Flame FP-35 Скачать руководство пользователя страница 10

10 

EQUIVALENT VENT LENGHT (EVL) 

The longer the run of pipe in your installation, the more restriction there is 
in the system. Therefore, larger diameter pipe should be used for longer 
runs. 

 

Use 4” pipe if you have more than 

15 feet

 of Equivalent Vent Length 

(EVL). 

 

Horizontal runs shall not exceed 10 feet of EVL. 

 

To calculate EVL, use the following conversions table: 

Qty 

Type of pipe 

EVL equivalent(ft) 

90° elbow or “T” 

1 45° 

elbow 

1 ft 

Horizontal pipe run 

1 ft 

Vertical pipe run 

0.5 

NOTE: At altitudes above 3,000 feet, we suggest the use of 4” diameter 
vent at an EVL of 7 feet or more. 

Here is an example on how to calculate the EVL of your installation.  (See 
Figure 15) 

(3 x 4’ of vertical length = 12’ x 0.5 = 6 EVL) + (1 x elbow or "T" = 5 EVL) + 
(2 x 1’ of horizontal length = 2 EVL) 

Total EVL = (6 + 5 +2) = 13.  So 3” diameter vent is allowed 

INSTALLATION CONFIGURATIONS

 

A. HORIZONTALLY THROUGH WALL 

(REFER TO FIGURE 7, 8 OR 10) 

 

NOTE: 

Follow Vent chimney manufacturer’s instructions. 

 
1. 

Position stove, adhering to clearances shown in Figures 1 & 2. 

 
2. 

Determine position of hole in wall; directly behind stove exhaust vent 
(refer to figure 4). 

 
3. 

Always maintain 3” clearance from combustible materials. 

 
4. 

Install Vent wall thimble per Vent manufacturer’s instructions. 

 
5.  Attach enough piping to penetrate and extend at least 6 inches 

beyond the exterior wall.  There should always be at least one foot of 
vertical rise for each foot of horizontal run (

see

 

Appendix A

).  At least 

3 feet of vertical rise are needed in all cases.  A longer vertical rise will 
favour a better exhaust. 

 
6. 

To reduce the risk of smoke spillage, never terminate with a horizontal 
run. If your system terminates with a horizontal run, add at least 3 feet 
of vertical rise (

see Appendix A

). 

 

7.  Attach cap and seal outside wall thimbles with non-hardening 

waterproof mastic. 

 
 
Termination should not be located so that hot exhaust gases can ignite 
trees, shrubs, or grasses or be a hazard to children. Exhaust gases can 
reach temperatures of 500ºF and cause serious burns if touched.

 

45 DEGREE ELBOW

FOLLOW CHIMNEY OR 
VENT MANUFACTURER'S 
INSTRUCTIONS

WALL

THIMBLE

TERMINATION 
COLLAR

CLEAN OUT
TEE

WALL
STRAP

90 DEGREE ELBOW

 

Figure 14 

Venting through wall 

 

1' HORIZONTAL RUN EVL = 1'

FOLLOW CHIMNEY OR 
VENT MANUFACTURER'S 
INSTRUCTIONS

VERTICAL LENGTH4' EVL = 4 X 0.5' = 2'

1' HORIZONTAL RUN EVL = 1'

90° ELBOW "T" LEE = 5'

CLEAN OUT
TEE

VERTICAL LENGTH 4' EVL = 4 X 0.5' = 2'

VERTICAL LENGTH 4' EVL = 4 X 0.5' = 2'

WALL
STRAP

VERTICAL ROOF VENT

WALL

THIMBLE

 

Figure 15 

Venting trough wall 

 

Locate terminations: a) not less than 3 feet above any forced air inlet 

located within 10 feet; b) not less than 4 feet below or horizontally from, 

or one foot above, any door, window or gravity air inlet into any building; 

c) not less than two feet from an adjacent building and not less than 7 feet 

above grade when located adjacent to a public walkway. Mobile home 

installations must use a spark arrester. Other restrictions may apply, such 

as the need to maintain a minimum distance to a gas meter. US and 

Canadian Standards may vary.  

Consult the vent manufacturer’s 

instructions

.

 

 
 
 

Содержание FP-35

Страница 1: ...damage bodily injury or even death Save these instructions Some surfaces become hot at higher feeding rates To prevent potential burns avoid contact with those areas This heating unit must serve as a...

Страница 2: ...only Do not burn coal of any type in this appliance It is designed for residential installation according to current national and local building codes as a freestanding or insert room heater It is al...

Страница 3: ...in summer time may cause the heat sensors on the stove to activate the blowers disconnect the stove when not used for extended periods Contact your local building officials to obtain a permit and info...

Страница 4: ...MASONRY FIREPLACE 12 INSTALLATION THROUGH SIDE OF MASONRY CHIMNEY 12 INSERT INSTALLATION 13 INSERT INTO EXISTING MASONRY FIREPLACE 13 CLEARANCES 14 OPERATION 15 PROPER FUEL 15 PRE START UP CHECK 15 B...

Страница 5: ...WARNING CODE I 27 STOVE STOPS FEEDING PELLETS AND SHOWS WARNING CODE O 27 STOVE STOPS FEEDING PELLETS AND SHOWS WARNING CODE H 28 STOVE STOPS FEEDING PELLETS AND SHOWS WARNING CODE d 28 SMOKE SMELL C...

Страница 6: ...6...

Страница 7: ...the pedestal kit or faceplate kit are supplied with the corresponding kit Normally your dealer will perform these functions CLEARANCES The FP 35 has been tested and listed for installation in regular...

Страница 8: ...e a listed pellet vent that meets the ULC S 609 M89 and ULC ORD C441 M90 Standards For the United States we recommend that you use a listed pellet vent that meets the UL 641 7 th edition Standard This...

Страница 9: ...sure that they are cleaned on a regular basis as per our recommended maintenance schedule This is particularly critical if you have animals in your house such as a dog or a cat Filters that are not c...

Страница 10: ...t least 3 feet of vertical rise are needed in all cases A longer vertical rise will favour a better exhaust 6 To reduce the risk of smoke spillage never terminate with a horizontal run If your system...

Страница 11: ...quare hole in roof always 3 larger all the way around pipe Install upper edge and sides of flashing under roofing materials nail to the roof along upper edge Do not nail lower edge Seal nail heads wit...

Страница 12: ...ter of the hole where the pipe is to pierce the masonry chimney 2 It will be necessary to cut out the masonry around the location of the pipe center mark Cut a 4 inch diameter hole for 3 inch pipe and...

Страница 13: ...the floor Option B through the back wall Option C through chimney top 5 Attach the DuraVent adapter a section of pipe and clean out tee making sure the clean out tee is centered in the chimney flue ar...

Страница 14: ...14 CLEARANCES COMBUSTIBLE SHELF FROM DOOR OPENING FLOOR PROTECTION 6 11 7 10 1 2 6 Figure 33 Clearances...

Страница 15: ...CK Remove burn pot making sure it is clean and none of the air holes are plugged Clean the firebox and then reinstall burn pot Clean door glass if necessary a dry cloth or paper towel is usually suffi...

Страница 16: ...y activating this function the stove will feed for 1 minute and the display will blink You can stop the distribution by touching the sign a second time or by starting the stove CAUTION THIS FUNCTION C...

Страница 17: ...rative panel for the insert This control is used to adjust the air intake manually depending on the type of installation and different brands of pellets used It allows you to improve the efficiency of...

Страница 18: ...OTE If an overheating situation occurs the high temperature switch called the L 250 manual reset will automatically shut down the auger motor fuel feed system and a warning code will appear b If the c...

Страница 19: ...onvection blowers will also slow down to low speed When the thermostat calls for heat again the stove will automatically switch back to the selected heat level N B If the room temperature remains stab...

Страница 20: ...your stove is not connected to a thermostat or a fresh air supply do not leave it at the maximum setting If the ambient air becomes to hot the stove may overheat and the thermal protection on the com...

Страница 21: ...problems e Sweep the ashes in the firebox into the ash drawer through the opening at the bottom of the firebox or vacuum to remove ashes WARNING Make sure ashes are cool to the touch before using a v...

Страница 22: ...that the open side of the baffle is located on the left c Chamber walls Periodically you must vacuum the ashes that may have accumulated on the main walls of the combustion chamber START BY REMOVING...

Страница 23: ...CONNECTOR Figure 48 Exhaust blower cleaning CHIMNEY CLEANING a Creosote Formation When wood is burned slowly it produces tar and other organic vapours which combine with expelled moisture to form creo...

Страница 24: ...st Blower Vacuum Pressure Switch Tap Brush Venting System Inspect Sweep Gaskets Inspect Hopper Empty Vacuum Gasket around door and door glass should be inspected and repaired or replaced when necessar...

Страница 25: ...xhaust pipe are blocked with ash or foreign material Follow all cleaning procedures in the maintenance section of the owner s manual 3 Vent pipe is incorrectly installed Check to make sure vent pipe i...

Страница 26: ...shaft from the auger housing Start by emptying the hopper Take off the rear panel of the stove s body Then remove the auger motor by removing the screws holding the motor to the auger shaft Once the m...

Страница 27: ...n occurs call your dealer or technician 5 The control board is not sending power to the igniter Check the voltage going to the igniter during ignition It should be a full current If the voltage is low...

Страница 28: ...nance procedures Press simultaneously for 2 seconds the reset and icons After 3 attempts reset is no longer possible Call SBI technical support STOVE STOPS FEEDING PELLETS AND SHOWS WARNING CODE d Pos...

Страница 29: ...een installed according to the instructions in the owner s manual 3 The air damper is too far closed for a higher setting Slide the air supply to a higher setting and try to burn the unit again 4 Burn...

Страница 30: ...nverted polarity in power outlet Will not keep the stove from operating Power outage Igniter fuse blew up SMOKE SMELL OR SOOT BUILD UP Because it is a wood burning device your BIO 35 may emit a faint...

Страница 31: ...ECTION BLOWER CONVECTION BLOWER POWER CORD Figure 47 Components rear HIGH TEMPERATURE SWITCH L 250 MANUAL RESET HIGH TEMPERATURE SWITCH F 160 HIGH TEMPERATURE SWITCH L 250 AUTOMATIC IGNITER AIR SUPPLY...

Страница 32: ...sket 2 requires 21045 Control Board Touch screen 44022 PC Board 44102 Combustion Exhaust Blower Assembly SE44101 Convection Blower 44100 Door Gasket AC06100 Door Glass SE49220 Hot Rod Igniter 44030 Th...

Страница 33: ...tal vent coming out at the back of the stove on a total distance of 4 feet followed by a Tee and a 6 foot vertical rise it would be acceptable The installation would end be within the allowable config...

Страница 34: ...uivalent vent lenght calculation table DRAW YOUR INSTALLATION 1 SQUARE 1 F00T PART DAILY 10 bags 25 bags E xchanger Baffle Left interior channel Hopper Evacuation blower Blower blades Pressure system...

Страница 35: ...e of the replacement part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or un...

Отзывы: