FTS 350i-2 USER MANUAL 

Flash Technology, LLC 

Revision A – 4/21/2022 

12 

2.4.3 CHECK ALARM STATUS  

VIA REMOTE CONTROL AND STATUS FLASHES 

After 5 minutes of operation, check the alarm status using the remote control. Point the remote control, within 20 
feet of the beacon, and press the “1” button. If there are no alarm conditions, the unit will respond with a single 
quick blink. If multiple quick blinks are observed, refer to 

Troubleshooting

 (page 14). 

VIA ALARM RELAY 

After 5 minutes of operation, check the alarm contact to ensure there are no alarm conditions. A multi-meter may 
be used to check for continuity between the COM (Red) and NC (Orange) conductors. The contact is closed when 
the beacon is powered, operating normally and no fault is detected. If an alarm condition is observed, refer to 

Troubleshooting

 (page 14). 

2.4.4 CHECK MONITORING STA TUS 

Confirm monitoring status by disconnecting power to the beacon. This should create an alarm. 

 

SECTION 3 – BEACON OPERATION 

3.1 SYSTEM OVERVIEW 

The standard 5-conductor power and alarm cable provides connection for the AC line (3 wires) and alarm 
monitoring connections (2 wires). Se

beacon wiring instructions

 (page 10). The optional 10-conductor cable 

provides the same connections and adds connections for the auxiliary control input (2 wires). 

The AC input power requirement is 100-240 VAC 50/60Hz. The dry contact alarm connection is closed when the 
beacon is operating normally and no fault is detected. 

The beacon senses ambient light using a photodiode. This determines night mode and enables the LED beacon 
flash. A GPS antenna and integrated receiver permit synchronization with other beacons. The Driver PCB detects 
alarm conditions including beacon failure, photodiode alarm and synchronization fault. 

The LED engine assembly contains high-performance RED and INFRARED (IR) LEDs, which illuminate when powered 
by the Driver PCB. 

The power supply, with surge suppressors, are located in the base of the beacon. The power supply generates the 
proper DC current to the Driver PCB when AC line voltage is applied at its input. The surge suppressors provide 
protection from incoming lightning and transient voltage induced surges. 

3.2 REMOTE CONTROL OPERA TION 

When purchasing the FTS 350i-2 beacons in sets of 1-10, a single remote control is included (1 beacon = 1 remote, 
2 beacons = 1 remote, 3 beacons = 1 remote etc…). Additional remote controllers may be ordered (PN 
11000017081) to assist with installation, configuration and troubleshooting. The remote control has the following 
functionality: 

 

Содержание FTS 350i-2

Страница 1: ...FTS 350i 2 USER MANUAL Flash Technology LLC Revision A 4 21 2022 1 FTS 350i 2 LED Integrated Beacon Red LED Obstruction Lighting System Reference Manual Part Number F7913502...

Страница 2: ...e every effort has been made to ensure that the information in this manual is complete accurate and up to date Flash Technology assumes no liability for damages resulting from any errors or omissions...

Страница 3: ...l times when you expose circuits and components and when you operate maintain or service this equipment AVOID TOUCHING LIVE CIRCUITS Avoid touching any component or any part of the circuitry while the...

Страница 4: ...tifications 6 1 2 Beacon Component Identification 7 Section 2 Installation Unpacking Mounting Wiring and Checkout 8 Warning 8 Installation Procedures 8 2 1 Unpack the FTS 350i 2 8 2 2 Mount the Beacon...

Страница 5: ...2 1 Beacon flashhead Dimensions and Mounting Outline 9 Figure 2 2 Mounting Outline with Adapter Bracket 10 LIST OF TABLES Table 2 1 Standard Power Alarm Connections 10 Table 2 2 Power Alarm and Radar...

Страница 6: ...sures maximum visibility to pilots in all circumstances while providing significant electrical power savings over incandescent fixtures The lighting system is equipped with an alarm contact to monitor...

Страница 7: ...N COMPONENT IDENTIFICATION Figure 1 1 Beacon External View Figure 1 2 Beacon Base Assembly Fresnel Lens and LED Engine Assembly GPS Antenna Light Collector Photodiode Cable Pigtail Base Assembly Surge...

Страница 8: ...ght that interferes with mode change operation The GPS antenna located on top of the beacon must have an unobstructed view of the sky for proper reception and synchronization The beacon is equipped wi...

Страница 9: ...FTS 350i 2 USER MANUAL Flash Technology LLC Revision A 4 21 2022 9 Note All dimensions are in inches millimeters in brackets Figure 2 1 Beacon flashhead Dimensions and Mounting Outline...

Страница 10: ...per operation and protection of the beacon Optional 75 foot 100 foot and custom cables lengths are available Optional dry contact monitoring connections permit monitoring of lighting system operation...

Страница 11: ...ire back do not use Bare Drain Cut wire back do not use 2 4 VERIFYING OPERATION Apply power to the beacon and verify operation 2 4 1 POWER UP When powered up the beacon will begin flashing after sever...

Страница 12: ...ptional 10 conductor cable provides the same connections and adds connections for the auxiliary control input 2 wires The AC input power requirement is 100 240 VAC 50 60Hz The dry contact alarm connec...

Страница 13: ...ctive after 19 hours without a mode change Disabled PD alarm functions are turned OFF for areas that experience extended day nighttime conditions Pressing button 3 will show the current PD Alarm setti...

Страница 14: ...n and the Induced LI flash alarms from button 8 Also cancels the 15 min forced red mode on power up SECTION 4 MAINTENANCE AND TROUBLESHOOTING 4 1 MAINTENANCE No regularly scheduled maintenance is requ...

Страница 15: ...respond with a single quick blink to a button press of 1 on the remote control Yes No Beacon is operational Replace the unit Table 4 4 Troubleshooting Beacon Flashes in Daytime 4 3 BEACON REPAIR PROC...

Страница 16: ...TEGRATED LED BEACON 1350200 5 3 RMA POLICY If any system or part s purchased from Flash Technology needs to be returned for any reason subject to the warranty policy please see the current RMA policy...

Отзывы: