Configuration
The easy-Drive 200L must be configured prior to operation.
All configuration within the actuator is done by setting values in Modbus registers. Configuration software, providing a
visual interface to the registers, is available through your Emerson sales office or at
. Control
and monitoring can be done using any Modbus master (flow computer, PLC, PC).
See Appendix A for a full map of Modbus registers and their functions.
Control Method Configuration
There are 2 functional configurations available for the easyDrive electric actuator: On/Off and Positioning.
All available input signals are shown in table 2.
Table 2. All Available Input Signals
CONFIGURATION
ON/OFF
POSITIONING
Control Source
Modbus
Local
Modbus
Local
Input Signal
Modbus
Dual Dry Contact
Single Dry Contact
Modbus
4-20 mA (default)
Modbus setup
Use of a serial or USB to RS-485 device is required to connect to the actuator. Refer to manufacturer's requirements for
installation. The easyDrive 200L Modbus factory defaults are Address 1, 9600 baud, even parity, 1 stop bit, MSB.
When a connection has been achieved, the actuator may be configured as required for the application.
Figure 10. Fisher easy-Drive Configuration Software