background image

 
 
 
 
 
LOCATION 

The HEPA Air Cleaner should be located as close to the 
return air duct as possible. This allows for shorter lengths 
of  ducting  which  helps  keep  the  static  pressure  lower. 
The  unit  can  be  adapted  to  mount  on  a  wall  or  be 
suspended  from  the  ceiling.  Care  should  be  taken  to 
keep  the  unit  away  from  an  area  where  there  is  a 
possibility of moisture leaking on to it. Ensure there is 24-
36  inches  (61  -  91.4  cm)  above  the  unit  to  remove  the 
filters for cleaning or replacing. 
It  is  important  to  maintain  some  distance  between  the 
intake  and  the  exhaust  openings  in  the  return  air  duct. 
Failure to do this may result in short cycling between the 
intake  and  the  clean  air  discharge.  It  is  recommended 
you  leave  10  feet  (3  m)  between  the  intake  and  the 
exhaust;  however,  as  little  as  6  feet  (1.8  m)  will  work 
effectively.  If  the  distance  is  smaller  than  6  feet,  it  is 
important that an air deflector is installed in the duct.

 

If outside air is introduced into the return air duct, either 
direct  or  through  a  HRV  (Heat  Recovery  Ventilator),  it 
should be added to the system before the intake inlet to 
the Air Cleaner.  

GENERAL INSTALLATION STEPS 

1.  Remove any  packaging or plastic from filters before 

installing.  See  Maintenance  for  instructions  to 
remove the filters. 

2.  When  the  unit  is  shipped,  the  8  inch  intake  and 

exhaust  collars  are  not  installed  on  the  unit.  The 
collars  must  be  attached  with  the  collar  ring  facing 
out.  Remove  the  8  inch  collars  from  the  unit  by 
cutting  the  ties  which  hold  them  to  the  enclosure. 

Remove  the  collars  from  the  enclosure  by 
compressing  the  ring  and  pulling  out  of  the 
enclosure.  To  install  the  collars,  invert  the  collar  so 
the large ring is to  the outside. Compress the collar  
ring  until  you  can  insert  the  smaller  flange  into  the 
opening  in  the  enclosure.  Enlarge  the  ring  to  its 
maximum  and  turn  the  collar  in  the  hole  until  the 
holes in the enclosure line up  with the slotted holes 
in  the  smaller  collar  flange.  Secure  the  collar  to  the 
enclosure with one screw. Install two screws into the 
ring  to  hold  it  to  the  proper  diameter.  Secure  both 
collars to the enclosure with the screws provided. 

3.  A duct take-off adapter and a 10 foot length of 8 inch 

flex  duct  is  required  to  attach  between  the  8  inch 
intake  collar  on  the  unit  and  the  existing  cold  air 
return duct. 

Pick  the  place  on  the  return  duct  or  trunk  where 
you wish to install the duct take-off adaptor for the 
intake.  The  place  should  be  somewhere  on  the 
duct  after  the  last  branch  coming  back  to  the 
furnace, where all of the return air will pass. 
Hold the duct take-off on the return duct and mark 
the duct on the inside of the ring. 
Cut a hole in the duct just outside of the mark you 
made  on  the  duct.  Remove  the  backing  from  the 
adhesive  and  place  the  take-off  adaptor  over  the 
hole  you  cut.  Secure  the  take-off  to  the  duct  with 
four #8 x 1/2” sheet metal screws.  
Extend the flex duct to the length you require. Fold 
any  loose  edges  of  the  flex  duct  to  the  outside  of 
the  duct  or  use  a  crimping  tool  to  slightly  expand 
the duct. Place the flex duct over the take-off ring 
on the duct and secure the flex duct to the take-off 
ring  with  four  screws.  Run  the  flex  duct  to  the 
intake  collar  (top  collar)  on  the  back  of  the  unit. 
When  running  the  duct,  make  sure  that  there  are 
no  kinks  or  sharp  bends  that  will  impede  the  air 
flow to the unit. Secure the flex duct to the  intake 
collar  with  four  screws.  Seal  the  flex  duct  to  both 
rings with aluminum tape. 

4.  A duct take-off adaptor and a 10 foot length of 8 inch 

flex  duct  duct  is  required  to  attach  between  the 
exhaust  collar  on  the  unit  and  the  existing  cold  air 
return.  The  exhaust  flex  duct  should  be  attached  to 
the  return  air  duct,  close  to  the  furnace.  The  ideal 
location  is  low  on  the  return  air  boot  near  the 
furnace.  

Pick the spot on the return air boot where you wish 
to install the take-off ring for the exhaust.  
Hold  the  duct  take-off  adaptor  on  the  return  duct 
and mark the duct on the inside of the ring. 
Cut a hole in the duct just outside of the mark you 
made  on  the  duct.  Remove  the  backing  from  the 
adhesive and place the take-off ring over the hole 

with one of the mounting holes centered above 
the  hole  in  the  duct. 

Secure  the  take-off  to  the 

duct with the screws provided.  
To  prevent  air  shear  inside  the  duct,  you  must 
install the deflector  inside the boot or duct, so the 

WARNING  

This  unit  must  be  installed  on  the  return  air  side  of 
the system only. Do not connect to supply side. 
Do not install in a cooking area or connect directly to 
any appliance.  

Flange 

Collar 
Installed 

Ring 

Содержание FSHEPA375

Страница 1: ...ted Carbon Prefilter removes lint and unpleasant odours to extend life of HEPA Filter Carbon VOC After Filter removes additional unpleasant odours and gases Easy to change filters Heavy gauge steel cabinet and powder coat paint finish provide rigid installation and durability Powerful motor delivers 305 CFM of filtered air Small footprint for easier more convenient installation Versatile installat...

Страница 2: ...that may apply Follow all safety codes Wear safety glasses and work gloves WHAT THE HEPA AIR CLEANER DOES The Whole House True HEPA Air Cleaner has been designed to remove particulate such as atmospheric and household dust coal dust insecticide dust mites pollen mold spores fungi bacteria viruses pet dander cooking smoke and grease tobacco smoke and more It also removes odours with the Carbon Pref...

Страница 3: ... of 8 inch flex duct is required to attach between the 8 inch intake collar on the unit and the existing cold air return duct Pick the place on the return duct or trunk where you wish to install the duct take off adaptor for the intake The place should be somewhere on the duct after the last branch coming back to the furnace where all of the return air will pass Hold the duct take off on the retur...

Страница 4: ... For efficient operation the filters must be changed on a regular basis If you notice a reduction in air flow from the system check the filters 1 To access the filters turn the Air Cleaner OFF at the switch and remove the top cover 2 Carefully remove the filters to avoid spilling of collected contaminants Dispose of filters in a plastic bag and discard with regular household trash 3 Remove plastic...

Страница 5: ... Flow 305 CFM 518 5 m hr Power Cord 10 0 ft 3 05 m Filter Dimensions Carbon Prefilter HEPA Filter Carbon VOC After Filter 47 x 11 5 x 0 25 in 12 H x 14 25 Dia x 2 375 in 26 63 x 11 5 x 5 in 119 4 x 29 2 x 0 63 cm 30 5 H x 36 2 Dia x 6 cm 67 6 x 29 2 x 1 3 cm Carbon Prefilter Collecting Surface Area 3 75 ft 0 35 m HEPA Collecting Surface Area 100 ft 9 29 m Carbon VOC After Filter optional Surface A...

Страница 6: ...The expressed warranties made in this warranty are exclusive and may not be altered enlarged or changed by any distributor dealer or other person whatsoever FIVE SEASONS COMFORT LIMITED WILL NOT BE RESPONSIBLE FOR 1 Normal maintenance as outlined in the Owner s Manual including cleaning and or replacement of filters 2 Damage or repairs needed as a consequence of any misapplication negligent handli...

Отзывы: