DIFFERENT PRESSURE CONTROL VALVE
FlowCon DPCV
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Denmark
Dubai
USA
Singapore
1H95000 - 04/2016
- 3 -
Figure 7
Using the DPCV as a shut-off valve
To use the FlowCon DPCV as a shut-off valve
please use a 4mm hex key on the top as shown
in figure 7. Turn the hex key clockwise (several
rotations) until end point to close the valve, and
counter-clockwise until end point to open the
valve and in order for it to function as a differen-
tial pressure control valve again (the setting is
kept). Be sure not to use more than 1Nm torque.
General
Water must always be suitably treated, clean
and free from debris. It is recommended that a
strainer be installed prior to the inlet of the capil-
lary tube to prevent damage or blockage due to
debris. Further, it is recommended not to exceed
the maximum operational differential pressure.
Warranty obligation
Failure to abide by all recommendations as per
this installation and operation instruction will void
warranty.
When manually operating the valve do not use
more than 1 Nm torque. Using more than 1 Nm
torque will void warranty.