44
8.4.13 Point check function
Press the “LED DISPLAY” button of remote controller three times(“Swing button” for some remote
controllers) and then press “AIR DIRECTION” button three times, the air conditioner will enter the
“information enquiry” status. After that, press the “LED DISPLAY” button to enquiry the next one
information and press the “AIR DIRECTION” button to enquiry the last one information.
Table:
Enquiry
information
Displaying
code
Display value
Meaning
Remark
T1
T2
T3
T4
T2B
TP
TH
Targeted
Frequency
Actual
Frequency
T1
T2
T3
T4
Tb
TP
TH
FT
Fr
-1F,-1E,-1d,-1c,-
1b,-1A
-25,-24,-23,-22,-21,-2
0
1. All the displaying temperature is
actual value.
2. All the temperature is °C no
matter what kind of remote
controller is used.
3. T1,T2,T3,T4,T2B display
range:-25~70,
TP display range:-20~130.
4. Frequency display range:
0~159HZ.
5. If the actual value exceeds the
range, it will display the maximum
value or minimum value.
-19—99
-19—99
A0,A1,…A9
100,101,…109
b0,b1,…b9
110,111,…119
c0,c1,…c9
120,121,…129
d0,d1,…d9
130,131,…139
E0,E1,…E9
140,141,…149
F0,F1,…F9
150,151,…159
Indoor fan
speed
/Outdoor fan
speed
IF
OF
0
OFF
1,2,3,4
Low speed, Medium
speed, High speed,
Turbo
For some big capacity motors.
14-FF
Actual fan
speed=Display value
turns to decimal
value and then
multiply 10. The unit
is RPM.
For some small capacity motors,
display value is from
14-FF(hexadecimal), the
corresponding fan speed range is
from 200-2550RPM.
EXV opening
angle
LA
0-FF
Actual EXV opening
value=Display value
turns to decimal
value and then
multiply 2.
Compressor
continuous
running time
CT
0-FF
0-255 minutes
If the actual value exceeds the
range, it will display the maximum
value or minimum value.
Causes of
compressor
stop.
ST
0-99
For the detailed
meaning, please
consult with engineer
Decimal display
Indoor unit
status 0
A0
0-FF
For the detailed
meaning, please
consult with engineer
Содержание FSAI-Pro-122AE2
Страница 11: ...11 5 Wiring Diagram 5 1 Indoor Unit FSOAI Pro 92AE2 FSAI Pro 122AE2 ...
Страница 12: ...12 5 2 Outdoor Unit FSOAI Pro 92AE2 ...
Страница 13: ...13 FSOAI Pro 122AE2 ...
Страница 48: ...48 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1 ...
Страница 53: ...53 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3 ...
Страница 55: ...55 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Страница 56: ...56 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Страница 57: ...57 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Страница 58: ...58 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...