DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual
30
6.5 DRY mode operation procedure
①
If room Temp. is more than 2°C below Set TEMP. , compressor and outdoor unit fan motor stop, indoor
unit fan motor runs at low speed.
②
If room Temp. is between 2°C of Set TEMP. , the compressor and outdoor unit fan motor will run for 6
minutes and stop for 4 minutes, and always in such a cycle, the indoor unit fan motor will run at low speed.
③
If room Temp. is more than 2°C above Set TEMP. , compressor and outdoor unit fan motor run as COOL
mode , the indoor unit fan motor runs at low speed.
Fig. 24