19
ENG
8.3 Error messages
Error
no.
Description
Remark
Reset Measure
1
Min. pressure alarm
limit
The programmed value F1 6 is reached or
exceeded.
B
Test compressor (fuse). Interpretation,
check parameter choice.
2
Max. pressure alarm
limit
The programmed value F1 7 is reached or
exceeded.
Check valve (fuse). Interpretation, check
parameter choice.
3
Min. level alarm limit
The programmed value F2 6 is reached or
exceeded. Equipment without fillcommand
or fillcommand with insufficient flow.
Adjust water, note error - No.5. Incorrect
interpretation or first filling. Check
expansion volume.
4
Max. level alarm limit
The programmed value F2 7 is reached or
exceeded (Pressure not maintained).
A
Drain water, note error - No.5. Incorrect
interpretation or first filling. Check
expansion volume.
5
Filling quantity
The programmed quantity per day is
reached (value F2 5). Too high fill command
B
Attention, leaking or failing installations
cause water damage and high costs.
Check equipment.
7
Operating time
compressor
The programmed value F1 12 is reached or
exceeded.
A
Test compressor, air filter.
Flamco Service.
8
Water supply
The programmed value F4 6 is reached or
exceeded.
A,C
Diaphragm pressure to low, check water
supply.
9
Valve 3 error
Valve 3 of the refill equipment is not closed.
Check valve 3. Clean or replace the
valve if neccessary.
10
Cycle time
The programmed value F4 3 is reached
or exceeded.
Check refill equipment. Check on
leakage.
11
Cycles
The programmed value F4 4 is reached
or exceeded.
Check refill equipment. Check on
leakage.
12
Quantity limit
The programmed value F4 1 is reached
or exceeded.
Check refill equipment. Check on
leakage.
13
Running time
The programmed value F4 2 is reached
or exceeded.
Check refill equipment. Check on
leakage.
14
Water purification
The programmed value F4 7 is reached
or exceeded.
Check refill equipment. Check on
leakage.
15
Min. pressure limiter
active
Pressure under set value of min.pressure
limiter
A
Check if min. pressure limiter option is
installed and functioning.
If no pressure limiter is needed,
de-activate in menu G 8.
16
Diaphragm rupture
Signal diaphragm rupture sensor is on
(Pressure not maintained).
A
Check the diaphragm on breaks.
(Continuing water leakage after opened
valve condensate outlet [36]).
Flamco service.
17
Perform maintenance The programmed value F6 10 is reached
or exceeded
Perform the sceduled maintenance
21
Min. voltage sensor
The minimal voltage for the sensor is not
reached
B
Signal current could be > 20 mA.
Restart controller.
22
Short-circuit pressure The input signal from the pressure sensor is
too high (> 20 mA). Excessive pressure to
the sensor, false installation, short circuit of
the inlet. (External influences).
B
Installation of the sensors, check
equipment.
23
Pressure, wire rupture The input signal from the pressure sensor
is (< 4 mA) or not available. Inlet sensor
interrupted, not installed (Sensor defect).
Installation of the sensors, check
equipment.
24
Short-circuit level
The input signal from the level sensor is
(< 20 mA) or not available. Inlet sensor
interrupted, not installed (Sensor defect).
Installation of the sensors, check
equipment.
25
Level, wire rupture
The input signal from the pressure sensor
is (< 4 mA) or not available. Inlet sensor
interrupted, not installed. (Sensor defect).
Installation of the sensors, check
equipment.
26
Voltage RTC
The support voltage for the timer, operating
hours is not reached.
A
Check time, date (input).
27
Flash memory error
Read error flash memory
B
Flamco Service.
28
Flash memory error
Write error flash memory
Flamco Service.
29
Flash memory error
Programming error flash memory.
Flamco Service.
A
Necessary, reset possible within normal use (control restarts after resetting).
B
No duty, automatic reset within normal use.
C
Refer to the refill equipment chapter.