Flanders Filters - Foremost in Air Filtration            

Toll Free: 1-800-637-2803

1

High Capacity Design

The Alpha 2000 High Capacity HEPA filter is avail-
able in a nominal 12” depth configuration. It is
designed for optimum performance and low operat-
ing costs in both new and replacement systems.
The Alpha 2000 saves space, energy, and material
and labor costs with 40% more media area than the
standard capacity Alpha Cell filter.

Save Space

Alpha 2000 HEPA filters operate at 500 fpm (2000
cfm for a 24” x 24” size) at 1.35 inch w.g. clean
pressure drop versus conventional Alpha Cell filters
that operate at 250 fpm and .80 inch w.g. clean
pressure drop.

Construction

A popular  construction option consists of 16 ga.
galvaneal frames and moisture-resistant microfine
wet-laid fiberglass media folded over hemmed-
edge low amplitude corrugated aluminum separa-
tors. The filter pack is bonded to the frame by a fire-
retardant urethane elastomer to provide a rigid
leak-free assembly.   

Save Energy

Alpha 2000 filters in a conventional HEPA filter
bank impose a lighter load on the fan when operat-

ed at conventional 250 fpm velocities during the life
of the filters. The Alpha 2000 99.97% and 99.99%
high capacity 24” X 24” X 11.5” filter has a clean
pressure drop of 1.0 inch w.g. at 1500 cfm, com-
pared to standard Alpha Cell filters with a clean
pressure drop of 1.50 inch w.g. at the same air flow.

Save Replacement  Material and Labor
Costs

Savings are significant with high capacity Alpha
2000 filters. They operate at lower velocities and
provide life cycles up to three times the life of stan-
dard capacity filters. Savings are achieved in
replacement materials and labor costs as a result of
fewer filters.

Alpha 2000

High Capacity HEPA Filters

Bulletin PB1402-0107

Important Features

•  Efficiencies are 99.97% and 99.99% on 0.30

and 99.9995% on 0.12 micrometer particles.

• High capacity Alpha 2000 filters can reduce the

filter bank size

• Corrugated aluminum separators stabilize the

moisture-resistant media pack (separator
style)

•  Available as a separatorless media filter with a

self-supporting media pack (*Pureform)

• Available in a variety of frame materials in

gasket or fluid seal design. 

0

125

250

375

500

625

Air Velocity (fpm)

Pressure Drop (in. w

.g.)

Alpha 2000 Pressure Drop vs. Air Velocity

2.20

2.00

1.80

1.60

1.40

1.20

1.00

0.80

0.60

0.40

0.20

0.00

HEPA
ULPA

®

F O R E M O S T   I N   A I R   F I L T R A T I O N

Содержание FFI Alpha 2000

Страница 1: ...tional 250 fpm velocities during the life of the filters The Alpha 2000 99 97 and 99 99 high capacity 24 X 24 X 11 5 filter has a clean pressure drop of 1 0 inch w g at 1500 cfm com pared to standard Alpha Cell filters with a clean pressure drop of 1 50 inch w g at the same air flow Save Replacement Material and Labor Costs Savings are significant with high capacity Alpha 2000 filters They operate...

Страница 2: ...upport ing and self separating Pureform Media Pack The Pureform Filter offers many advantages over conventional Separator Style HEPA Filters More usable media area for longer service life because of higher dust holding capacity Reduced cost of ownership because of longer service life Maximum utilization of the media Can handle some harsh environments which may attack aluminum separators Media pack...

Страница 3: ...ames Upon request the filter will have a stamp indicating compliance with UL 900 Class 1 UL 586 UL 586 is typically required for Nuclear Grade HEPA Filters Many of the Flanders non Nuclear HEPA Filters meet the requirements of UL 586 To be listed under UL 586 filters must be submitted to Underwriters Laboratories for extensive testing including spot flame and environmental exposure to heated air U...

Страница 4: ...efficiency of 99 97 on 0 30 micrometer parti cles when tested at rated capacity on a Q 107 Penetrometer in accordance with IEST RP CC 001 3 Type A Measure the upstream and down stream concentration of these particles with a light scattering photometer determine the pene tration and calculate the efficiency 3 3 Alpha 2000 Scan Tested HEPA Filters shall have a minimum efficiency of 99 99 on 0 30 mic...