C1 Controllers and Transmitters

Instruction Manual

September 2009

13

RESET ADJUSTMENT KNOB

PROPORTIONAL BAND
ADJUSTMENT KNOB

PRESSURE SETTING
DIAL (KEY 6)

ADJUSTER SCREWS (KEY 48)

CALIBRATION ADJUSTER (KEY 36)

FLAPPER (KEY 40)

NOZZLE (KEY 54)

GE28281

B

E1060

PRESSURE SETTING KNOB
(KEY 58)

Figure 7. Proportional

Plus

Reset Controller Adjustment Locations

Proportional

Plus

Reset Controllers

This section describes the adjustments and
procedures for calibration and startup. The
adjustment locations are shown in figure 7 unless
otherwise specified. All adjustments must be made
with the cover open. When the adjustments and
calibration procedures are complete, close and latch
the cover. To better understand the adjustments and
overall operation of the controller, refer to the
Principle of Operation section in this manual for
proportional

plus

reset controllers. Refer also to the

schematic diagram in figure 13.

Adjustments

Adjustment: Set Point

Adjust the pressure setting knob by turning the knob
clockwise to increase the set point and
counterclockwise to decrease the set point.

Rotate the knob until the indicator points to the
desired set point pressure value. The pressure
setting dial will reflect the desired set point if the
controller is accurately calibrated.

Adjustment: Proportional Band

To adjust the proportional band, rotate the
proportional band adjustment knob to the desired
value.

The proportional band adjustment determines the
amount of change in controlled pressure required to
cause the control valve to stroke fully. It may be
adjusted from 3 to 100 percent for 0.2 to 1.0 bar (3
to 15 psig) or 6 to 100 percent for 0.4 to 2.0 bar (6 to
30 psig) of the nominal sensing element pressure
rating.

Adjustment: Reset

To adjust reset action turn the knob clockwise to
decrease the minutes per repeat. Turn the knob
counterclockwise to increase the minutes per repeat.
Increasing the minutes per repeat provides a slower
reset action.

The reset adjustment dial is calibrated in minutes per
repeat. By definition, this is the time in minutes
required for the reset action to produce an output
change which is equal to the change produced by
proportional control action. This is in effect, the time
in minutes required for the controller to increase (or
decrease) its output pressure by an amount equal to
a proportional increase (or decrease) caused by a
change in set point or process pressure.

Содержание C1B

Страница 1: ...Plus Reset Controllers 16 Differential Gap Controllers 16 Adjustments 16 Adjustment Set Point 16 Adjustment Proportional Band 17 Calibration Differential Gap Controllers 17 Startup Differential Gap Co...

Страница 2: ...ications for the C1 Series controllers and transmitters are listed in table 1 Table 2 explains available configurations and options Educational Services For information on available courses for C1 Ser...

Страница 3: ...0 4 to 2 0 bar 6 to 30 psig 0 12 normal m3 hour 4 5 scfh Supply and Output Connections 1 4 NPT internal Common Signal Pressure Conversions See table 6 Proportional Band Adjustment For Proportional Onl...

Страница 4: ...0 span Hazardous Area Classification Complies with the requirements of ATEX Group II Category 2 Gas and Dust Refer to figure 25 for location of ATEX marking Approximate Weight 8 2 kg 18 pounds Options...

Страница 5: ...0 mbar 0 to 10 inch Hg 0 to 1 0 bar 0 to 30 inch Hg 1 4 2 8 2 8 20 40 40 6 9 100 Compound Pressure 75 mbar vac to 75 mbar 30 inch wc vac to 30 inch wc 500 mbar vac to 500 mbar 15 inch Hg vac to 7 5 ps...

Страница 6: ...ve actuator mount the instrument according to the following instructions Mounting parts for the different actuator types and sizes vary Two typical actuator mounting installations are shown in figure...

Страница 7: ...irements of ISA Standard 7 0 01 A maximum 40 micrometer particle size in the air system is acceptable Further filtration down to 5 micrometer particle size is recommended Lubricant content is not to e...

Страница 8: ...r seal systems as needed in the process pressure lines If the instrument is located such that the adjacent process pressure lines will be approximately horizontal the lines should slope downward to th...

Страница 9: ...n in figure 4 unless otherwise specified All adjustments must be made with the cover open When the adjustments and calibration procedures are complete close and latch the cover To better understand th...

Страница 10: ...s must be dead ended into a pressure gauge The following procedures use a 0 2 to 1 0 bar 3 to 15 psig output pressure range as an example For a 0 4 to 2 0 bar 6 to 30 psig output range adjust the valu...

Страница 11: ...g screws key 48 and moving the calibration adjuster key 36 a small distance as indicated in figure 5 10 Repeat steps 4 through 9 until no further adjustment is necessary 11 Proceed to the startup proc...

Страница 12: ...example liquid pressure or liquid flow For slow processes example temperature calculate the percentage from the equation below For a slow process determine the initial proportional band setting in pe...

Страница 13: ...the indicator points to the desired set point pressure value The pressure setting dial will reflect the desired set point if the controller is accurately calibrated Adjustment Proportional Band To ad...

Страница 14: ...es per repeat fastest setting 4 Rotate the proportional band adjustment knob to 1 5 15 percent proportional band 5 Verify that the calibration adjuster screws key 48 are at mid position in the calibra...

Страница 15: ...1 do not watch the output gauge while changing the calibration adjuster The change in output is not a good indication of the change in span While moving the calibration adjuster IF OUTPUT IS BELOW 8 T...

Страница 16: ...or change the set point a small amount and check for system cycling If the system does not cycle then lower the proportional band raising the gain and disturb the system again Continue this procedure...

Страница 17: ...the proportional band assembly refer to figure 18 a Turn the proportional band assembly key 73 to 10 b Unscrew the spring adjustor key 65 removing the bias spring key 70 and washers key 62 with it c...

Страница 18: ...ressure with rising process pressure In the above example this pressure is 5 5 bar 80 psig b Increase pressure to the sensing element while monitoring the output pressure gauge The controller output p...

Страница 19: ...ly solely on the dial setting Monitor the process pressure and output pressure to be sure the desired settings are attained Adjustment Span The span adjustment is graduated from 0 to 10 A setting of 1...

Страница 20: ...adjust the span by loosening the two adjusting screws key 48 and moving the calibration adjuster key 36 a small distance as indicated in figure 12 9 Repeat steps 4 through 8 until no further adjustme...

Страница 21: ...e relay diaphragm and loading pressure controller output pressure registers on the small relay diaphragm A change in the process pressure moves the beam and flapper with respect to the nozzle by eithe...

Страница 22: ...ontrollers Action of a proportional plus reset controller is similar to that of a proportional only controller except that feedback from the controller output pressure is piped to a reset bellows as w...

Страница 23: ...is process continues rapidly until the controller output pressure is at the upper range limit The action of a differential gap controller is so rapid that output pressure changes from zero to maximum...

Страница 24: ...stem key 3 must be mounted on the supply pressure regulator CAUTION Before performing this procedure be sure the replacement gauges are the correct range so they are not damaged by overpressure Note K...

Страница 25: ...SCREW KEYS 40 AND 46 BELLOWS KEY 52 BELLOWS KEY 52 BELLOWS KEY 52 BELLOWS KEY 52 Figure 15 Reverse Direct Acting Tubing Connections for Proportional Controllers or Transmitter 3 Disconnect the contro...

Страница 26: ...acing Bellows Sensing Element Refer to figure 24 for key number locations unless otherwise directed 1 Shut off the supply pressure and process lines to the controller or transmitter 2 Disconnect the t...

Страница 27: ...ect the tubing check all connections for leaks and perform the appropriate calibration procedures Changing Anti Reset Windup Differential Relief Valve Refer to figure 23 for key number locations 1 Not...

Страница 28: ...sure produces decreasing output pressure to direct action increasing process pressure produces increasing output pressure or vice versa Changing the action is accomplished by reversing the positions o...

Страница 29: ...sembly key 37 Inspect the O rings key 77 located in the recessed area under the reversing block screw head and between the reversing block assembly and the calibration adjuster key 36 Replace these O...

Страница 30: ...Unscrew the machine screws key 41 figure 21 or 22 and remove the subassembly from the case 4 If the controller or transmitter uses a Bourdon tube sensing element disconnect the Bourdon tube from the...

Страница 31: ...art required as found in the following parts list WARNING Use only genuine Fisher replacement parts Components that are not supplied by Emerson Process Management should not under any circumstances be...

Страница 32: ...ecified Triple scale Stainless steel 0 2 0 bar 0 0 2 MPa and 0 30 psig 11B8584X022 0 20 bar 0 2 0 MPa and 0 300 psig 11B8584X012 0 69 bar 0 6 9 MPa and 0 1000 psig 11B8584X032 High Temp silicone 1N873...

Страница 33: ...0 0 400 0 700 0 700 0 1400 0 1400 0 30 0 30 0 60 0 60 0 100 0 100 0 200 0 200 32B1243X012 32B1243X212 2 32B1243X022 32B1243X172 2 32B1243X032 32B1243X202 2 32B1243X042 32B1243X162 2 0 2000 0 2000 0 40...

Страница 34: ...on steel zinc pl 36 Calibration Adjuster 37 Reversing Block 1 Z33520 zinc die casting 38 Sleeve 1 POM polyoxymethylene 39 Beam G10080 carbon steel zinc pl 40 Flapper 1 S30100 SST 41 Machine Screw stee...

Страница 35: ...r 71 Gauge Pressure Bellows input 3 Brass 0 150 mbar 0 60 inches wc positive 0 150 mbar 6 60 inches wc vacuum and 75 0 75 mbar 30 0 30 inches wc compound 1L3780000A2 0 250 mbar 0 100 inches wc positiv...

Страница 36: ...oportional Band Adjustment Knob steel PPS 74 Machine Screw 1 18 8 SST 2 req d 75 Gasket 1 Std Temp chloroprene 2 req d 1D397003012 High Temp silicone 2 req d 1N873604142 76 Nozzle O Ring 1 Std Temp ni...

Страница 37: ...r steel pl for Bourdon tube instruments 2 req d for bellows sensing instruments 4 req d 100 Bellows Yoke zinc use with gauge and differential pressure bellows Note Keys 101 through 105 are used for ga...

Страница 38: ...E PRESSURE BELLOWS SENSING ELEMENT SIDE VIEW OF SUBASSEMBLY WITH DIFFERENTIAL PRESSURE BELLOWS SENSING ELEMENT NOTES KEYS 33 46 AND 74 ARE NOT SHOWN KEY 52 IS FEEDBACK BELLOWS KEYS 71K 71L 71M ARE PAR...

Страница 39: ...67 For yoke mounting on 480 Vertical For yoke mounting on 1051 and 1052 Size 40 positions 1 and 3 w switch and Size 60 position 1 w switch All others Key Description 213 Mounting Plate steel continued...

Страница 40: ...Assembly steel For panel or wall mounting 2 req d 252 Cap Screw steel pl For panel or wall mounting 4 req d Note Specify quantity of fittings Connector Brass 1 4 NPT X 1 4 O D tubing 1 4 NPT X 3 8 O D...

Отзывы: