4. Take two diode measurements, one in forward bias and one in reverse
bias. This can be accomplished by, first, placing the probe ends of the test
leads in parallel to the part under test in one direction and then taking a
second measurement in the reverse polarity orientation.
5. If the reading is between 0.40 V and 0.90 V in one direction and OL (over-
load) in the opposite direction, the component is good. If the measurement
is 0V in both directions (shorted) or OL in both directions (open), the com-
ponent is bad.
6. The available Function Icons in the Diode mode are Settings and MIN/
MAX/AVG. See Section 7,
Function Icons
, for complete details.
5.15
Type-K Thermocouple Measurements
CAUTION
The supplied thermocouple is rated for -4~482
℉
(-20~250
℃
) only, it is not rated for the
entire specified temperature range of the meter.
#NAS100017; r. AB/59644/59644; en-US
18