rises to a set point and over flow protection turning off a pump or sounding an alarm when a high level is reached Features of a Latching Relay automatic fill or empty The la...

Страница 7: ... amps for reactive loads the current must be derated or protection circuits used When the red LED is ON and the relay is in the energized state the NO terminal will be closed and the NC terminal will be open 5 Invert switch This switch reverses the logic of the relay control in response to the switch es conditions that used to energize the relay will now de energize the relay and vice versa 6 Time...

Страница 8: ...quick review of wiring the LC52 series to common 4 20 mA transmitters EchoSonic II LU23 LU27 LU28 LU29 series EchoPod DL10 DL14 DL24 DL34 series Sourcing mode Factory Setting EchoSpan LU80 LU81 LU83 LU84 series Sourcing Mode Factory Setting Echotouch LU30 5004 and LU30 5064 only Sourcing Mode Factory Setting Echotouch LU30 5003 and LU30 5063 only Sinking mode internal jumper must be changed DeltaS...

Страница 9: ...urcing to sinking remove jumper from JWA and place on JWB The LC52 is shipped from the factory in the sourcing mode JWA active 4 Gently return PCB into housing and replace back panel Note Loop powered devices can operate in either the souring or sinking modes Sourcing Mode Sinking Mode No Change Required EchoSonic II LU23 LU27 LU28 LU29 series EchoSpan LU80 LU81 LU83 LU84 series EchoPod DL10 DL14 ...

Страница 10: ...uit board PCB from the housing Use caution when removing the PCB 2 Locate jumpers JW1 JW2 and JW3 on the PCB 3 To change from 120 VAC to 240 VAC a Remove the jumpers from JW1 JW2 and add a jumper to JW3 4 To change from 240 VAC to 120 VAC a Remove the jumper from JW3 and add jumpers to JW1 JW2 5 Gently return PCB into housing and replace back panel 120 VAC Jumper Setting 240 VAC Jumper Setting Rel...

Страница 11: ...ower supply or some other indicator or backup alarm to warn of a power failure in the alarm circuit In this application the normal status of the relay set point at the bottom of the tank will be wet and the relay will be energized holding the alarm circuit open The relay LED will be ON so for this application Invert should be set to the OFF position High Level Alarm In the same manor this system c...

Страница 12: ...hould open starting to fill the tank When the liquid is above the low relay set point the valve will remain open When the liquid reaches the high relay set point the valve should close Latch In any 2 setpoint relay configuration LATCH must be ON Invert Referring to the logic chart in Step Nine we look for the setting that will de energize the relay valve close when both relay set points are wet In...

Страница 13: ...bar graph will jump one Green bar to the right next to RLY2A 8 Use UP DWN buttons to change display to the desired RLY2A value 9 Press the SET button again Immediately the LED bar graph will jump one Green bar to the right next to RLY2B 10 Use UP DWN buttons to change display to the desired RLY2B value 11 Press the SET button again Immediately the LED bar graph will return back to it normal operat...

Страница 14: ...mpty with latch ON With Latch OFF the relay will only respond to the RLY 2A relay set point RLY 2B will be ignored With Latch OFF the setting for RLY 2B will be ignored All changes to the relay s state will occur from the RLY 2A relay set point Invert OFF Latch OFF RLY 2A RYL 2B Relay Wet Dry No Effect No Effect ON OFF Invert ON Latch OFF RLY 2A RYL 2B Relay Wet Dry No Effect No Effect OFF ON With...

Страница 15: ...A Check for loose or open wires between the transmitter and LC52 and check the output of the transmitter Bar Graph shows a single Red bar This indicates a current input greater than 20mA Remove power immediately Check for a short in the wiring between the transmitter and LC52 or for some other power source that is affecting the input loop RLY 2B does not appear Flip Latch switch to ON Relay switch...

Страница 16: ...e LC52 1001 OFFSET 0 0 SPAN 60 0 RLY 1 55 0 RLY 2A 50 0 RLY 2B 10 0 The next exercise demonstrates the same inventory control with automatic filling and a high level alarm However the units have been changes from inches to gallons Within the tank 1 50 gallons of liquid The usable range is now 300 gallons of liquid The pump starts filling at 50 gallons of liquid and stops filling at 250 gallons of ...

Страница 17: ...C52 1001 OFFSET 16 0 SPAN 56 0 RLY 1 50 0 RLY 2A 20 0 RLY 2B N A The next exercise demonstrates the same inventory control with a high and low level alarm However the units have been changes from inches to gallons Along the straight side of the tank 1 50 gallons of liquid The usable range is now from 50 to 250 gallons of liquid The high level alarm occurs at 220 gallons of liquid The low level ala...

Страница 18: ...ocedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowline have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shipment to Flowline Flowline reserves the right to unilateral...