background image

 
MAINTENANCE: 
 

1.  

Every construction heater should be inspected before each use, and at least 
annually by a qualified service person. 

 
2.  

The hose assembly shall be visually inspected prior to each use of the heater. If 
it is evident there is excessive abrasion or wear, or the hose is cut, it must be 
replaced prior to the heater being put into operation. The replacement hose 
assembly shall be that specified by the manufacturer. 

 
3.  

The appliance must be kept clear and free from combustible materials, gasoline 
and other flammable vapors and liquids. 

 
4.  

The flow of combustion and ventilation air must not be obstructed. Be sure to 
check the fan assembly and ensure that the motor and blade are operating 
properly. 

 
5.  

Compressed air should be used to keep components free of dust and dirt build 
up. Note: Do not use the compressed air inside any piping or regulator 
components. 

Содержание F-1000T

Страница 1: ...ture reference For F 1000T DUAL FUEL CONSTRUCTION HEATER CERTIFIED FOR USE IN CANADA AND U S A As per Standard ANSI Z83 7 2000 CSA 2 14 2000 Gas Fired Construction Heaters Unvented Unattended Type FLAGRO INDUSTRIES LIMITED ST CATHARNIES ONTARIO CANADA ...

Страница 2: ...OSION HAZARD KEEP SOLID COMBUSTIBLES SUCH AS BUILDING MATERIALS PAPER OR CARDBOARD A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES OR PRODUCTS SUCH AS GASOLINE SOLVENTS PAINT THINNER DUST PARTICLES OR UNKNOWN CHEMICALS WARNING NOT FOR HOME OR RECREATIONAL VEHICLE USE WARNING INTENDED US...

Страница 3: ... YOU HAVE QUESTIONS ABOUT APPLICATIONS Other standards govern the use of fuel gases and heat producing products in specific applications Your local authority can advise you about these SPECIFICATIONS Model Number F 1000T Input 1 000 000 btuh Fuel Natural Gas or Propane Inlet Pressure Natural Gas 7 0 W C Propane 11 W C Ignition Direct Spark Ignition Thermostat Control Air Circulation 7000 cfm Fuel ...

Страница 4: ... vapor withdrawal only 1 All cylinder connections must be made using a wrench to tighten the POL fitting 2 Be sure that the cylinder valve is in the closed position when connection or disconnecting the cylinder 3 A soap and water solution must be applied to all connections in order to leak check the system The gas must be turned off at the propane supply cylinder s when the heater is not in use Wh...

Страница 5: ...d depending on the fuel being used A fuel selector valve is located on the manifold of the heater Ensure that this valve is in the proper position depending on the fuel being used DO NOT operate the heater with the valve in the incorrect position HOSES All hoses used to connect this heater of fuel supply must be Type 1 approved propane natural gas hose assemblies ELECTRICAL WARNING Electrical Grou...

Страница 6: ...t into operation The replacement hose assembly shall be that specified by the manufacturer 3 The appliance must be kept clear and free from combustible materials gasoline and other flammable vapors and liquids 4 The flow of combustion and ventilation air must not be obstructed Be sure to check the fan assembly and ensure that the motor and blade are operating properly 5 Compressed air should be us...

Страница 7: ...y 4 Open all gas supply valves 5 Depress the main switch to the START position The fan will start and the burner should ignite 6 Set the Thermostat to the desired temperature 7 If heater fails to ignite after 3 attempts call your supplier for service TO SHUT DOWN 1 Close the main gas supply valve while the heater is operating 2 Move the main switch to the OFF position 3 Disconnect the heater from ...

Страница 8: ... turn counter clockwise to decrease sensitivity POSSIBLE CAUSE Blockage in copper inlet tubes REMEDY Disconnect tubes from air switch Use high pressure air to clean any debris that my block the airflow POSSIBLE CAUSE Faulty Switch REMEDY Replace Switch POSSIBLE CAUSE Rear of heater blocked REMEDY Ensure rear of heater is unobstructed and proper rear clearances are maintained see approval label ...

Страница 9: ...ssures are supplied to the heater see approval label POSSIBLE CAUSE Spark Plug REMEDY Ensure gap in spark plug is approx 3 16 Check spark plug wire connections Ensure spark plug has good spark Replace spark plug if necessary POSSIBLE CAUSE Ignition Board REMEDY Ensure electrical signals for both spark plug and solenoid are present use volt meter Ensure ignition board is properly grounded POSSIBLE ...

Страница 10: ...PROBLEM HEATER WILL NOT REMAIN LIT AFTER START UP POSSIBLE CAUSE Faulty flamerod wire REMEDY Check flamerod wire for any damage Ensure connections are secure Replace flamerod if necessary ...

Страница 11: ...CTOR VALVE S 1003 FUEL SHUT OFF VALVE S 1003A IGNITOR S 408A FAN BLADE S 1001 PRESSURE ADJUSTMENT CAP FOR S 1002 REG S 1002C REGULATOR 1 2 PSI S 1002 S S FILTER SCREEN S 1002FS FLAME ROD S 406A FLAME ROD WIRE S 407A IGNITOR WIRE S 1009A OFF RUN START SWITCH S 411 BURNER S 1005 MAIN RELAY S 412 ...

Страница 12: ...OARD S 415P AIR PROVEN SWITCH S 414 THERMOSTAT S 416 REAR SCREEN S 1019 8 RUBBER WHEELS S 1022 AIR SENSING TUBES S 1027 POWER CORD S 1021 CLEAR INDICATOR LIGHT S 1020A RED INDICATOR LIGHT S 1020B GREEN INDICATOR LIGHT S 1020C MOTOR MOUNT BRACKET S 1033 ...

Страница 13: ...A IGNITION WIRE S 410 HIGH TEMPERATURE LIMIT S 411 OFF RUN START SWITCH S 412 MAIN RELAY S 414 AIR PROVING SWITCH S 415P POTTED IGNITION CONTROL 120V S 415W WIRING HARNESS S 416 THERMOSTAT S 1019 SCREEN ASSEMBLY S 1020A CLEAR INDICATOR LIGHT S 1020B RED INDICATOR LIGHT S 1020C GREEN INDICATOR LIGHT S 1021 POWER CORD INCLUDING PLUG S 1022 RUBBER WHEEL 8 ACCESSORIES B42R1 25 SECOND STAGE REGULATOR 1...

Страница 14: ...000T WIRING DIAGRAM 2010 Note If any of the origional wire as supplied with the appliance must be replaced it must be replaced with type 14g TEW wire or its equivalent FLAGRO INDUSTRIES LIMITED V1 L1 V2 L2 S1 GND IGN FLAME ROD SPARK PLUG FENWAL IGNITION BOARD GROUND POTTED CONTROL BROWN BLACK YELLOW WHITE WHITE BLACK STRIPE PURPLE RED GREEN LIGHT SOLENOID VALVE SOLENOID VALVE ...

Отзывы: