Installation and maintenance

 

7

  

Fläkt Woods 

9325 GB 2016.09.16 

Specifications are subject to change without further notice

Frequency converter Fc102 (quick guide)

activating pid regulation

See sensor

See sensor

Setpoint

Adjust if

necessary

 

step 

description   tF 

  FF 

 1  

Press [Quick menus]

 2  

Press [Quick menus]

 3  

Select Q3-3 Closed Loop Settings

 4  

Select Q3-30 Single Zone Int.Setpoint

 5  

1-00 Confi  guration Mode  

 

[3] Closed Loop    

[3] Closed Loop

 6  

20-12 Reference/Feedback Unit  

[72] Pa    

 

[72] Pa

 7  

20-13 Minimum Reference/Feedb.  

0 Pa  

 

 

0 Pa

 8  

20-14 Maximum Reference/Feedb.  

______________Pa    

______________Pa

 9  

Press [

] once

10  

6-24 Terminal 54 Low Ref./Feedb.  

0 Pa  

 

 

0 Pa

11  

6-25 Terminal 54 High Ref./Feedb.  

______________Pa    

______________Pa

13  

6-26 Terminal 54 Filter Time Const  

1 s  

 

 

1 s

14  

Press [

] four times

15  

20-21 Setpoint 1   

 

 ______________Pa   

 ______________Pa

16  

20-81 PID Normal/Inverse Control  

[0] Normal  

 

[0] Normal

17  

Press [

] twice

18  

20-93 PID Start Speed  

 

2.0  

 

 

2.0

19  

20-94 PID Proportional Gain   

30.0s    

 

30.0s

20  

Press [Main Menu] twice

21  

Select 0–** Operation / Display

22  

Select 0–2* LCP Display

23  

0–20 Display Line 1.1 Small    

[1654] Feedback 1   

[1654] Feedback 1

Confi guration carried out by __________________________________________________ 

Date ________________________________

Содержание FC102

Страница 1: ...onnections 3 Control unit LCP 4 Manual operation 4 Reverse the direction of rotation 4 More information 4 Wiring diagram 5 Basic configuration 6 PID regulation 7 AIRTREATMENT 9325GB2016 09 16 AIRCOMFO...

Страница 2: ...mains voltage disconnecting permanent magnet motors and DC bus supplies including battery backup UPS and DC bus connections for other frequency converters Wait until the capacitors have fully dischar...

Страница 3: ...alogue I O 4 LCP contact 5 Analogue switches 6 Cable support PE earth 7 Earthing plate 8 Earth clamp 9 Shielded cable earth clamp and cable support 10 Motor connection 11 Relay 1 12 Relay 2 13 Brake a...

Страница 4: ...ion or access a parameter group Green indication power on Yellow indication warning Red indication alarm D Driftsl gesknappar och terst llning Hand on Starting the motor for local control Off Stopping...

Страница 5: ...5 40 0 Relay output 1 Run Indicator NO NC Param 5 40 1 Start Reference 0 10VDC FW standard Actual value PID regulation Start Danfoss FC102 24V 12 24V 13 DIG IN 18 DIG IN 19 COM 20 DIG IN 27 DIG IN 29...

Страница 6: ...z 12 Apply on terminal block 53 Yes Yes 13 Application Fan Fan 14 Autom Energy Optimisation Yes 2 4 pon Yes 2 4 pin No other No other 15 AMA Yes Yes 16 Con rm AMA OK OK 17 Press Main Menu twice 18 Sel...

Страница 7: ...20 14 Maximum Reference Feedb ______________Pa ______________Pa 9 Press once 10 6 24 Terminal 54 Low Ref Feedb 0 Pa 0 Pa 11 6 25 Terminal 54 High Ref Feedb ______________Pa ______________Pa 13 6 26 Te...

Страница 8: ...p bits 2 No parity 1 Stop bit Parameter Description TF FF 6 50 Function terminal block 42 4 20mA 4 20mA Parameter Description TF FF 6 14 Output frequency equivalent to 4mA 0 Hz 0 Hz 6 15 Output freque...

Отзывы: