Flanders High Temperature Rigid Filter PB1003 Скачать руководство пользователя страница 2

Operating

Nominal Size

500 fpm

Media

Weight

Efficiency

Limit 

º

F

H x W x D (inch)

Rating

Area

Each

cfm

pd

(sq. ft.)

(lbs)

750

24 x 24 x 12

2000

.45

140

26

60-65%

24 x 12 x 12

1000

69

21

900

24 x 24 x 12

2000

.50

175

28

24 x 12 x 12

1000

90

22

750

24 x 24 x 12

2000

.55

140

26

80-85%

24 x 12 x 12

1000

69

21

900

24 x 24 x 12

2000

.60

175

28

24 x 12 x 12

1000

90

22

750

24 x 24 x 12

2000

.65

140

26

90-95%

24 x 12 x 12

1000

69

21

900

24 x 24 x 12

2000

.70

175

28

24 x 12 x 12

1000

90

22

Notes:

1.  PD represents clean pressure drop in inches w.g. The recommended final pressure drop is 2.5 inch w.g.
2.  Operation down to zero velocity is satisfactory for all models.
3.  Efficiencies are average and are based on ASHRAE Standard 52.1 and 52.2 dust spot test methods.

Performance values stated may be averages typical of the products listed. Contact factory for actual perform-
ance test reports on specific products.

4. Perfmormance values shown in this publication may be averages or estimates intended to generally represent

product styles.  Always contact factory for latest actual test data on specific Flanders Precisionaire models.

1.0 General

1.1 High

temperature

rigid

filters

shall

be

PrecisionCell HT separator type as manufactured
by Flanders.

1.2 Filter sizes and temperature ranges shall be as

scheduled on the drawings.

2.0 Filter Construction

2.1 Filters shall be constructed by pleating a contin-

uous sheet of wet-laid micro-fine glass media
into closely spaced pleats with hemmed-edge
corrugated aluminum separators.

2.2 The filter pack shall be sealed into a 24 ga.

aluminized

steel

frame

with

fire-retardant

sealant.

2.3 Expanded metal aluminized steel faceguards

shall be installed on the air entering and air leav-
ing sides.

2.4 A 1/2” “T” strap shall be installed on the down-

stream side and 1/2” horizontal strap on the air
entering side.

3.0 Performance

3.1 Initial and final resistance shall not exceed the

scheduled values.

3.2 Media area shall equal that of the scheduled

high temperature filter.

3.3 The manufacturer shall guarantee performance

as outlined in section 7.4 of ARI Standard 800.

Guide Specifications

REPRESENTED BY:

Flanders - PrecisionAire

Foremost in Air Filtration

Toll Free: 1-800-637-2803