5.5V or 22mA. If the FDHC-100 detects a loss of the command signal, the Fault indicator will flash and 
the actuator will be moved to one of three preset positions: the 

open 

position, the 

closed 

position, or the 

position last attained prior to losing the command signal. The LOSS OF COMMAND function is used to set 

the desired default position.  When the LOSS OF COMMAND function is selected, the adjust buttons are 

used to set the default position.  The FDHC-100 indicates the selected default setting by flashing the 

Open function indicator for the 

open 

default position, or it will flash the Close function indicator for the 

closed 

default position. When neither indicator is on, then the "last position" default is selected. When a 

0-5V or 0-10V command signal is used, a loss of command signal cannot be detected. Therefore, if the 

unit is configured for a 0-5V or 0-10V command signal (see COMMAND INPUT), the MODE button will not 

select the LOSS OF COMMAND function. 
 

AUX POSITION OUT CAL 

Note that the AUX POSITION OUT CAL indicator also serves as a Fault indicator. When the indicator is on 
steady, the AUX POSITION OUT CAL function is selected. When the indicator flashes, a Fault condition 

has been detected (see FAULT INDICATOR for details). The AUX POSITION OUT CAL function is used to 

calibrate an optional feedback transmitter output. An appropriate transmitter option module is required 

to use this feature.  When the AUX POSITION OUT CAL function is first selected (by pressing the MODE 

button while in the LOSS OF COMMAND function), the CLOSE indicator will flash, and the voltage or 
current associated with the 

closed 

position will appear at the option module output. If desired, the 

output can be adjusted (using the adjust buttons) to any value from 0 to 10V (for a voltage output) or   

0 to 20mA (for a current output).  The new setting is then associated with the 

closed 

position.  Pressing 

the MODE button again will leave the unit in the AUX POSITION OUT CAL function except that the OPEN 
indicator will flash, and the output voltage or current associated with the 

open 

position will appear at the 

option module output. Like the 

closed 

setting, the output can be adjusted to any voltage (from 0 to 10V) 

or current (from 0 to 20mA), and the new setting is then associated with the 

open 

position. 

 

FAULT INDICATOR 

The FDHC-100 detects various fault conditions that prohibit the unit from controlling the actuator. When 

any of these conditions are detected, the Fault indicator will flash, and the motor outputs are turned off 

until all fault conditions have been corrected. If an appropriate relay option module is installed, the Fault 
relay output on the option module will also turn off. A communications option module can read the 

specific condition(s) causing the fault. Note that a fault condition DOES NOT disable the motor outputs 

when manually controlling the actuator with the adjust buttons; while useful for troubleshooting, care 

should be exercised when operating the motor under a fault condition. The OVERRIDE mode can also 
operate the motor when a fault condition exists – see OVERRIDE MODE for details. The various fault 

conditions are described below: 

 

LOSS OF COMMAND - If the command signal is disconnected or out of range, the fault indicator will 

remain on until the signal is reconnected or back in range. 
 

FEEDBACK POT FAULT - A fault condition is detected whenever the feedback signal is out of range (that 

is, less than 5% of the potentiometer value or more than 95% of the potentiometer value), or when any 

of the potentiometer connections are broken. Normal operation resumes when the potentiometer is 
reconnected or back in range. 

 

MOTOR 1 STALL - A fault condition is detected when no actuator motion is detected while the Motor 1 

output is turned on. The fault condition will disable the Motor 1 output only, and the fault is cleared 

Содержание FDHC-100

Страница 1: ...lt relay contact or digital communications A wide range of data is accessible through a digital communications module providing additional control or information The unit is of single solid construction and is easily mounted with two screws The FDHC 100 is interchangeable with the AMC and LRC standard size controllers and can be used to upgrade performance for those applications FEATURES Positions...

Страница 2: ... Operation Manual FDHC 100 Configuration Operation Man Rev 0 August 16 2010 2 of 14 Flomatic Corporation Glens Falls NY 12801 Phone 518 761 9797 Fax 518 761 9798 Digital High Resolution OUTLINE FDHC 100 FDHC 100C 117VAC CE ready FDHC 100A FDHC 100D 234VAC FDHC 100B FDHC 100E 24VAC CE ready ...

