background image

please visit www.flexston.com 

19 

07 

ECO mode frequency range setting 

 

 

 

 

 

 

 

 

 

 

08 

Bypass mode setting 

 

 

 

 

 

 

 

 

09 

Battery backup time setting 

10 

Programmable output setting** 

11 

Shutdown point for programmable output 

12 

Hot standby function enable/disable 

13 

Battery voltage adjustment 

14 

Charger voltage adjustment 

15 

Output voltage adjustment 

 

 

 

 

 

*Y means that this program can be set in this mode. 
**Programmable output setting is not supported by Rack models. 

Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery 
connection.    (Normal UPS shutdown means turning off input breaker in bypass mode). 

l

 

01: Output voltage   

Interface 

Setting 

 

Parameter 3: Output voltage 

You may choose the following output voltage in parameter 3: 

208: 

Presents output voltage is 208Vac 

220:

 Presents output voltage is 220Vac 

230:

 Presents output voltage is 230Vac 

240: 

Presents output voltage is 240Vac 

l

 

02: Output frequency   

Interface 

Setting 

60 Hz, CVCF mode 

 

50 Hz, Normal mode 

 

ATO 

 

Parameter 2: Output Frequency 

Setting the output frequency. You may choose following three 
options in parameter 2: 

50.0Hz: 

The output frequency is setting for 50.0Hz.   

60.0Hz:

 The output frequency is setting for 60.0Hz. 

ATO:

 If selected, output frequency will be decided according to 

the latest normal utility frequency. If it is from 46Hz to 54Hz, the 
output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the 
output frequency will be 60.0Hz. ATO is default setting. 
 

Parameter 3: Frequency mode 

Setting output frequency at CVCF mode or not CVCF mode. You 
may choose following two options in parameter 3: 

CF:

 Setting UPS to CVCF mode. If selected, the output frequency 

will be fixed at 50Hz or 60Hz according to setting in parameter 2. 
The input frequency could be from 46Hz to 64Hz. 

NCF:

 Setting UPS to normal mode (not CVCF mode). If selected, 

the output frequency will synchronize with the input frequency 
within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to 
setting in parameter 2. If 50 Hz selected in parameter 2, UPS will 
transfer to battery mode when input frequency is not within 
46~54 Hz. If 60Hz selected in parameter 2, UPS will transfer to 
battery mode when input frequency is not within 56~64 Hz.   
*If Parameter 2 is ATO, the Parameter 3 will show the current 
frequency. 

Note: If the UPS is set to CVCF mode, the bypass function will be disabled automatically. 
But when a single UPS without parallel function is powered on with mains and before the UPS 
finished the startup, there will be a few seconds of voltage pulse (same as the input voltage) 
on the bypass output. 

Содержание MaxiFlex10K

Страница 1: ...User Manual Uninterruptible Power Supply System MaxiFlex 6K MaxiFlex 6KRM MaxiFlex 10K...

Страница 2: ...gs and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through...

Страница 3: ...2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 9 2 5 SOFTWARE INSTALLATION 10 3 OPERATIONS 11 3 1 BUTTON OPERATION 11 3 2 LED INDICATORS AND LCD PANEL 11 3 3 AUDIBLE ALARM 13 3 4 SINGLE UPS OPERATION 14 3 5...

Страница 4: ...tion Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip ove...

Страница 5: ...disconnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62...

Страница 6: ...e user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only available for parallel model One share current cable only available for parallel model One batter...

Страница 7: ...port 2 USB communication port 3 Emergency power off function connector EPO connector 4 Share current port only available for parallel model 5 Parallel port only available for parallel model 6 Intelli...

Страница 8: ...3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table Model Wiring spec AWG Input Output Battery Ground Maxiflex6K 10 10 10 Maxiflex10K 8 8 8 M...

Страница 9: ...e are one DC breaker to disconnect the battery pack and the UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external battery pack is installed...

Страница 10: ...directly connect to the loads 4 Each UPS is connected to an independent battery pack 5 Remove the cover of parallel share current cable port on the UPS connect each UPS one by one with the parallel ca...

Страница 11: ...ion Wiring diagram of parallel system for rack models 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown Diagram 4 Paralle...

Страница 12: ...P key Press this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details...

Страница 13: ...sabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 2...

Страница 14: ...s Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Overload Beeping twice every second No Low battery Beeping once every second Battery unconnected Over charge EPO ena...

Страница 15: ...ect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel will display total load level 2 If it is necessary to connect the inductive loads such as a print...

Страница 16: ...in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery self test 2 To keep the system reliable the UPS will perform the battery self test automatically periodically Th...

Страница 17: ...e input breaker and switch off the battery breaker 4 Remove the cabinet and then modify the jumper on the control board to set the battery numbers refer to NOTE below Then disconnect battery wire for...

Страница 18: ...nto bypass mode without output 2 Turn off the output breaker of this unit and then turn off the input breaker of this unit 3 After it shuts down you can turn off the battery breaker and remove the par...

Страница 19: ...ers to set up the UPS Refer to following diagram Parameter 1 It s for program alternatives There are 15 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or v...

Страница 20: ...ng for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output...

Страница 21: ...ng range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz l 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose following two options DIS...

Страница 22: ...ion is not supported by the Rack model Interface Setting Parameter 3 Set programmable output You may choose the following three options ON Programmable output is manually switched on timelessly OFF Pr...

Страница 23: ...e UPS is running at normal mode and can t restart without battery l 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Para...

Страница 24: ...s within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at AC mode LCD display ECO mode Description When the input voltage is within voltage...

Страница 25: ...y status LCD display Fault status Description When UPS has fault happened it will display fault messages in LCD panel LCD display 3 9 Fault Code Fault event Fault code Icon Fault event Fault code Icon...

Страница 26: ...wice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beeping ev...

Страница 27: ...Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becom...

Страница 28: ...eck if the PRA ID number is right after turning on input breakers one by one If all the number displays are correct it s ok to turn on UPSs after disabling the warning message by pressing UP and DOWN...

Страница 29: ...es and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery...

Страница 30: ...FICIENCY AC mode 89 Battery Mode 88 BATTERY Type Numbers 12 V 7 Ah x 20 12 V 9 Ah x 20 Recharge Time 7 hours recover to 90 capacity 3 hours recover to 90 capacity 9 hours recover to 90 capacity Chargi...

Отзывы: