128-PQC
3
Table 3. Maximum Allowable Shutoff Pressure Drops
FLOWING
PORT
CADMIUM COLORED MAIN
SPRING 14A8831X012
RED MAIN SPRING 14A9077X012
SEATING
ACTUATOR
ACTION
FLOWING
PRESSURE
DROP
PORT
DIAMETER
0 to 20 Psig (0 or
1.4 Bar) Actuator
0 to 35 Psig (0 or
2.4 Bar) Actuator
0 to 20 Psig (0 or
1.4 Bar) Actuator
0 to 35 Psig (0 or
2.4 Bar) Actuator
SEATING
ACTION
DROP
TENDS TO:
Inches
mm
1.4 Bar) Actuator
Input Signal (2
Springs Required)
2.4 Bar) Actuator
Input Signal (4
Springs Required)
1.4 Bar) Actuator
Input Signal (2
Springs Required)
2.4 Bar) Actuator
Input Signal (4
Springs Required)
Inches
mm
Psi
Bar
Psi
Bar
Psi
Bar
Psi
Bar
Spring
Open valve
1/4
3/8
1/2
3/4
6.4
9.5
12.7
19.1
1510
520
220
30
104
36
15
2.1
3370
1340
690
240
232
92
47
16
3380
1340
700
240
233
92
48
16
3600
3120
1720
710
248
215
118
49
Metal
S ring
closes valve
Close valve
1/4
3/8
1/2
3/4
6.4
9.5
12.7
19.1
940
1130
1330
2030
65
78
92
140
1860
2450
2920
3600
128
169
201
248
1370
1540
1710
2320
94
106
118
160
2920
3300
3600
3600
201
227
248
248
Spring
opens valve
Close valve
1/4
3/8
1/2
3/4
6.4
9.5
12.7
19.1
170
530
540
1400
12
36
37
96
350
610
1150
2910
24
42
79
200
Valve will not shut off with this
combination of spring and application
Spring
Open valve
1/4
3/8
1/2
3/4
6.4
9.5
12.7
19.1
1000
710
400
160
69
49
28
11
1000
1000
830
350
69
69
57
24
1000
1000
830
360
69
69
57
25
1000
1000
1000
790
69
69
69
54
Soft
S ring
closes valve
Close valve
1/4
3/8
1/2
3/4
6.4
9.5
12.7
19.1
940
1000
1000
1000
65
69
69
69
1000
1000
1000
1000
69
69
69
69
1000
1000
1000
1000
69
69
69
69
1000
1000
1000
1000
69
69
69
69
Spring
opens valve
Close valve
1/4
3/8
1/2
3/4
6.4
9.5
12.7
19.1
560
480
540
1000
39
33
37
69
660
960
1000
1000
45
66
69
69
Valve will not shut off with this
combination of spring and application
Figure 2. Typical Nameplate
24B1860-B / DOC
Installation
WARNING
To avoid personal injury or property
damage resulting from the sudden re-
lease of pressure, do not install the
valve assembly where service condi-
tions could exceed the limits given in
this manual or on the appropriate name-
plates. The leakoff and spring case
vents must be kept open. Avoid danger
of fire or explosion from venting of flam-
mable or otherwise hazardous fluid into
a closed or poorly vented location by
providing adequate ventilation.
1. Before installing the valve, inspect the valve body
and associated equipment for any damage and for any
foreign material.
2. The control valve may be installed in any orienta-
tion. However, the normal method is with the actuator
above the valve, especially for an angle configuration.