INSTALLATION AND OPERATION INSTRUCTION

DIFFERENT PRESSURE CONTROL VALVE

FlowCon DPCV

FlowCon International assumes no responsibility 

for mistakes, if any, in any printed material.

Denmark 

Dubai 

USA 

Singapore 

www.flowcon.com

        

1H95000 - 04/2016

- 1 -

FlowCon DPCV 15-50mm

Figure 1

Figure 2

Figure 3

Install the 

FlowCon DPCV

 in the return pipe-

work of the riser with connection to the supply 

pipework of the riser through the capillary tube 

as called for in the design drawings. It is recom-

mended that a strainer be installed prior to the 

inlet of the capillary tube to prevent damage or 

blockage due to debris. INSTALL THE VALVE 

HOUSING WITH THE FLOW DIRECTIONAL 

TRIANGLE POINTING IN THE CORRECT DI-

RECTION.

The valve body is available with female threaded 

end connections. The thread standard is EN 

10226-1, which is a straight metric thread. Please 

clear threads on both valve and piping of de-

bris. Sealant such as pipe dope or Teflon tape is 

recommended. WHEN USING HEMP AS PIPE 

SEALANT, ENSURE NO STRANDS ARE LEFT 

IN THE VALVE OR PIPING. 

The capillary tube is available with ¼” straight 

male end connections with gaskets for sealing. 

One end is mounted on the upper part of the 

DPCV instead of the black plastic

plug. The other end is mounted at the inlet of the 

riser fx. in a FlowCon ABS.

For each end of the capillary tube start by mount-

ing the big nut with the gasket (

) in the valve 

and proceed as shown in figure 2. Pull the small 

nut (

) onto the copper tube (

) with the thread 

toward the end of the tube, and then push the 

cutting ring (

) onto the tube as far as possible. 

Push the copper tube into the hole of the big nut 

and screw the small nut into the big nut with a 

wrench using 12-15Nm.

When the DPCV is installed with the capillary 

tube in place and the system is operational, 

please vent the capillary tube as shown in figure 

3. Open the highest elevated screw byturning it 

counter-clockwise max. 2 rotations until water 

runs constantly from it, and then close it again. 

As standard, the valve body is supplied with 

plugs in the body tappings. Each plug is sealed 

Содержание DPCV

Страница 1: ...lon tape is recommended WHEN USING HEMP AS PIPE SEALANT ENSURE NO STRANDS ARE LEFT IN THE VALVE OR PIPING The capillary tube is available with straight male end connections with gaskets for sealing One end is mounted on the upper part of the DPCV instead of the black plastic plug The other end is mounted at the inlet of the riser fx in a FlowCon ABS For each end of the capillary tube start by moun...

Страница 2: ...change the setting please remove the black lock ring and turn the black top part by hand as shown in figure 4 do not use more than 1 Nm force Turn the black top part clockwise to increase and counter clockwise to decrease the setting The setting can be seen directly on the valve because the scale is printed on the top part which is turned and the setting is defined by the groove in the brass part ...

Страница 3: ... to function as a differen tial pressure control valve again the setting is kept Be sure not to use more than 1Nm torque General Water must always be suitably treated clean and free from debris It is recommended that a strainer be installed prior to the inlet of the capil lary tube to prevent damage or blockage due to debris Further it is recommended not to exceed the maximum operational different...

Страница 4: ...DIFFERENT PRESSURE CONTROL VALVE FlowCon DPCV FlowCon International assumes no responsibility for mistakes if any in any printed material Denmark Dubai USA Singapore www flowcon com 1H95000 04 2016 4 ...

Отзывы: