Installation and maintenance
7
Fläkt Woods
9325 GB 2016.09.16
Specifications are subject to change without further notice
Frequency converter Fc102 (quick guide)
activating pid regulation
See sensor
See sensor
Setpoint
Adjust if
necessary
step
description tF
FF
1
Press [Quick menus]
2
Press [Quick menus]
3
Select Q3-3 Closed Loop Settings
4
Select Q3-30 Single Zone Int.Setpoint
5
1-00 Confi guration Mode
[3] Closed Loop
[3] Closed Loop
6
20-12 Reference/Feedback Unit
[72] Pa
[72] Pa
7
20-13 Minimum Reference/Feedb.
0 Pa
0 Pa
8
20-14 Maximum Reference/Feedb.
______________Pa
______________Pa
9
Press [
▼
] once
10
6-24 Terminal 54 Low Ref./Feedb.
0 Pa
0 Pa
11
6-25 Terminal 54 High Ref./Feedb.
______________Pa
______________Pa
13
6-26 Terminal 54 Filter Time Const
≥
1 s
≥
1 s
14
Press [
▼
] four times
15
20-21 Setpoint 1
______________Pa
______________Pa
16
20-81 PID Normal/Inverse Control
[0] Normal
[0] Normal
17
Press [
▼
] twice
18
20-93 PID Start Speed
2.0
2.0
19
20-94 PID Proportional Gain
30.0s
30.0s
20
Press [Main Menu] twice
21
Select 0–** Operation / Display
22
Select 0–2* LCP Display
23
0–20 Display Line 1.1 Small
[1654] Feedback 1
[1654] Feedback 1
Confi guration carried out by __________________________________________________
Date ________________________________