VESDA-E VEU-A10 Product Guide
www.xtralis.com
5
2
Product Information
2.1
Detector Components
The VEU-A10 detector contains field-replaceable Filter, Aspirator and Chamber Assembly components.
These are shown below in Figure 2-1.
F
D
C
B
E
Legend
A
Fascia with 3.5"
touchscreen display
B
Filter
C
Chamber Assembly
D
Aspirator
E
Sampling Module
F
Base
Figure 2-1: Detector components
Refer to Chapter 7 for further information regarding maintenance scheduling and availability of spare parts.
2.2
How the VEU-A10 works
An air sampling pipe network collects samples from the protected area. The integrated aspirator draws air into
the sampling pipe(s).
The air from each sampling pipe passes through an air flow sensor and then a sample of the air is drawn into
the smoke detection chamber via the sampling module, after first passing through the replaceable filter.
A further filter provides filtered clean air to protect the optical surfaces inside the detection chamber from
contamination.
The detection chamber uses a short wavelength laser light source in conjunction with photodiodes and
advanced imaging technology to achieve optimum response to a wide range of smoke types.
If the detected smoke is higher than the set alarm thresholds it is reported as an Alert, Action, Fire 1 or Fire 2
alarm condition.
Air is exhausted from the VEU-A10 and may be vented back into the protected zone.
Alarms can be signalled via Relays and VESDAnet. Ethernet and WiFi can be used for configuration and
secondary monitoring, and a USB interface is provided for initial setup.
The detector has a LED plus LCD user interface. A series of LEDs display Alarm, Fault, Disable and detector
power on status. The detector has a buzzer which can be configured to signal alarm, fault, disable and
standby status. A button allows the user to Reset or Disable the detector or to acknowledge status. In
addition an LCD displays detector status including smoke level and a smoke level bar graph, alarm
thresholds, trouble status, % airflow level, normalization status and filter life used.
Содержание VESDA-E VEU-A10
Страница 1: ...VESDA E VEU A10 Product Guide November 2018 Document 22077_12 Part Number 30334 ...
Страница 2: ......
Страница 10: ...VESDA E VEU A10 Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEU A10 Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEU A10 Product Guide 48 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VEU A10 Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 100: ...VESDA E VEU A10 Product Guide 94 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 106: ...VESDA E VEU A10 Product Guide 100 www xtralis com This page is intentionally left blank ...
Страница 110: ...VESDA E VEU A10 Product Guide 104 www xtralis com This page is intentionally left blank ...
Страница 116: ...VESDA E VEU A10 Product Guide 110 www xtralis com Z zone 59 61 79 105 ...