background image

OPERATING INSTRUCTIONS MANUAL

FLE-150RC

575V

INDUSTRIAL / COMMERCIAL ELECTRIC HEATER

(OPERATOR MUST RETAIN FOR FUTURE REFERENCE)

Suitable for indoor  installation only / Unvented / Unattended Type

26 Benfield Drive, St.Catharines, Ontario Canada L2S 3V5  

(P) 905-685-4243 - (F) 905-685-0113

Содержание FLE-150RC

Страница 1: ...0RC 575V INDUSTRIAL COMMERCIAL ELECTRIC HEATER OPERATOR MUST RETAIN FOR FUTURE REFERENCE Suitable for indoor installation only Unvented Unattended Type 26 Benfield Drive St Catharines Ontario Canada L...

Страница 2: ...USE OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTIONS MANUAL LABEL ETC CONTACT THE MANUFACTURER WARNING FIRE BURN INHALATION AND EXPLOSION HAZARD KEEP SOLID C...

Страница 3: ...stat option available Inlet Duct Adapter The FLE 150RC includes a permanant inlet duct adapter Safety Always verify that you have proper voltage supply 575V It is important to check the wiring connect...

Страница 4: ...embly and ensure the motor and blade are operating properly 4 Compressed air may be used to keep components free of dust and dirt build up Pre Start Checklist 1 Heater must be level and lockable wheel...

Страница 5: ...ower supply 5 Pull Master button to the out position 6 Determine Manual or Remote Thermostat if remote set desired temperature 7 Turn Blower on off switch to the ON position The blower will start and...

Страница 6: ...0 7300 120F 83 DB 90 kW 307 000 6700 88F 81 DB 60kW 205 000 5400 56F 76 DB FAN ONLY 7900 N A 85 DB SHUTDOWN 1 Move all heat control setting to the OFF position 2 Leave Fan in the ON position for 3 5 m...

Страница 7: ...RISE above ambient 60KW 56 F 90KW 88 F 150 KW 120 F AMP DRAW MOTOR 5 AMPS 60KW 54 AMPS 90KW 81 AMPS 150KW 136 AMPS DB noise level FAN ONLY 85 60KW 76 90KW 81 150KW 83 INLET SIZE no ducting 20 Dia OUTL...

Страница 8: ...E 150RC 90 KW 50 Hz 4650 CFM FLE 150RC 150 KW 55 Hz 5300 CFM FLE 150RC FAN ONLY 60 Hz 7900 CFM THE VFD HAS BEEN PASSWORD PROTECTED WITH THE PREPROGAMMED SETTINGS THESE SETTINGS ARE THE MINIMUM AIR FLO...

Страница 9: ...CE OF WARNING OR FAULT MESSAGES THAT MAY APPEAR ON THE SCREEN OF THE VFD IF ANY OF THE MESSAGE DO APPEAR PLEASE REVIEW THE VFD MANUAL OR CONTACT FLAGRO INDUSTRIES TO HELP CORRECT THE ISSUE TO REVIEW F...

Страница 10: ...VARIABLE FREQUENCY DRIVE STATUS WARNING MESSAGES...

Страница 11: ......

Страница 12: ...VARIABLE FREQUENCY DRIVE FAULT MESSAGES...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...UT POWER ON TRANSFORMER SHOULD BE 120 VOLTS IF NO POWER TURN POWER OFF AND CHECK FU1 5A FUSE IF GOOD CHECK FB4 5 A FUSES FOR CONTINUITY IF TRANSFORMER HAS PROPER OUTPUT POWER CHECK VFD SCREEN FOR COMM...

Страница 17: ...O DETERMINE IF FAULTY SHUT POWER OFF BYPASS SWITCH THEN TURN POWER ON FOR TEST INSPECT INTAKE AIR FILTER S CLEAN IF REQUIRED UNIT PROVES AIR BLOWER RUNS BUT HEAT WILL NOT ENGAGE CHECK OHMS RESISTANCE...

Страница 18: ...TACT BLOCK BEHIND HEATER SWITCH RED WIRE PERFORM OHM RESISTANCE TEST BYPASS HIGH LIMIT OR AIR PRESSURE SWITCH IF ELEMENT STILL DOES NOT ENGAGE RUN JUMPER WIRE FROM TB3 TO TB10 IF ELEMENT WORKS PROBLEM...

Страница 19: ...CK FUSES TO THE CONTACTOR THAT IS NOT WORKING PROPERLY DO OHM TEST OF ELEMENT EACH SIDE TEST SEPARATE FLE 60 20KW 40KW FLE 150RC 60KW 90KW PLEASE SEE CHART BELOW FOR READINGS TEST OHM READING FLE 150R...

Страница 20: ...PEED DRIVE 7 5 HP MOTOR FLE 1503A 575VOLT FLE 1504A 575 VOLT FUSES FLE 1509 125 Amp Class T FLE 1510A 80 Amp Class T FLE 1511B 12 Amp Class CC FLE 631 Amp Class CC FLE 1515 2 Amp AGC Glass TRANSFORMER...

Страница 21: ...POSITION SWITCH FLE 633 60KW 90KW THERMOSTAT MANUAL BLOWER ON OFF EMERGENCY STOP BUTTON FLE 634 GREEN AIR PROVEN LIGHT FLE 636 FLE 635 HIGH LIMIT AIR PROVEN LIGHT THERMOSTAT FV 414B N C CONTACT BLOCK...

Страница 22: ...OCKABLE FLE 610 6 RIGID FLE 611 BLUE FLE 612 BLACK FLE 613 GREEN FLE 614 RED CAM LOCK PANEL CAM LOCK DETACHABLE FLE 615 BLUE FLE 616 BLACK FLE 617 GREEN FLE 618 RED SNAP COVERS PANEL FLE 611A BLUE FLE...

Страница 23: ...12 AMP CLASS CC TIME DELAY FUSE THREE PER HEATER FLE 1512 AIR PROVING SWITCH COMPLETE FLE 1513 OUTLET HIGH LIMIT 250F FLE 1514 INLET GUARD PRIOR TO 2018 FLE 1515 2 AMP FUSE FLE 609 6 LOCKABLE SWIVEL...

Страница 24: ...ODULE ONLY FLE 635B RED HIGH LIMIT NON PROVEN AIR LIGHT LED COMPLETE FLE 636 GREEN AIR PROVEN LIGHT LENS ONLY FLE 636A GREEN AIR PROVEN LIGHT LED MODULE ONLY FLE 636B GREEN AIR PROVEN LIGHT LED COMPLE...

Страница 25: ...W BC L2 L3 3L1 BK 14 AWG 12 TEW BC 3L2 3L3 FB3 12 A FB4 0 5A U1 V1 W1 PE 7 5 HP FLA 7 A 3 M T1 T2 T3 PE GB Ground Bar PE 2A FU1 TB 2 GB Ground Bar L1 BK 2 AWG 16 T90 THHN 1R1 BK 6 AWG 45 SEW 2 2L1 BK...