14
CABINET PREPARATION
1)
The range is a free standing unit. If the unit is to be placed adjacent to cabinets, the clearances
shown in fig. 10 (RGS-48 & 36) & fig. 12 (RGS-305) are required. The same clearances apply to island
installations.
2)
The range can be placed in various positions with respect to the cabinet front, with the front frame
either flush or projecting, depending on the countertop depth.
3)
The gas and electrical supply should be within the zones shown (fig. 10 & 12).
4)
The maximum depth of over head cabinets installed on either side of the hood is 13”.
5)
Any openings in the wall behind the range and in the floor under the range must be sealed.
6)
When there is less than a 12” clearance between combustible material and the back edge of the
range, (above the cooking surface) a DCS backguard must be installed, (fig. 11 page 12).
When clearance to combustible material is over 12” no backguard is necessary (fig. 11 page 12).
Backguards must be ordered separately. Fig. 11 indicates the space required for each
type of backguard.
7)
Always keep the appliance area clear and free from combustible materials, gasoline and other
flammable vapors and liquids.
8)
Do not obstruct the flow of combustion and ventilation air to the unit.
min. 36" wide hood
CAUTION:
36" min. to
combustible
material
,
from cooking
surface
electrical
supply
gas supply
35-3/8" max. for level counter,
36-3/4" max. with range
leveling legs fully extended
12" min. to combustible
material
, each side
cooking surface
1 2 "
B
A
A
min. 48" wide hood
3-1/4 "
3-1/2 "
1 8" Min.
1 3 "
Max
A B
RGS 48 models = 8" 16"
RGS 36 models = 4" 12"
∆
As defined in the “National Fuel Gas Code”
(ANSI Z223.1, lastest edition).
The horizontal surfaces of the range top (cooktop)
trim must not
be below countertop
level.
Fig. 10 RGS 48” & 36” Models Only
Содержание DCS RGS Series
Страница 24: ...23 NOTES...
Страница 25: ...NOTES 24...