Factory defined curves
If the heating curve is set optimally for heating of your apartment or house, corrections will not
be necessary.
1.4.3. Why does the characteristic heating curve have to be set?
After the first settings of the heating curve authorized person can adjust, correct that curve if
necessary
.
Every heating room is built up differently. Different heating elements and heating systems can be used
(radiators, under
floor or combined heating) and every building has a different thermal insulation.
For the maximum exploitation of the heating and maximum energy savings, characteristic heating
curve has to be set using the parameter on the control panel, in a way
that the chosen heating curve is
suitable for the heating system and for the quality of the building.
1.4.4. Corrections of the room temperature
Based on the experience, factory settings of the device are for the average insulated object and room
temperature of 22
o
C. If factory settings are not adequate for achieving the desired room temperature,
supplemental adjustments of the standard heating curves can be made.
Changing the inclination
When changing the heating curve, inclination is changing too, and in that way the temperature of
w
ater in the boiler is changing when the external temperature is low (below
+ 5
o
C).
Level changes - offset
By offsetting the heating curve for the chosen value
the temperature of
water in the boiler is changing
without changing the shape of the curve.
Values in the table below are used for the orientation and the user can change them any time as
he/she wishes
to
.
Experience has shown the following (for the average building quality):
when the temperature of water for heating changes from 5 to 7
o
C that will change the room
temperature by approximately 2
o
C.
Thermal (heating) processes are slow, all corrections function after a period of time. It would
be better if further corrections were made a day or two later.
To gain
experience, we suggest that you
should
write
all corrections (within
a period of searching for
the right parameters) in
the
protocol of the corrections
.
In the
table below you can find instructions how to correct the heating curve for the radiator heating
depending on the achieved room temperature
.