JANUARY 2014
page
www.fisherstoves.co.nz
remember:
•
The flue system should rise vertically from the appliance with as few offsets as possible. Offsets should
be avoided where possible as each change in direction creates a resistance to airflow and makes flue
cleaning difficult.
•
The flue system must be well sealed with a minimum of fixings at each joint.
•
The flue pipe penetrating the chimney must continue to the minimum length of 4.6m from the top of the
floor protector to the cowl.
•
Flue exiting more than metres from the ridgeline must terminate no less than 1 metre above the roof
penetration (see diagram 1 below).
•
Where the top of the flue pipe is more than 2 metres above its highest fixing point, it must be stayed
against high winds.
9.
Drill and fix flue system into flue spigot with stainless steel self-tapping screws.
10.
Drill and secure the appliance to the floor protector using the two holes in the rear
legs of the appliance
FiTTiNG seismiC resTrAiNT
The Floor Protector must be mechanically fixed to the floor by bolting or screwing.
Note:
Floor Protector to be fixed by gluing when on a concrete floor that may have water pipes or electrical
wires present. The appliance can then be bolted to the floor protector with two 6mm x 50mm dynabolts.
BAFFLe
Before lighting your appliance for the first time, make sure the baffle is in the correct position being as far to
the rear as possible.