Electrical Wiring
1.
Remove switch box cover.
2.
Remove protection plug(s) from conduit entries and install conduit or other approved connection means.
3.
Engage wires in terminal strip using a small screwdriver (1/2” blade).
Note:
terminals 1, 2, & 3 are for the top
switch and terminals 4, 5, & 6 are for the bottom switch.
Wiring Diagram
is on the inside of the switchbox cover.
Warning:
To maintain IP67 weather protection, any unused conduit entry must be closed with
appropriate conduit plug. Conduit plugs supplied with the switch box are for transit purposes
only.
3-D Visual Indicator Setting
1.
Rotate actuator to closed.
2.
Loosen the four screws securing the plastic indicator dome and rotate it to show ‘CLOSED’.
Note: the dome and
rotor can be removed and rotated ¼ turn for OPEN-CLOSE visual indication from the end switchbox.
SPST Proximity Switch Specifications
•
Type:
Dry contact reed switch
•
Contacts:
Form-A
•
Maximum switching power:
2.0 A
•
Maximum switching current:
3.0 A
•
Maximum switching voltage:
400 VDC / 400 VAC
•
Initial contact resistance:
0.080 Ohms
•
Maximum operating time:
2.5 msec
•
Operating temperature range:
-40C to +125C
•
Approvals:
UL and CSA Recognized Component
SPDT Proximity Switch Specifications
•
Type:
Dry contact reed switch
•
Contacts:
Form-C
•
Maximum switching power:
20W
•
Maximum switching current:
1.0 A
•
Maximum carrying current:
2.0 A
•
Maximum switching voltage:
150 VDC / 150 VAC
•
Initial contact resistance:
0.100 Ohms
•
Maximum operating time:
2.0 msec
•
Operating temperature range:
-40C to +125C
•
Approvals:
UL and CSA Recognized Component
CAUTION:
Reed Proximity switches sense magnetic fields and may accidentally trip if magnets are within 1/2” from
the sensing surface.
Page 2 of 2
Doc # 52PRSIOM21715