Supply air unit VEKC - Integrated Control Equipment Curo
25
FläktGroup DC_9965GB_20190124_R3
Specifications are subject to alteration without notice
7. PARAMETER LIST
Incorrect parameter settings may cause malfunction and freezing damage in hot water coil.
Therefore all settings has to be made by persons with necessary knowledge.
1)
R/W = Read and write value, R = Read only value
Parameter
Type of value
1)
Range
Unit
Default value
Comments
Supply air
R
–40-100
° C
–
Outdoor air
R
–40-100
° C
–
Extract air
R
–40-100
° C
–
Freeze protection
R
–40-100
° C
–
For unit with Hot Water Coil
Set point
R/W
15-35
° C
19
Summer / Winter mode
R
Summer / Winter
–
–
Output signal, Post Heater
R
0-100
%
–
Output signal, Pre Heater
R
0-100
%
–
Not for VEKA
Output signal, Heat Recovery
R
0-100
%
–
Not for VEKA
Output signal, Cooling
R
0-100
%
–
Control mode/Calculated Set point
R
15-35
° C
–
TEMPERATURE STATUS
Parameter
Type of value
1)
Range
Unit
Default value
Comments
Supply Fan, speed
R
0 or 15-100
%
–
Exhaust Fan, speed
R
0 or 15-100
%
–
FAN STATUS
Parameter
Type of value
1)
Range
Unit
Default value
Comments
CO
2
value
R
0-2000
ppm
–
Not for VEKA
AIR QUALITY
Parameter
Type of value
1)
Range
Unit
Default value
Comments
Software version, Control panel
R
–
–
–
Bootloader version, Control panel
R
–
–
–
Software version, Control board
R
–
–
–
Bootloader version, Control board
R
–
–
–
Unit type
R
–
–
VEKA
IP Octet 1
R
0-255
–
–
Actual IP–address, accessory
IP Octet 2
R
0-255
–
–
IP Octet 3
R
0-255
–
–
IP Octet 4
R
0-255
–
–
SYSTEM OVERWIEV
Parameter
Type of value
1)
Range
Unit
Default value Comments
Schedules
R
–
–
–
Active schedules, read onl
y
SCHEDULES