Страница 3: ...mes in three versions to accommodate different voltage applications The FDHC 100 and FDHC 100C are rated for 117 VAC 10 the FDHC 100A and FDHC 100D are rated for 234 VAC 10 and the FDHC 100B and FDHC 100E are rated for 24 VAC 10 The unit is easily mounted with 2 screws and is equipped with removable screw terminals that provide for easy field wiring The unit s size mounting and screw terminals are...

Страница 4: ...rovides an auxiliary 5V output which can be used to connect a command potentiometer By connecting one end of a potentiometer to pin 7 the other end to pin 4 and the wiper to pin 6 a local control knob can be implemented Pin 8 provides an auxiliary 15VDC output which can be used to power an input or output 4 20mA transmitter ACTUATOR J1 The actuator motor and feedback potentiometer are connected to...

Страница 5: ...l Pot Cal indicator will turn on steady to indicate that the unit is being controlled by the Override Input Shorting J7 pin 1 to pin 2 returns the unit to normal operation and the previously selected mode Note that earlier models may not have connector J7 and therefore do not have the OVERRIDE mode feature Controlling the FDHC 100 from the Override Input is accomplished by connecting a specific re...

Страница 6: ...ed when using one of the analog command types and can be used to override the analog command The AUTO indicator will flash whenever the unit is being controlled by the communications module MANUAL FB POT CAL The MANUAL FB POT CAL function allows manual operation of the actuator by using the adjust buttons and without affecting any other settings within the FDHC 100 When the button is pressed the m...

Страница 7: ... used to drive an alarm or merely act as an auxiliary limit switch Upon selecting the AUX CLOSE OUTPUT function the FDHC 100 will begin moving the actuator to the previously set position It is not necessary to make an adjustment if the unit has been previously set to the desired position AUX OPEN OUTPUT The AUX OPEN OUTPUT function is used to set an optional output setting that is associated with ...

Страница 8: ... can be adjusted using the adjust buttons to any value from 0 to 10V for a voltage output or 0 to 20mA for a current output The new setting is then associated with the closed position Pressing the MODE button again will leave the unit in the AUX POSITION OUT CAL function except that the OPEN indicator will flash and the output voltage or current associated with the open position will appear at the...

Страница 9: ...hes employed in actuators essentially disconnect one of the motor windings The FDHC 100 will detect this as a motor stall To avoid this condition the limit switches must be set outside of the operating range set by the CLOSE and OPEN functions ELECTRONIC BRAKE FEATURE The Electronic Brake feature of the FDHC 100 provides highly reliable and accurate braking of the motor and it is a key element in ...

Страница 10: ...resume continuous operation The duty cycle period is approximately 2 seconds with an on time that automatically various depending on the heating of the motor While this operation slows down the actuator s operation it does not impact the resolution performance of the FDHC 100 and it prevents disruption of a process due to a thermal switch shutdown OPTION MODULES Various option modules can be plugg...

Страница 11: ... 8 125mA maximum not including option module 5V OUT J2 7 5mA maximum NOTE Do not connect these outputs to other power supplies AC MOTOR OUTPUTS Off state Leakage Current 15mA Maximum Load Current 60 C 5A ENVIRONMENTAL Operating Temperature Range 0 C to 60 C Storage Temperature Range 40 C to 85 C Relative Humidity Range 0 to 90 non condensing CE CERTIFICATION FDHC 100D only EN55011 Class A RF Emiss...

Страница 12: ...roller Configuration and Operation Manual FDHC 100 Configuration Operation Man Rev 0 August 16 2010 12 of 14 Flomatic Corporation Glens Falls NY 12801 Phone 518 761 9797 Fax 518 761 9798 FDHC 100 FDHC 100 FDHC 100 FDHC 100 WIRING DIAGRAMS Input Signal Configurations ...

Страница 13: ...roller Configuration and Operation Manual FDHC 100 Configuration Operation Man Rev 0 August 16 2010 13 of 14 Flomatic Corporation Glens Falls NY 12801 Phone 518 761 9797 Fax 518 761 9798 FDHC 100 FDHC Series FOTR 100 Option Module WIRING DIAGRAMS Special Applications ...

Страница 14: ...er Configuration and Operation Manual FDHC 100 Configuration Operation Man Rev 0 August 16 2010 14 of 14 Flomatic Corporation Glens Falls NY 12801 Phone 518 761 9797 Fax 518 761 9798 FDHC Series FDHC Series FAMM 100 FAMM 100 WIRING DIAGRAMS Special Applications continued ...

Отзывы: