1.7 FITTING TO PRE-CAST FLUE INSTALLATIONS

When installing this appliance into pre-cast flues, always ensure that the
spigot restrictor baffle has been removed.
To install the fire box in to pre-cast flue starter blocks, there must be at least
170mm from the mounting face of the fire to the rear of the pre-cast flue
starter block

to allow sufficient space for debris collection.  It is important to 

consider this depth when choosing a fire surround as the thickness of the fire 
surround must be sufficient to give a total depth of 

at least 170 mm to the rear of

the starter block

, otherwise there will be insufficient depth.  To increase this depth

the optional black 50mm spacer frame may be purchased, this will reduce the
depth required to 

120mm

or the fire surround may be packed away from the wall

using suitable non-combustible board, providing the installation is correctly sealed.
If in doubt about the suitability of the fire contact CFM Europe Ltd. for advice
before proceeding.  

This fire has been designed to fit standard 100mm pre-

cast starter blocks with 3 inch rebated surrounds.

It is important to ensure that the pre-cast flue is in good condition and is free from
extruded mortar or sealant from between the flue blocks.

This appliance has been tested for use in a pre-cast flue block complying
with BS EN 1858.  In accordance with BS EN 1858, pre-cast flues built with
directly plastered faces (front or rear) are not correctly installed as to ensure
proper operation with any type of gas fire.  In some instances of this flue
construction, temperature cracking of surface plaster may occur through no
fault of the appliance.  An air gap or some form of insulation material should
be installed to prevent normal flue temperatures from damaging wall 
surfaces.

1.8 FITTING TO PRE-FABRICATED TWIN WALL METAL FLUE BOXES

The appliance may be fitted to twin wall metal flue boxes conforming to the con-
structional requirements of BS 715, (for example the Selkirk LFE 125 box).  The
box must have a minimum flue diameter of 125mm internal and minimum internal
dimensions of 160mm deep by 580mm high by 350mm wide.  There are no maxi-
mum dimensional requirements for the box.  The top face of the box must be 
insulated with a minimum thickness of 50mm of non-combustible mineral wool 
insulation or similar material.  The flue box must stand on a non-combustible base
of minimum thickness 12mm.  

1.9

HEARTHS

This appliance must only be installed on to a concrete or non-combustible hearth.
The hearth material must be a minimum thickness of 12mm with the top surface at 
least 50mm above the floor.  The hearth must be fitted symmetrically about the fire 
opening and have a minimum width of 760mm and a minimum projection of
300mm forwards from the fire opening.  If the black spacer frame is used, the
hearth projection forward from the fireplace opening will require to be 350mm.

8

Содержание Linear Pebble

Страница 1: ...0161 620 6677 Linear Pebble DECORATIVE PEBBLE FUEL EFFECT GAS FIRE Installation and Maintenance Instructions Hand these instructions to the user Model No s FRDPU0MN are for use on Natural Gas G20 at a...

Страница 2: ...lage Monitoring System 9 Section 2 Installation of Fire 2 1 Unpacking the fire 10 2 2 Installing the fire box 10 15 2 3 Gas soundness and burner pressure 16 Section 3 Assembling Fuel Bed and Commissio...

Страница 3: ...n Gross Heat Input 4 2 kW Cold Pressure 20 0 1 0 mbar Ignition Push button Piezo Electrode Spark Gap 4 5mm Packed Weight without fender 15 kg Fire box Dimensions with linear trim fitted Width with lin...

Страница 4: ...B S E N 1858 Chinmeys Components Concrete Flue Blocks 8 I S 813 1996 Domestic Gas Installation Republic of Ireland No purpose made additional ventilation is normally required for this appli ance when...

Страница 5: ...f additional overhang over 150mm 1 5 FLUE CHIMNEY INSPECTION Before commencing installation a flue or chimney should be inspected to ensure that all the following conditions are satisfied 1 Check that...

Страница 6: ...e test must always be carried out during commissioning of the appliance 1 6 FIRE PLACE OPENING AND CHIMNEY CATCHMENT SPACE The front opening of the fire place must be between 375 and 440 mm wide and b...

Страница 7: ...extra This appliance is suitable for use in fireplaces fitted with an existing chairbrick without the need for removal of the chairbrick providing the minimum depth of the fireplace exceeds 260mm If...

Страница 8: ...with BS EN 1858 In accordance with BS EN 1858 pre cast flues built with directly plastered faces front or rear are not correctly installed as to ensure proper operation with any type of gas fire In s...

Страница 9: ...oducts in the room in which the fire is operated The following are impor tant warnings relating to this spillage monitoring system 1 The spillage monitoring system must not be adjusted by the installe...

Страница 10: ...uction book and Installation book 1off Linear Ashpan 2 2 INSTALLING THE FIRE BOX Establish which type of flue you are intending to install the fire in to 225 x 225mm 9 inch x 9 inch brick built chimne...

Страница 11: ...arth is protected from damage and carefully lift the fire box into the fire opening then slide it back into position Check that the fire box flange fits flush to the sealing face of the fire surround...

Страница 12: ...elbow The gas connection to the appliance should be made to the isolating inlet elbow using 8mm rigid tubing There must be no soldered joints within the firebox See fig 5 6 below for suggested concea...

Страница 13: ...nd using screws which are supplied The foam seal supplied must be fitted around the perimeter of the spacer in a goalpost arrangement to ensure a seal is achieved to the fireplace To fit using the pre...

Страница 14: ...mum travel for the tensioning nut i Fit a screwed nipple on to each of the cables and pull hand tight up against the tensioning screw then secure each nipple with a flat bladed screwdriver See fig 8 b...

Страница 15: ...irebox fixing method is as follows In installations where the cable method is not suitable e g loose masonary in rear of fire opening the firebox can be secured to the fire surround using four screws...

Страница 16: ...e full on position d Check that the gas pressure is 20 0 mbar 1 0mbar 8 0 in w g 0 4 in w g e Turn off the fire remove the manometer and refit the pressure test point screw Check the pressure test poi...

Страница 17: ...the front ceramic rail is correctly located onto the lip on the burner front ceramic support See fig 11 below Fig 11 c Pick pebbles A to E and arrange along the the front rail ensuring that they are...

Страница 18: ...ig 13 below Fig 13 e Select pebbles K L M and arrange along the rear of the fuelbed using the ribs in the rear of the fuelbed as a guide for placement See fig 14 below Fig 14 f Select the two small pe...

Страница 19: ...the release of dust is kept to a minimum To ensure that the release of fibres from these R C F articles is kept to a minimum dur ing installation servicing we recommend that you use a HEPA filtered v...

Страница 20: ...the main burner will go out but the pilot will remain lit g Slightly depress the control knob and turn to the off position the pilot will now be extinguished WARNING If the fire goes out for any reaso...

Страница 21: ...be repeated with the fan running on maximum and all interconnecting doors open f After ensuring that the fire is safe to use it should be left on high position to fully warm up During this time a sli...

Страница 22: ...and put them in a safe location Remove the loose pebbles from the fuel bed and front ceramic rail Remove the front ceramic from the rail Unscrew the two pozi driv fixing screws which secure the burne...

Страница 23: ...ontrol tap locates with a flat in the control panel Carry out a gas tightness test after re assembly 4 4 Removing the Oxy Pilot Assembly Note Because this appliance is fitted with an atmosphere sensin...

Страница 24: ...set B 77250 L H Fibre Board B 68930 R H Fibre Board B 68940 Upper Rear Fibre Board B 68910 Lower Rear Fibre Board B 68920 Piezo Igniter B 1320 Ignition Wire B 39030 Gas Valve B 36990 This appliance mu...

Отзывы: