2.3.3

 

Important general faults

Faults that have a "!!    Fault    !!" in the first display line can be reset by means of an inverter reset, provided that the
fault cause no longer exists. These are faults that are not necessarily caused by an inverter defect. They may as well
be caused by incorrect settings (parameterization) or by external influences.

If one of the following faults arises the inverter switches off electronically:

Fault message

on the display

Possible fault cause

!!Fault     !!

Not ready for travel

The inverter has received travel commands although it did not give a ready signal;
different travel commands too quickly one after another; travel command given
during check up; new travel command despite alarm signal.

!!Fault     !!

Fault tacho

No tacho connected, however parameterized. Fault in actual value acquisition
(tacho) detected; broken cable missing supply voltage at tacho, too high motor slip
i.e. slip frequency > 4-fold rated slip frequency, with this no actual value; pulse
frequency > 550 kHz; motor parameter incorrect; fault in the control; wrong type of
tacho (HTL-level.

!!Fault     !!

Overspeed

The permissible parameterized maximum speed has been exceeded during travel; in
case check parameterizing vRmax.

!!Fault     !!

Checksum custom.par

Board info defectly

!!Fault     !!

Overcurrent

Short-circuit; low-resistance earth fault.

!!Fault     !!

Overvoltage

Mains voltage failure or real under voltage; phase failure; fuse defective; power unit
defective incorrect adjustment of parameter V mains nom..

!!Fault     !!

Undervoltage

Mains voltage failure or real under voltage; phase failure; fuse defective; power unit
defective incorrect adjustment of parameter V mains nom..

!!Fault     !!

Invertertemp.

Inverter overloaded; defective fan; device utilization too high regarding installation
height; coolant temperature too high; ambient temperature too high

!!Fault     !!

Motor PTC thermistor

PTC thermistor at terminals X52:1/2; motor overloaded; bad or insufficient motor
ventilation or too high ambient temperature.

!!Fault     !!

Short circuit

Short circuit in the line inverter output/motor or in the motor itself;

!!Fault     !!

Earth fault

Fault in the motor or in motor supplies; device internal earth connection, too long
motor line; too small insulation resistance.

!!Fault     !!

Insulation fault

Only with 500 V devices and IT configuration:

Earth connection at one of the output phases (U2, V2, W2) or the intermediate circuit
potentials.

!!Fault     !!

Travelling contactor

Valid for 1 travelling contactor operation: Travelling contactor does not release after
travel stop or energy flow to the motor is not interrupted; connection X1:28 via the
break of the remaining contactor to X1:38 is missing. Operation with 2 travelling
contactors: Connect X1:28 (+24V) to X1:38.

!!Fault     !!

Direction-Signals

No direction information to the DYNAVERT L of both the direction inputs (X1:36;
X1:37) low or high: unpermissible status; parameterizing for direction setting faulty
(see 

P-SYSTEM DATA

).

Содержание DYNAVERT L

Страница 1: ...due to the factory adjustment 11 1 3 2 Setting the stopping accuracy 15 1 3 2 1 Setting the stopping accuracy with actual value feedback 15 1 3 2 2 Setting the stopping accuracy without actual value f...

Страница 2: ...rt storage The instructions for transport storage and proper use shall be complied with The climatic conditions shall be in conformity with prEN 50178 4 Installation The installation and cooling of th...

Страница 3: ...DYNAVERT L SAFETY INSTRUCTIONS 3 Version 11 10 02 4Bs0503en 002...

Страница 4: ...r residual voltage prior to starting any work Attention Electrical systems and machines may only be installed connected commissioned serviced and operated by experts who are trained applying the appli...

Страница 5: ...adhered to Device specific General remarks referring security The output side of DYNAVERT L inverters is stable at no load short circuit proof and earth fault proof The earthing cable of the electron...

Страница 6: ...COMMISSIONING DYNAVERT L 4Bs0503en 002 Version 11 10 02 6 1 Commissioning 1 1 Connecting diagrams customer connections L20 to L75 series 4...

Страница 7: ...optionally operation without tacho possible Track A in case of clockwise rotating field of the motor run 90 before track B 3 factory setting operation only with input AB X1 37 4 factory setting param...

Страница 8: ...y pressing Example Series of keystrokes for changing the rated speed v 3 Press button Press button to enter the menu P TRAVEL CURVE DATA Press button Press button down to v 3 Press button Press button...

Страница 9: ...DYNAVERT L COMMISSIONING 9 Version 11 10 02 4Bs0503en 002 next page H H H H H H H H H H H...

Страница 10: ...COMMISSIONING DYNAVERT L 4Bs0503en 002 Version 11 10 02 10 previous page All parameters marked with are hidden parameters in the menu tree...

Страница 11: ...or the normal travel Pay attention to the application limits limits for the travelling speed etc see Inverter Documentation 4Bs0323en chapt 1 2 1 sytem description system applications Connection For t...

Страница 12: ...m s cm m s cm cm up to 0 8 higher 125 0 08 9 15 0 8 1 2 150 0 1 12 25 2 Menu item P MONITORING parameterize v max v max should be 10 higher than the rated speed v 3 3 Menu item P SYSTEM DATA set v n r...

Страница 13: ...DYNAVERT L COMMISSIONING 13 Version 11 10 02 4Bs0503en 002 t_rel mec br 0 05...

Страница 14: ...s 5 Menu item P CHECK UP set Check Up Yes press button HINT If there is the message Fault v3 brak dist3 after check up the parameterized distance of the braking tag P TRAVEL CURVE DATA Brak dist 3 is...

Страница 15: ...be shorter than the physical required minimum braking distance from speed v3 Check the calculation of v n from section 1 3 1 page 11 item 3 Adjust the braking tags in the shaft if the values for the m...

Страница 16: ...lue curve According to the deviation from the actual rated value this method results in other values for the indicated Brak d S The actual measured braking distance should correspond centimeter exact...

Страница 17: ...hes off electronically and changes to fault condition A fault is indicated by the fault LED on the control panel In addition to this a clear text message is given on the status display and the fault i...

Страница 18: ...hat are caused by an inverter defect If such a fault cannot be reset a service station must be informed Fault message on the display Possible fault cause Inverter fault Wrong power unit Incorrect powe...

Страница 19: ...Overvoltage Mains voltage failure or real under voltage phase failure fuse defective power unit defective incorrect adjustment of parameter V mains nom Fault Undervoltage Mains voltage failure or real...

Страница 20: ...v N is higher than the permissible monitoring limit for readjusting speed v Nmax P CHECK UP Fault v R v Rmax Revision speed v R is higher than the permissible monitoring limit for revision speed vRma...

Страница 21: ...v n and max permissible speed v R result in a too high output frequency which the inverter may no longer generate P CHECK UP Fault v N too high Parameterized ratio v n and max permissible speed v N re...

Страница 22: ...V at X1 42 is missing Motor too small The connected motor is too small for automatic R1 measurement not possible Automatic R1 measurement not possible at the moment e g because of a fault or controlle...

Страница 23: ...03721 84313 Fax Nr 04146 1607 eab stade t online de Europe and Middle East Company NETHERLANDS LOHER Benelux Nijverheidsweg 75B NL 3771 ME Barneveld Tel Nr 0031 342 404667 Fax Nr 0031 342 404661 t br...

Отзывы: