DRAW

The draft of a chimney is determined by the following formula:

T = H (YA - YB)

T = Draft in mm.ca

H = Height of the vertical chimney in meters. YA = 

Specific weight of the outside air in kg / m³.

YB = Specific weight of the combustion gases expelled in kg / m³.

SECTION

The section of the chimney for the two series is determined by the following formula:

S = 8.61 Q / H½

S = Section of the chimney in cm²

Q = This is the power of the boiler in kW / h. H = 

The reduced height expressed in meters.

The reduced height of the chimney is defined by the following formula:

Hr = H - (N. 0.5 + L + R)

Hr = Reduced height

H = Actual height of the chimney. N 

= Number of elbows.

L = Horizontal length.

R = Generator back pressure.

R = 1mm up to 50,000 kcal / h. R = 

2mm up to 160,000 kcal / h.

NOTE: These values   must be increased by 6% depending on the region for every 500 

meters of elevation above sea level.

DUCT DEPRESSION

The draft measurement must be carried out under the shutter, which will allow the shutter to be 
balanced during the measurement.

The flue gas pipe must never be reduced to a diameter smaller than that of the 

outlet nozzle. However, there is no problem if the duct is of a larger diameter. In the 

event of installation on an old masonry duct, it is essential to pipe the duct.

5

02/04/2019

Page

 

During installation, at the time of commissioning, it is recommended to have a draft 

measurement called "depression" carried out in order to check the water column of the 

chimney's depression.

This measurement is carried out while hot when the device is at its normal output after 

approximately half an hour of operation.

This depression should be 2 mm WC after the pull key.

It is therefore recommended for this result a vertical height of 5m for an 

FH50ECP 

 and 6 

to 7m for an 

FH100ECP

.

In order to stabilize the draft, it is necessary to install at the outlet of the Ø 153mm nozzle for 

FH50ECP

 and 200mm for 

FH100ECP

, a tee fitted with a regulator flap.

Содержание FH100ECP

Страница 1: ...1 02 04 2019 Page INSTALLATION INSTRUCTIONS Wood Warm Air Heaters FH50ECP and FH100ECP Please read carefully the precautions for use and the instructions for use before any installation andcommissioning ...

Страница 2: ...r As soon as you decide to stop using the appliance you must not use parts that could constitute a Make sure that these instructions are always included with the device The regulatory protection of the device must be ensured in accordance with the classification standards for the professional premises where it is installed If the appliance is installed in a place where there are disabled people an...

Страница 3: ...airing d A perforated ash collection drawer with adjustable primary combustion air intake ruler e A chimney nozzle fitted with a draft key through which the combustion residues pass to be expelled through the smoke duct outside the heated enclosure Ventilation group The device is equipped with a medium pressure centrifugal fan which allows the connection of a distribution duct Chimney nozzle The a...

Страница 4: ...raft regulator This duct will be insulated as far as possible in double skin to avoid the dew point 1m after the discharge nozzle We offer an optional STAINLESS STEEL starter kit with buffer to facilitate maintenance by relocating the duct Never horizontal part with 90 elbows Elbow open 45 Elbow 90 Elbow 90 1m Elbow open 45 NO YES 4 02 04 2019 2 1 PACKAGING AND TRANSPORT 2 2 INSTALLATION INSTRUCTI...

Страница 5: ...ESSION The draft measurement must be carried out under the shutter which will allow the shutter to be balanced during the measurement The flue gas pipe must never be reduced to a diameter smaller than that of the outlet nozzle However there is no problem if the duct is of a larger diameter In the event of installation on an old masonry duct it is essential to pipe the duct 5 02 04 2019 Page During...

Страница 6: ...ect There are no voltage variations greater than 10 or 15 The fuses are in good condition There is no shortage of solid fuel NOTE Any repairs must be carried out by qualified technical personnel using original spare parts It is forbidden to open or manipulate the components of the generator with the exception of those provided for maintenance NEVER TURN ON THE GENERATOR WITHOUT CONNECTING THE ELEC...

Страница 7: ...the outside of the heat exchanger tubes if necessary by steam washing using a high pressure cleaner Empty and clean the ash drawer Vacuum the soot in the combustion chamber clean the brickwork Periodically replace damaged bricks see spare parts list Maintenance of the flue gas pipe Disassemble the duct components and carefully sweep the flammable deposit film Electric fan unit Blow out the inside ...

Страница 8: ...an to the 240V T electrical network load the fireplace to 30 of its capacity i e around 3 to 4 kg with low density wood but with rapid combustion of species wood from pallets poplars offcuts wooden logs After the total combustion of this charge repeat the operation with 50 of the charge draft key open to the max Commissioning after briquetting Load the appliance with wood or any other non pollutin...

Страница 9: ... regulation key Group electro fan Fairing exchanger heat Brickwork refractory ground Hopper air distribution Door of loading Drawer collection of Room of combustion 9 02 04 2019 2 7 EXPLODED VIEW OF THE UNIT Stainless steel grid Page ...

Страница 10: ...180 mm 700 mm 1110 mm 1180 mm 780 mm 620 mm 970 mm 182 mm 900 mm 1286 mm 1790 50 mm 845 mm 1340 50 mm 10 02 04 2019 2 8 DIMENSIONS Page Model FH50ECP Model FH100ECP ...

Страница 11: ... heating cycle Electrical cabinet V1 Indicator voltage presence P2 Inverter summer Winter Th Thermostat fan Description of the dashboard Thermostat Summer Fuse Stop Winter Voltage presence indicator Probe position thermostatic Passage of the probe thermostatic Position behind the grid In the 220 V mono motor connection box Power cable departure from the cabinet Earth lug 11 02 04 2019 2 9 DESCRIPT...

Страница 12: ...the loading that is to say 10 kg of wood for the model FH50ECP or 20 kg of wood for the model FH100ECP Page At 50 power i e around 150 C you can reload the wood heater with fuel to develop the maximum power i e 5 kg for the FH50ECP or 10 kg for the FH100ECP of additional fuel Functioning As soon as the vegetable fuel is burnt the flue gas temperature is indicated on the visual thermal control The ...

Отзывы: