Fisher R130/21 Скачать руководство пользователя страница 2

Types 749B and R130

2

Specifications

The Specifications table lists the specifications for the regulators.  Contact the factory if the regulators are to be used on 

any sevice other than LP-Gas, natural gas, or air.

Introduction

Scope of the Manual

The Instruction Manual covers installation and 

maintenance for the Types 749B, R130 changeover 

manifolds and the Types 64SR/122 and HSRL-749B 

commercial automatic changeover regulators. 

Description

Changeover Manifold Assemblies

Type R130/21

—Composed of two Type 67C 

regulators and a special 0 to 60 psig / 0 to 4.1 bar 

pressure gauge, the Type R130/21 delivers a 45 psig / 

3.1 bar outlet pressure on supply and 30 psig /  

2.1 bar on reserve.  The gauge, which serves as the 

changeover indicator, is painted red from 0 to 35 psig / 

0 to 2.4 bar.  When the dial reads in the 0 to 35 psig / 

0 to 2.4 bar range, it indicates that the manifold has 

switched from the supply to the reserve cylinder. 

Type 749B/21

—Large capacity changeover manifold 

for commercial and industrial applications.  It consists of 

two Type 64 regulators and a Type 803 direct indicator. 
The assembly is used primarily in conjunction with 

either a Type HSRL or 64SR regulator.  The standard 

outlet setting is 15 psig / 1.0 bar (supply) and 5 psig / 

0.34 bar (reserve).  

 

CAPACITY BTU/HR. 

PROPANE

TYPE

INLET 

CONNECTIONS

OUTLET 

CONNCETIONS

OUTLET PRESSURE SETTING

Supply Setting

Reserve Setting

1,475,000

(1)

R130/21

1/4-inch FNPT

1/4-inch FNPT

45 psig

3.1 bar

30 psig

2.1 bar

1,500,000

(1)

749B/21

1/2-inch FNPT

1/2-inch FNPT

15 psig

1.0 bar

5 psig 

0.35 bar

1.   Based on 100 psig / 6.9 bar inlet, reserve setting.

Changeover Manifold Assemblies

Commercial Automatic Changeover Regulators

CAPACITY  

BTU/HR. 

PROPANE

TYPE

INLET 

CONNECTION

OUTLET 

CONNCETION

OUTLET 

PRESSURE SETTING

OUTLET

ADJUSTMENT RANGE

MOUNTING

BRACKET

1,575,000

HSRL-749B

1/2-inch FNPT

3/4-inch FNPT

11-inches w.c.

27 mbar

9 to 13-inches w.c. 22 to 32 mbar

P100A

1,210,000

64SR/122

1/2-inch FNPT

1/2-inch FNPT

10 psig 

0.69 bar

5 to 20 psig

0.35 to 1.4 bar

- - - 

Maximum Inlet Pressure

250 psig / 17.2 bar

Temperature Range

-20 to 160°F / -29 to 71°C

CAUTION

Capacity of all these changeover 

manifolds is dependent on the size of 

the second stage regulator with which 

they are used.  

!

WARNING

If the manifolds are used on final-stage   

(pounds-to-pounds), a relief valve is 

required in the downstream system.  

 

Commercial Automatic Changeover Regulators 

Designed for large capacity multi-cylinder or tank 

installations, these regulators are used on such 

applications as bakeries, motels, restaurants, and 

grain dryers.  The manifold portion of the assembly 

(Type 749B/21) consists of two Type 64 regulators and 

a direct mounted Type 803 indicator.  

 

Type HSRL-749B

—For low-pressure service.  The 

Type HSRL second-stage portion has the “drip lip” 

vent feature and built-in travel stop to open the internal 

relief valve.  

 

Type 64SR/122

—For high-pressure (pounds to 

pounds) service with the second-stage composed of 

Type 64SR that has internal relief.  

Содержание R130/21

Страница 1: ...l and service this equipment Things to tell the Gas Customer 1 Point out the regulator s vent to the customer or vent assembly or vent tube and stress that this opening must remain unobstructed at all...

Страница 2: ...g 1 475 000 1 R130 21 1 4 inch FNPT 1 4 inch FNPT 45 psig 3 1 bar 30 psig 2 1 bar 1 500 000 1 749B 21 1 2 inch FNPT 1 2 inch FNPT 15 psig 1 0 bar 5 psig 0 35 bar 1 Based on 100 psig 6 9 bar inlet rese...

Страница 3: ...or manifold will open and maintain the reserve setting to the second stage regulator which continues to regulate the pressure to the appliance At the time the pressure in the Supply container drops to...

Страница 4: ...inspected for any damage that may have occurred Large volumes of gas may discharge through the regulator vent during internal relief valve operation which can result in fire or explosion from accumula...

Страница 5: ...ulator assembly is supplying the correct pressure to the appliance Failure to provide the correct pressure to the appliance can result in personal injury from fire and or explosion or damage downstrea...

Страница 6: ...To adjust the indicator remove the screw key 6 and the lens key 3 Using a small slotted screw driver turn the adjusting screw clockwise to increase the pressure or Figure 4 Indicator Assembly Drawing...

Страница 7: ...ulator each time a gas delivery is made for 1 Improper installation 2 Plugged or frozen vent 3 Wrong regulator or no regulator in the system 4 Internal or external corrosion 5 Age of the regulator 6 A...

Страница 8: ...as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability We reserve the right to modify or improve the designs or specification...

Отзывы: