GLEC-6 - Installation and maintenance
16
FläktGroup
DC-10087-GB 2018-01-03_R0
Specifications are subject to alteration without notice
The airflow sensor is used for measuring the airflow of the fan.
The method is based on pressure differential. The pressure is
measured at the specific point in the inlet cone and the reference
pressure is measured upstream of the inlet cone. The air flow
sensor is factory mounted in the inlet cone.
10 AIR FLOW MEASUREMENT
(OPTIONAL)
11 CODE KEY
Kitchen exhaust fan
GLEC-a-bbb-c-ddd-0
Type (a)
6 = High temperature
Size (bbb)
031, 040, 050
Motor (c)
1 = 1-phase motor (sizes 031 and 040)
3 = 3-phase motor (size 050)
Motor power (ddd)
055 = 0.55 kW (GLEC-6-031)
080 = 0.75 kW (GLEC-6-040)
220 = 2.20 kW (GLEC-6-050)
Version (e)
0
q
v
=
A
D
p
m
k
The air flow is calculated from the equation:
q
v
= air flow (m
3
/s)
k = k-factor (see name plate of each fan)
D
p
m
= differential pressure reading (Pa)