Flavel FSCC12MN Скачать руководство пользователя страница 8

1.7 FITTING TO FIREPLACES WITH EXISTING CHAIRBRICKS AND

CONVENTIONAL BRICKBUILT CHIMNEYS

This appliance is suitable for use in fireplaces fitted with an existing chairbrick

without the need for removal of the chairbrick, providing the minimum depth of the

fireplace exceeds 190mm. If the depth is less than 190mm then the spacer

(optional) must be used to give a minimum clearance from the rear of the fire to

the rear of the chairbrick of at least 90mm to allow sufficient space for the collec-

tion of debris which may fall down the chimney. The fireplace must be checked to

ensure that no part of the chairbrick is within 50mm of the flue outlet of the fire

when installed.

1.8 FITTING TO PRE-CAST FLUE INSTALLATIONS

When installing this appliance into pre-cast flues, always ensure that the

spigot restrictor baffle has been removed.

To install the fire box in to pre-cast flue starter blocks, there must be at least

132mm from the mounting face of the fire to the rear of the pre-cast flue

starter block

to allow sufficient space for debris collection. It is important to

consider this depth when choosing a fire surround as the thickness of the fire

surround must be sufficient to give a total depth of

at least 132 mm to the rear of

the starter block

, otherwise there will be insufficient depth. To increase this depth

the fire surround may be packed away from the wall using suitable

non-combustible board, providing the installation is correctly sealed. If in doubt

about the suitability of the fire contact BFM Europe for advice before proceeding.

It is important to ensure that the pre-cast flue is in good condition and is free from

extruded mortar or sealant from between the flue blocks.

This appliance has been tested for use in a pre-cast flue block complying

with BS EN 1858. In accordance with BS EN 1858, pre-cast flues built with

directly plastered faces (front or rear) are not correctly installed as to ensure

proper operation with any type of gas fire. In some instances of this flue

construction, temperature cracking of surface plaster may occur through no

fault of the appliance. An air gap or some form of insulation material should

be installed to prevent normal flue temperatures from damaging wall

surfaces.

1.9 FITTING TO PRE-FABRICATED TWIN WALL METAL FLUE BOXES

The appliance may be fitted to twin wall metal flue boxes conforming to the con-

structional requirements of BS 715, (for example the Selkirk LFE 125 box). The

box must have a minimum flue diameter of 125mm internal and minimum internal

dimensions of 160mm deep by 580mm high by 350mm wide. There are no maxi-

mum dimensional requirements for the box. The top face of the box must be

insulated with a minimum thickness of 50mm of non-combustible mineral wool

insulation or similar material. The flue box must stand on a non-combustible base

of minimum thickness 12mm.

8

Содержание FSCC12MN

Страница 1: ...EFFECT GAS FIRE Installation and Maintenance Instructions Hand these instructions to the user Model No FSCC12MN FSCC23MN FSCC42SN FSCC53SN are only for use on Natural Gas G20 at a supply pressure of...

Страница 2: ...2 4 Gas Tightness Inlet Pressure SC models 19 20 Section 3 Assembling Fuel Bed and Commissioning 3 1 Assembling the ceramics and fuel bed 20 23 3 2 Lighting the appliance MC models 24 3 3 Lighting th...

Страница 3: ...CC53SN 19 0 kg FSCC12MN FSCC23MN Fire box Dimensions with trim fitted Width with standard trim no spacer 480mm Height with standard trim no spacer 590mm Depth overall without fender 125mm Depth Flush...

Страница 4: ...nd flues 7 B S E N 1858 Chinmeys Components Concrete Flue Blocks 8 I S 813 1996 Domestic Gas Installation Republic of Ireland No purpose made additional ventilation is normally required for this appli...

Страница 5: ...150mm 1 5 FLUE CHIMNEY INSPECTION Before commencing installation a flue or chimney should be inspected to ensure that all the following conditions are satisfied 1 Check that the chimney flue only ser...

Страница 6: ...ied out during commissioning of the appliance 1 6 FIRE PLACE OPENING AND CHIMNEY CATCHMENT SPACE The front opening of the fire place must be between 330 and 430 mm wide and between 550 and 570mm high...

Страница 7: ...h mm Minimum Depth Required mm 330 minimum opening width 222 340 218 350 215 360 211 370 205 380 199 390 193 400 189 410 183 420 178 430 172 440 maximum opening width 168 For example if the appliance...

Страница 8: ...e fire surround may be packed away from the wall using suitable non combustible board providing the installation is correctly sealed If in doubt about the suitability of the fire contact BFM Europe fo...

Страница 9: ...oxygen sensing pilot This is designed to shut the fire off in the event of a partial or complete blockage of the flue causing a build up of combus tion products in the room in which the fire is opera...

Страница 10: ...book and Installation book 2 2 INSTALLING THE FIRE BOX Establish which type of flue you are intending to install the fire in to 225 x 225mm 9 inch x 9 inch brick built chimneys 175mm 7 inch diameter...

Страница 11: ...ted from damage and carefully lift the fire box into the fire opening then slide it back into position Check that the fire box flange fits flush to the sealing face of the fire surround or wall with n...

Страница 12: ...present c Remove the burner To allow burner removal the control lever operat ing cable must be removed The control lever operating cable can be seen running across the base of the fire below the burne...

Страница 13: ...g screws at either side of the firebox and the two fixing screws at the base of the fire See fig 7 below Carefully pull the base of the burner forwards from the fuel bed support panel The burner can n...

Страница 14: ...g 8mm rigid tubing There must be no soldered joints within the firebox See fig 8a 8b below for suggested concealed pipe layouts Fig 8a Fig 8b Note Before breaking into the gas supply a pressure drop t...

Страница 15: ...which in turn will damage the burner and control systems of the product Fig 9 below shows a correctly sealed installation Fig 9 PLEASE NOTE Seal off unused gas inlet apertures and cable fixing holes...

Страница 16: ...of the cables through one of the two holes on each side of the flue outlet shroud g Position the fire carefully on the protected surface of the hearth and reach into the fire opening Thread each of t...

Страница 17: ...l Refit the burner Fit the four retaining screws and check that the burner is correctly locked into position On slide control models refit the control cable To do this firstly locate the nipple on one...

Страница 18: ...otherwise serious damage may be caused to the gas control valve on the fire The other firebox fixing method is as follows In installations where the cable method is not suitable e g loose masonary in...

Страница 19: ...point screw for gas tightness with the appliance turned on using a suitable leak detection fluid or detector 2 4 GAS TIGHTNESS AND INLET PRESSURE SLIDE CONTROL MODELS a Remove the pressure test point...

Страница 20: ...t and is not lodged on the burner See fig 13 below Fig 13 b Position the two halves of the front ceramic L H R H on the locating channel in the front ceramic ensuring it is located onto the lip on the...

Страница 21: ...hey are evenly spaced Use the recess s in the front ceramic rail as a guide for placement See fig 15 below Fig 15 d Select four of the large coals and arrange behind the front row of coals ensuring th...

Страница 22: ...ear of the fuelbed using the recesses in the rear of the fuelbed as a guide for placement See fig 17 below Fig 17 f Select three of the medium sized coals and arrange along the fuelbed behind the seco...

Страница 23: ...tory Ceramic Fibre articles is kept to a minimum during installation and servicing we recommend that you use a HEPA filtered vacuum to remove any dust accumulated in and around the appliance before an...

Страница 24: ...trol knob and turn to the off position the pilot will now be extinguished 3 3 LIGHTING THE APPLIANCE Slide Control Models a Turn on the isolation valve Depress the control lever fully downwards to the...

Страница 25: ...5 10 minutes If the test indicates that spillage is occurring and the flue restrictor baffle has been fitted it should be removed and the test repeated after the fire has cooled d If spillage persists...

Страница 26: ...a safe location Remove the loose coals from the fuel bed and front ceramic rail Remove the front ceramic from the rail Unscrew the two pozi driv fixing screws which secure the burner heat shield and r...

Страница 27: ...t it is not possible to replace the thermocouple separately because the thermocouple position is factory set to a tight tolerance Any replacement of parts on the pilot requires a complete new pilot as...

Страница 28: ...ly tension the operating cable To do this first set the control lever to the horizontal central position this is the position which creates maximum tension in the operating cable Refit the operating c...

Страница 29: ...d the two inline leads from the microswitch 4 8 3 Unscrew and remove the two pozi drive screws which secure the pilot assembly to the burner Remove the pilot 4 8 4 Re assemble in reverse order and car...

Страница 30: ...ush in the gap between the two lengths of p t f e sleeve Ensure that the cable is located in the retaining hole in the locking bush and tighten the screw sufficiently to retain the cable but still all...

Страница 31: ......

Страница 32: ...55640 Slide Valve SC models B 40890 Ignition Wire SC models 750 14340 Spark Generator SC models B 13540 Microswitch SC models 750 15600 Piezo Igniter MC models B 1320 Ignition Wire MC models B 14340 G...

Отзывы: