Filter Depth

D = 5-7/8

F = 11-1/2

Filter Face Size (H x W)

B=8”

N=30”

R=6

C=12” P=36” S=72”
E=18”

H=42” U=113/8

G=24”   Q=48”  Y=23 3/8

ODD Size Designator

Odd size designators are an alpha numeric descrip-
tion. The first two digits specify the height whole num-
ber with an alpha designator specifying the height
fraction. The second two digits specify the width
whole number with an alpha designator specifying
the width fraction. And the last alpha designator
specifies the depth. If he height or width is less than
10 inches, use a 0 in front of the dimension.

A = O”

E=1/4”

J=1/2”

N=3/4”

B=1-1/16”

F=5/16”

K=9/16”

P=13/16”

C=1/8”

G=3/8”

L=5/8”

Q=7/8”

D=3/16”

H=7/16”

M=11/16”     R=15/16”   

Hardware

O = None
T = Extractor Clips

Efficiency

007 = 99.97% DOP
99.99% on .30 micrometers=SU Sealant

Capacity / Pack Style

C = Separator

Frame Material

02 = 16 GA 409 Stainless
03 = 16 GA 304 Stainless

Frame Style

03 = Double-Turned Flange
05 = 3/4 in. Deep Channel

Sealant Material

IE = High Temperature Silicone
IG = Ceramic and Glass Mat
SE = high Temperature Silicone Scan Tested (99.99% on
0.30 micrometers)

Gasket Material         Gasket Location

0 = None

0 = None

3 = Silicone Sponge

1 = Upstream

4 = Woven Glass

2 = Downstream

5 = Blu Jel

3 = Both Sides

Guide Specifications

1.0 General

1.1 High temperature separator style HEPA filters shall

be Alpha HT models as manufactured by Flanders.

1.2 Filter sizes, capacities and construction options

shall be as scheduled on the drawings.

2.0 Filter Construction

2.1 The filter pack shall be constructed by pleating a

continuous sheet of non-woven water-resistant
fiberglass media around hemmed-edge corrugated
aluminum separators.

2.2 The filter pack shall be sealed into a (409 stainless

steel) (304 stainless steel) frame with a high tem-
perature silicone sealant rated for 500°F or a glass
pack sealant rated for 1,000°F in exhaust applica-
tions.

2.3 (A chlorastic silicone gasket) (a woven glass gasket)

shall be provided to seal the filter in the mounting
device (Gasket Seal). A silicone gel shall be provid-
ed in a channel on one side to seal the filter in the
mounting device. filters with silicone gel have a max-
imum service temperature of 390°F (Gel Seal)

3.0 Performance

3.1

Initial and final resistances shall not exceed the

scheduled values.

3.2 Alpha HT HEPA Filters shall have a minimum effi-

ciency of 99.97% on 0.30 micrometer particles when
tested at rated capacity on a Q-107 Penetrometer in
accordance with IEST-RP-CC-001.3, Type A. Each
filter shall be challenged with an approved nearly
monodispersed oil aerosol of 0.30 micrometer size.
Measure the upstream and downstream concentra-
tion of these particles with a light scattering pho-
tometer, determine the penetration and calculate the
efficiency.

3.3 Alpha HT Scan Tested HEPA Filters shall have a

minimum efficiency of 99.99% on0.30micrometer
particles when tested at rated capacity on a Q-107
Penetrometer in  accordance with IEST-RP-CC-
001.3, Type C. The scan test shall consist of chal-
lenging the filter

with a high concentration of an

approved oil aerosol or PSL Spheres. Utilizing a
photometer or particle counter, the media pack and
the pack-to-frame seal shall be scanned to insure
that there are no leak greater than .01% of the
upstream concentration at 100 fpm face velocity.

REPRESENTED BY:

®

Flanders Filters, Inc.
531 Flanders Filter Road
Washington, NC  27889

Phone: (252) 946-8081
Toll Free: (800) 637-2803
Fax: (252) 946-3425

Website: www.flanderscorp.com

ALPHA HT COMPONENT CHART

0   -   0 0 7   -   C   -   0 2   -   0 3   -   I E   -   3 2   -   0 0   -   G G   -   F

Faceguard Material

Faceguard Location

0 = None

0= None

G = Aluminized Expanded Metal

1 = Upstream

5 = 22GA.SS 4x4 Mesh

2 = Downstream
3 = Both